EATON - MOELLER PKNM-10/1N/C/01-MW PKNM-10/1N/C/01-MW 236078 EATON ELECTRIC RCD/MCB combination switch, 10A, 100mA, miniature circuit-br. type .. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PKNM-10/1N/C/01-MW 236078 EATON ELECTRIC RCD/MCB combination switch, 10A, 100mA, miniature circuit-br. type ..

PKNM-10/1N/C/01-MW

236078

EATON - MOELLER

1 Pcs.

RCD/MCB combination switch, 10A, 100mA, miniature circuit-br. type C trip characteristic, 1-ph+N, residual current circuit-br. trip characteristic: AC

Automation > Earth leakage circuit breaker

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The PKNM-10/1N/C/01-MW Eaton Moeller RCD/MCB combination switch combines a miniature circuit breaker and residual current device into a unified modular assembly. Technicians apply these components to safeguard individual circuits against thermal overloads, short circuits, and dangerous earth leakages.

Pricing, availability, and lead time are confirmed per enquiry through an RFQ.

  • Rated operational current for specified heat dissipation: I n
  • Heat dissipation per pole, current-dependent: P vid
  • Equipment heat dissipation, current-dependent: P vid
  • Static heat dissipation, non-current-dependent: P vs
  • Heat dissipation capacity: P diss
  • Number of poles (total) (EF008618): 2
  • Number of protected poles (EF005548): 1
  • Rated current (EF000227): 10 A
  • Rated fault current (EF002358): 0.1 A
  • Leakage current type (EF002560): AC
  • Current limiting class (EF002568): 3
  • Surge current capacity (EF002564): 0.25 kA
  • Voltage type (EF000187): AC
  • Frequency (EF005455): 50 Hz
  • Release characteristic (EF000889): C
  • Concurrently switching neutral conductor (EF005997): Yes

More info

▲
Design verification as per IEC/EN 61439(Show features)(Hide features)
Technical data for design verification
Rated operational current for specified heat dissipation
In A 10
Heat dissipation per pole, current-dependent
Pvid W 0
Equipment heat dissipation, current-dependent
Pvid W 2.5
Static heat dissipation, non-current-dependent
Pvs W 0
Heat dissipation capacity
Pdiss W 0
Operating ambient temperature min.
°C -25
Operating ambient temperature max.
°C 40
0
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 6.0
Circuit breakers and fuses (EG000020) / Earth leakage circuit breaker (EC000905)
Electric engineering, automation, process control engineering / Electrical installation, device / Residual current protection system / MCB/RCCB combination ([email protected] [AFZ810012])
Number of poles (total)
2
Number of protected poles
1
Nominal rated voltage
V 230
Nominal rated current
A 10
Rated fault current
A 0.1
Leakage current type
AC
Current limiting class
3
Rated short-circuit breaking capacity EN 60898
kA 10
Rated short-circuit breaking capacity IEC 60947-2
kA 0
Frequency
50 Hz
Release characteristic
C
Concurrently switching N-neutral
Yes
Over voltage category
3
Pollution degree
2
Width in number of modular spacings
2
Built-in depth
mm 70
Suitable for flush-mounted installation
No
Degree of protection (IP)
IP20
Surge current capacity
kA 0.25
Voltage type
AC
Antinuisance tripping version
No

Product Datasheet