View larger
NZMN2-AF15-BT-NA 107631 Y7-107631 EATON ELECTRIC Circuit-breaker, 3p, 15A, box terminals
NZMN2-AF15-BT-NA
107631
Y7-107631
EATON - MOELLER
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Cataloged under part number NZMN2-AF15-BT-NA, this Eaton Moeller NZMN2-AF15-BT-NA 107631 Y7-107631 EATON ELECTRIC Circuit-breaker, 3p, 15A, box terminals functions as a molded case circuit breaker to safeguard electrical circuits against excessive current loads and short-circuit faults. Such components are frequently deployed in industrial control panels to protect sensitive equipment and wiring.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 15 A
- Rated voltage (EF003977): 690 V
- Overload release current setting (EF002336): 15 A
- Adjustment range undelayed short-circuit release (EF007131): 350 A
- Power loss (EF005387): None W
- Device construction (EF008240): Built-in device fixed built-in technique
- Integrated earth fault protection (EF007296): false
- Type of electrical connection of main circuit (EF006819): Frame clamp
- Suitable for DIN rail (top hat rail) mounting (EF007250): false
- DIN rail (top hat rail) mounting optional (EF008904): true
- With switched-off indicator (EF007006): false
- With integrated under voltage release (EF001390): false
- Number of poles (EF001391): 3
- Position of connection for main current circuit (EF006671): Front side
- Type of control element (EF006976): Rocker lever
- Complete device with protection unit (EF008906): true
More info
▲General specifications
UL 489
CE marking
UL listed
CSA-C22.2 No. 5-09
UL (Category Control Number DIVQ)
UL (File No. E31593)
CSA (Class No. 1432-01)
Specially designed for North America
IEC
CSA (File No. 22086)
CSA certified
IEC/EN 60947
UL/CSA
Product specifications
- Branch circuits, feeder circuits
- Use in unearthed supply systems at 690 V
Protection unit
Built-in device fixed built-in technique
Fixed
Damp heat, cyclic, to IEC 60068-2-30
300 V AC (between the auxiliary contacts)
IP20
300 A (415 V AC-1, making and breaking capacity)
15 A (660-690 V AC-3, making and breaking capacity)
15 A (690 V AC -1, making and breaking capacity)
IP66 (with door coupling rotary handle)
IP10 (tunnel terminal)
Max. 10 segments of 16 mm x 0.8 mm at box terminal
Min. 2 segements of 16 mm x 0.8 mm at rear-side connection (punched)
Min. 2 segments of 9 mm x 0.8 mm at box terminal
7500 operations at 690 V AC-1
6500 operations at 415 V AC-3
10000 operations at 400 V AC-1
5000 operations at 690 V AC-3
Current limiting circuit breaker
16 mm² - 18 mm² (2x)
Min. 16 mm x 5 mm direct at switch rear-side connection
Max. 20 mm x 5 mm direct at switch rear-side connection
6 mm² - 12 mm² (1x) at box terminal
16 mm² (1x) at tunnel terminal
4 mm² - 350 mm² (1x) at box terminal
4 mm² - 350 mm² (1x) at tunnel terminal