View larger
NZMH2-VEF175-NA 271132 Y7-271132 EATON ELECTRIC Circuit-breaker, 3p, 175A
NZMH2-VEF175-NA
271132
Y7-271132
EATON - MOELLER
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An NZMH2-VEF175-NA 271132 Y7-271132 EATON ELECTRIC Circuit-breaker, 3p, 175A is an automatic switching device used to safeguard electrical wiring and connected loads from dangerous current spikes and thermal overloads. Panel builders and system integrators integrate these breakers into power distribution layouts for reliable circuit protection.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 175 A
- Rated voltage (EF003977): 690 V
- Overload release current setting (EF002336): 175 A
- Adjustment range undelayed short-circuit release (EF007131): 2100 A
- Device construction (EF008240): Built-in device fixed built-in technique
- Integrated earth fault protection (EF007296): No
- Type of electrical connection of main circuit (EF006819): Screw connection
- Suitable for DIN rail (top hat rail) mounting (EF007250): No
- DIN rail (top hat rail) mounting optional (EF008904): Yes
- With switched-off indicator (EF007006): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Position of connection for main current circuit (EF006671): Front
- Type of control element (EF006976): Rocker lever
- Complete device with protection unit (EF008906): Yes
- Motor drive integrated (EF006697): No
More info
▲General specifications
CSA (File No. 22086)
CSA certified
Specially designed for North America
UL (Category Control Number DIVQ)
UL (File No. E31593)
IEC 60947-2
CSA-C22.2 No. 5-09
IEC/EN 60947
CE marking
UL listed
UL/CSA
IEC
CSA (Class No. 1432-01)
Product specifications
- Branch circuits, feeder circuits
- Use in unearthed supply systems at 690 V
Protection unit
DIN rail (top hat rail) mounting optional
Fixed
Damp heat, constant, to IEC 60068-2-78
500 V AC (between auxiliary contacts and main contacts)
IP20 (basic degree of protection, in the operating controls area)
300 A (415 V AC-1, making and breaking capacity)
175 A (660-690 V AC-3, making and breaking capacity)
300 A (380/400 V AC-1, making and breaking capacity)
IP66 (with door coupling rotary handle)
IP00 (terminations, phase isolator and strip terminal)
Min. 2 segments of 9 mm x 0.8 mm at box terminal
Max. 10 segments of 16 mm x 0.8 mm at rear-side connection (punched)
Min. 2 segements of 16 mm x 0.8 mm at rear-side connection (punched)
7500 operations at 690 V AC-1
6500 operations at 400 V AC-3
10000 operations at 400 V AC-1
5000 operations at 690 V AC-3
Current limiting circuit breaker
14 mm² - 18 mm² (1x)
Min. 16 mm x 5 mm direct at switch rear-side connection
Max. 20 mm x 5 mm direct at switch rear-side connection
16 mm² (1x) at tunnel terminal
6 mm² - 12 mm² (1x) at box terminal
4 mm² - 350 mm² (1x) at box terminal
4 mm² - 350 mm² (1x) at tunnel terminal