View larger
NZMN2-AF70-BT-NA 107640 Y7-107640 EATON ELECTRIC Circuit-breaker, 3p, 70A, box terminals
NZMN2-AF70-BT-NA
107640
Y7-107640
EATON - MOELLER
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Electrical panels utilize molded case circuit breakers like the NZMN2-AF70-BT-NA 107640 Y7-107640 EATON ELECTRIC Circuit-breaker, 3p, 70A, box terminals to protect branch circuits and industrial machinery from thermal overloads and short-circuit events. These protective devices automatically disconnect power when fault thresholds are exceeded.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 70 A
- Rated voltage (EF003977): 690 V
- Overload release current setting (EF002336): 70 A
- Adjustment range undelayed short-circuit release (EF007131): 6 A
- Power loss (EF005387): None W
- Device construction (EF008240): Built-in device fixed built-in technique
- Integrated earth fault protection (EF007296): false
- Type of electrical connection of main circuit (EF006819): Frame clamp
- Suitable for DIN rail (top hat rail) mounting (EF007250): false
- DIN rail (top hat rail) mounting optional (EF008904): true
- With switched-off indicator (EF007006): false
- With integrated under voltage release (EF001390): false
- Number of poles (EF001391): 3
- Position of connection for main current circuit (EF006671): Front side
- Type of control element (EF006976): Rocker lever
- Complete device with protection unit (EF008906): true
More info
▲General specifications
CSA (File No. 22086)
UL (File No. E31593)
UL listed
CE marking
IEC
IEC 60947-2
CSA (Class No. 1432-01)
UL 489
Specially designed for North America
CSA-C22.2 No. 5-09
UL (Category Control Number DIVQ)
CSA certified
IEC/EN 60947
Product specifications
- Branch circuits, feeder circuits
- Use in unearthed supply systems at 690 V
Motor drive optional
DIN rail (top hat rail) mounting optional
Built-in device fixed built-in technique
Damp heat, cyclic, to IEC 60068-2-30
300 V AC (between the auxiliary contacts)
IP20 (basic degree of protection, in the operating controls area)
300 A (415 V AC-1, making and breaking capacity)
70 A (660-690 V AC-3, making and breaking capacity)
300 A (380/400 V AC-1, making and breaking capacity)
IP40 (with insulating surround)
IP10 (tunnel terminal)
Min. 2 segments of 9 mm x 0.8 mm at box terminal
Max. 10 segments of 16 mm x 0.8 mm at box terminal
Max. 10 segments of 16 mm x 0.8 mm at rear-side connection (punched)
6500 operations at 400 V AC-3
5000 operations at 690 V AC-3
6500 operations at 415 V AC-3
7500 operations at 690 V AC-1
Current limiting circuit breaker
16 mm² - 18 mm² (2x)
Max. 20 mm x 5 mm direct at switch rear-side connection
Min. 16 mm x 5 mm direct at switch rear-side connection
6 mm² - 11 mm² (1x) direct at switch rear-side connection
16 mm² (1x) at tunnel terminal
4 mm² - 350 mm² (1x) at box terminal
4 mm² - 350 mm² (1x) at tunnel terminal