View larger
NZMH2-A25-NA 269229 Y7-269229 EATON ELECTRIC Circuit-breaker, 3p, 25A
NZMH2-A25-NA
269229
Y7-269229
EATON - MOELLER
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Protection against overloads and short circuits in motor control centers and power distribution boards is handled efficiently by the NZMH2-A25-NA 269229 Y7-269229 EATON ELECTRIC Circuit-breaker, 3p, 25A. Electrical engineers utilize these three-pole circuit breakers to safeguard branch circuits and ensure rapid disconnection during fault events. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 25 A
- Rated voltage (EF003977): 690 V
- Overload release current setting (EF002336): 20 A
- Adjustment range undelayed short-circuit release (EF007131): 350 A
- Device construction (EF008240): Built-in device fixed built-in technique
- Integrated earth fault protection (EF007296): No
- Type of electrical connection of main circuit (EF006819): Screw connection
- Suitable for DIN rail (top hat rail) mounting (EF007250): No
- DIN rail (top hat rail) mounting optional (EF008904): Yes
- With switched-off indicator (EF007006): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Position of connection for main current circuit (EF006671): Front
- Type of control element (EF006976): Rocker lever
- Complete device with protection unit (EF008906): Yes
- Motor drive integrated (EF006697): No
More info
▲General specifications
CSA (Class No. 1432-01)
IEC/EN 60947
UL 489
CE marking
UL (Category Control Number DIVQ)
CSA-C22.2 No. 5-09
IEC 60947-2
CSA (File No. 22086)
UL (File No. E31593)
Specially designed for North America
UL/CSA
IEC
CSA certified
Product specifications
- Branch circuits, feeder circuits
- Use in unearthed supply systems at 690 V
Motor drive optional
DIN rail (top hat rail) mounting optional
Fixed
Damp heat, cyclic, to IEC 60068-2-30
500 V AC (between auxiliary contacts and main contacts)
IP20
300 A (380/400 V AC-1, making and breaking capacity)
300 A (415 V AC-1, making and breaking capacity)
25 A (660-690 V AC-3, making and breaking capacity)
IP66 (with door coupling rotary handle)
IP10 (tunnel terminal)
Min. 2 segements of 16 mm x 0.8 mm at rear-side connection (punched)
Min. 2 segments of 9 mm x 0.8 mm at box terminal
Max. 10 segments of 16 mm x 0.8 mm at box terminal
5000 operations at 690 V AC-3
6500 operations at 415 V AC-3
7500 operations at 690 V AC-1
6500 operations at 400 V AC-3
Current limiting circuit breaker
14 mm² - 18 mm² (1x)
Min. 16 mm x 5 mm direct at switch rear-side connection
Max. 20 mm x 5 mm direct at switch rear-side connection
16 mm² (1x) at tunnel terminal
6 mm² - 11 mm² (1x) direct at switch rear-side connection
4 mm² - 3/0 mm² (1x) direct at switch rear-side connection
4 mm² - 350 mm² (1x) at box terminal