View larger
NZMH3-AEF600-NA 269290 Y7-269290 EATON ELECTRIC Circuit-breaker, 3p, 600A
NZMH3-AEF600-NA
269290
Y7-269290
EATON - MOELLER
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller circuit-breaker (NZMH3-AEF600-NA) functions as a heavy-duty industrial circuit protection device designed to interrupt high fault currents and protect primary electrical networks. Molded case breakers of this caliber are standard in industrial facilities for dependable feeder protection.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 600 A
- Rated voltage (EF003977): 690 V
- Overload release current setting (EF002336): 600 A
- Adjustment range undelayed short-circuit release (EF007131): 1200 A
- Device construction (EF008240): Built-in device fixed built-in technique
- Integrated earth fault protection (EF007296): No
- Type of electrical connection of main circuit (EF006819): Screw connection
- Suitable for DIN rail (top hat rail) mounting (EF007250): No
- DIN rail (top hat rail) mounting optional (EF008904): No
- With switched-off indicator (EF007006): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Position of connection for main current circuit (EF006671): Front
- Type of control element (EF006976): Rocker lever
- Complete device with protection unit (EF008906): Yes
- Motor drive integrated (EF006697): No
More info
▲General specifications
UL/CSA
UL (File No. E31593)
UL (Category Control Number DIVQ)
IEC/EN 60947
UL 489
CSA-C22.2 No. 5-09
CSA (Class No. 1432-01)
CE marking
IEC
UL listed
IEC 60947-2
Specially designed for North America
CSA certified
Product specifications
- Branch circuits, feeder circuits
- Use in unearthed supply systems at 690 V
Motor drive optional
Fixed
Damp heat, cyclic, to IEC 60068-2-30
300 V AC (between the auxiliary contacts)
IP20
630 A (380/400 V AC-1, making and breaking capacity)
450 A (660-690 V AC-3, making and breaking capacity)
500 A (415 V AC-1, making and breaking capacity)
IP66 (with door coupling rotary handle)
IP00 (terminations, phase isolator and strip terminal)
Min. 6 segments of 16 mm x 0.8 mm at rear-side connection (punched)
Max. 10 segments of 32 mm x 1 mm + 5 segments of 32 mm x 1 mm at rear-side connection (punched)
10 segments of 50 mm x 1 mm (2x) at rear-side width extension
Max. 8 segments of 24 mm x 1 mm (2x) at box terminal
Max. 10 segments of 24 mm x 1 mm + 5 segments of 24 mm x 1 mm
2000 operations at 400 V AC-3
2000 operations at 690 V AC-3
2000 operations at 415 V AC-3
5000 operations at 400 V AC-1
Current limiting circuit breaker
14 mm² - 18 mm² (1x)
Max. 10 mm x 50 mm (2x) at rear-side width extension
Min. 20 mm x 5 mm direct at switch rear-side connection
16 mm² - 185 mm² (1x) at tunnel terminal
350 mm² (2x) direct at switch rear-side connection
2 mm² - 500 mm² (1x) at box terminal
4 mm² - 350 mm² (1x) at tunnel terminal