View larger
NZMN2-S200-CNA 269262 Y7-269262 EATON ELECTRIC Circuit-breaker, 3p, 200A
NZMN2-S200-CNA
269262
Y7-269262
EATON - MOELLER
1 Pcs.
Automation > Motor protection circuit-breaker
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Eaton Moeller NZMN2-S200-CNA (NZMN2-S200-CNA 269262 Y7-269262 EATON ELECTRIC Circuit-breaker, 3p, 200A) is a magnetic circuit breaker designed to offer dependable short-circuit protection in industrial power distribution panels. Technicians rely on such units to swiftly isolate electrical faults and safeguard downstream distribution assets.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 0 A
- Adjustment range undelayed short-circuit release (EF007131): 8 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): No
- Switch off technique (EF007007): Magnetic
- Rated operating voltage (EF001435): 690 V
- Rated operation power at AC-3, 230 V (EF007025): 55 kW
- Rated operation power at AC-3, 400 V (EF001364): 110 kW
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rocker lever
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Degree of protection (IP) (EF005474): IP20
- Height (EF000040): 195 mm
More info
▲General specifications
UL listed
CE marking
IEC
CSA (Class No. 1432-01)
IEC 60947-2
CSA certified
Specially designed for North America
UL (File No. E31593)
CSA-C22.2 No. 5-09
UL/CSA
IEC/EN 60947
CSA (File No. 22086)
UL (Category Control Number DKPU2)
Product specifications
- Branch circuits, feeder circuits
- Use in unearthed supply systems at 690 V
Built-in device fixed built-in technique
Damp heat, constant, to IEC 60068-2-78
500 V AC (between auxiliary contacts and main contacts)
IP20
300 A (415 V AC-1, making and breaking capacity)
300 A (400 V AC-1, making and breaking capacity)
200 A (660-690 V AC-3, making and breaking capacity)
IP66 (with door coupling rotary handle)
IP10 (tunnel terminal)
Min. 2 segments of 9 mm x 0.8 mm at box terminal
Max. 10 segments of 16 mm x 0.8 mm at rear-side connection (punched)
Min. 2 segements of 16 mm x 0.8 mm at rear-side connection (punched)
6500 operations at 400 V AC-3
6500 operations at 415 V AC-3
5000 operations at 690 V AC-3
7500 operations at 690 V AC-1
14 mm² - 18 mm² (1x)
M8 at rear-side screw connection
Min. 16 mm x 5 mm direct at switch rear-side connection
6 mm² - 11 mm² (1x) direct at switch rear-side connection
6 mm² - 12 mm² (1x) at box terminal
4 mm² - 3/0 mm² (1x) direct at switch rear-side connection
4 mm² - 350 mm² (1x) at tunnel terminal