NZMH2-AF45-BT-NA 107815 Y7-107815 EATON ELECTRIC Circuit-breaker, 3p, 45A, box terminals
NZMH2-AF45-BT-NA
107815
Y7-107815
EATON - MOELLER
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Eaton Moeller NZMH2-AF45-BT-NA circuit-breaker is utilized in control panels and power distribution architectures to safely interrupt electrical flow during fault conditions, protecting downstream wiring and equipment. Industrial applications rely on these devices to maintain electrical safety margins. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 45 A
- Rated voltage (EF003977): 690 V
- Overload release current setting (EF002336): 45 A
- Adjustment range undelayed short-circuit release (EF007131): 6 A
- Device construction (EF008240): Built-in device fixed built-in technique
- Integrated earth fault protection (EF007296): No
- Type of electrical connection of main circuit (EF006819): Frame clamp
- Suitable for DIN rail (top hat rail) mounting (EF007250): No
- DIN rail (top hat rail) mounting optional (EF008904): Yes
- With switched-off indicator (EF007006): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Position of connection for main current circuit (EF006671): Front
- Type of control element (EF006976): Rocker lever
- Complete device with protection unit (EF008906): Yes
- Motor drive integrated (EF006697): No
More info
▲General specifications
IEC
UL (File No. E31593)
IEC 60947-2
Specially designed for North America
UL listed
UL/CSA
UL (Category Control Number DIVQ)
CSA (File No. 22086)
UL 489
IEC/EN 60947
CSA (Class No. 1432-01)
CSA-C22.2 No. 5-09
CSA certified
Product specifications
- Branch circuits, feeder circuits
- Use in unearthed supply systems at 690 V
Motor drive optional
DIN rail (top hat rail) mounting optional
Fixed
Damp heat, cyclic, to IEC 60068-2-30
500 V AC (between auxiliary contacts and main contacts)
IP20 (basic degree of protection, in the operating controls area)
45 A (660-690 V AC-3, making and breaking capacity)
300 A (380/400 V AC-1, making and breaking capacity)
300 A (415 V AC-1, making and breaking capacity)
IP66 (with door coupling rotary handle)
IP10 (tunnel terminal)
Min. 2 segments of 9 mm x 0.8 mm at box terminal
Min. 2 segements of 16 mm x 0.8 mm at rear-side connection (punched)
Max. 10 segments of 16 mm x 0.8 mm at rear-side connection (punched)
6500 operations at 400 V AC-3
5000 operations at 690 V AC-3
10000 operations at 400 V AC-1
6500 operations at 415 V AC-3
System and cable protection
16 mm² - 18 mm² (2x)
Max. 20 mm x 5 mm direct at switch rear-side connection
M8 at rear-side screw connection
6 mm² - 12 mm² (1x) at box terminal
6 mm² - 11 mm² (1x) direct at switch rear-side connection
4 mm² - 350 mm² (1x) at tunnel terminal
4 mm² - 3/0 mm² (1x) direct at switch rear-side connection