View larger
NZMH2-A250-NA 271107 Y7-271107 EATON ELECTRIC Circuit-breaker, 3p, 250A
NZMH2-A250-NA
271107
Y7-271107
EATON - MOELLER
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A reliable component for electrical distribution, the NZMH2-A250-NA 271107 Y7-271107 EATON ELECTRIC circuit-breaker provides essential overcurrent protection in commercial and industrial networks. Thermal-magnetic circuit breakers of this type safely interrupt fault currents to prevent damage to downstream wiring and connected electrical machinery.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 250 A
- Rated voltage (EF003977): 690 V
- Overload release current setting (EF002336): 200 A
- Adjustment range undelayed short-circuit release (EF007131): 1500 A
- Device construction (EF008240): Built-in device fixed built-in technique
- Integrated earth fault protection (EF007296): No
- Type of electrical connection of main circuit (EF006819): Screw connection
- Suitable for DIN rail (top hat rail) mounting (EF007250): No
- DIN rail (top hat rail) mounting optional (EF008904): Yes
- With switched-off indicator (EF007006): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Position of connection for main current circuit (EF006671): Front
- Type of control element (EF006976): Rocker lever
- Complete device with protection unit (EF008906): Yes
- Motor drive integrated (EF006697): No
More info
▲General specifications
CE marking
UL/CSA
IEC 60947-2
UL listed
IEC/EN 60947
UL (Category Control Number DIVQ)
CSA-C22.2 No. 5-09
CSA (Class No. 1432-01)
UL 489
Specially designed for North America
IEC
CSA (File No. 22086)
UL (File No. E31593)
Product specifications
- Branch circuits, feeder circuits
- Use in unearthed supply systems at 690 V
Motor drive optional
Fixed
DIN rail (top hat rail) mounting optional
Damp heat, cyclic, to IEC 60068-2-30
500 V AC (between auxiliary contacts and main contacts)
IP20 (basic degree of protection, in the operating controls area)
300 A (415 V AC-1, making and breaking capacity)
300 A (380/400 V AC-1, making and breaking capacity)
250 A (690 V AC-1, making and breaking capacity)
IP40 (with insulating surround)
IP00 (terminations, phase isolator and strip terminal)
Min. 2 segments of 9 mm x 0.8 mm at box terminal
Max. 10 segments of 16 mm x 0.8 mm at rear-side connection (punched)
Max. 10 segments of 16 mm x 0.8 mm at box terminal
6500 operations at 415 V AC-3
10000 operations at 400 V AC-1
6500 operations at 400 V AC-3
7500 operations at 690 V AC-1
System and cable protection
14 mm² - 18 mm² (1x)
Min. 16 mm x 5 mm direct at switch rear-side connection
M8 at rear-side screw connection
6 mm² - 12 mm² (1x) at box terminal
6 mm² - 11 mm² (1x) direct at switch rear-side connection
4 mm² - 350 mm² (1x) at tunnel terminal
4 mm² - 3/0 mm² (1x) direct at switch rear-side connection