View larger
NZMN2-SE220-CNA 271162 Y7-271162 EATON ELECTRIC Circuit-breaker, 3p, 220A
NZMN2-SE220-CNA
271162
Y7-271162
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Circuit-breaker, 3p, 220A identified by part number NZMN2-SE220-CNA from Eaton Moeller is an electronic switching device utilized for primary distribution and high-capacity industrial circuit protection. These robust units interrupt dangerous fault currents and safeguard heavy electrical distribution infrastructure across large manufacturing facilities.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 0 A
- Adjustment range undelayed short-circuit release (EF007131): 440 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): No
- Switch off technique (EF007007): Electronic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 220 A
- Rated operation power at AC-3, 230 V (EF007025): 55 kW
- Rated operation power at AC-3, 400 V (EF001364): 110 kW
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rocker lever
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Degree of protection (IP) (EF005474): IP20
More info
▲General specifications
CSA (File No. 22086)
CSA-C22.2 No. 5-09
IEC
Specially designed for North America
CE marking
UL listed
UL/CSA
CSA certified
UL (File No. E31593)
UL (Category Control Number DKPU2)
IEC 60947-2
IEC/EN 60947
CSA (Class No. 1432-01)
Product specifications
- Branch circuits, feeder circuits
- Use in unearthed supply systems at 690 V
Fixed
Damp heat, cyclic, to IEC 60068-2-30
500 V AC (between auxiliary contacts and main contacts)
IP20
220 A (660-690 V AC-3, making and breaking capacity)
300 A (415 V AC-1, making and breaking capacity)
300 A (400 V AC-1, making and breaking capacity)
IP66 (with door coupling rotary handle)
IP10 (tunnel terminal)
Min. 2 segments of 9 mm x 0.8 mm at box terminal
Max. 10 segments of 16 mm x 0.8 mm at box terminal
Max. 10 segments of 16 mm x 0.8 mm at rear-side connection (punched)
6500 operations at 415 V AC-3
7500 operations at 690 V AC-1
6500 operations at 400 V AC-3
5000 operations at 690 V AC-3
16 mm² - 18 mm² (2x)
Min. 16 mm x 5 mm direct at switch rear-side connection
M8 at rear-side screw connection
6 mm² - 11 mm² (1x) direct at switch rear-side connection
16 mm² (1x) at tunnel terminal
4 mm² - 3/0 mm² (1x) direct at switch rear-side connection
4 mm² - 350 mm² (1x) at box terminal