NZMN2-SE140-CNA 271161 Y7-271161 EATON ELECTRIC Circuit-breaker, 3p, 140A produced by Eaton Moeller is an electronic circuit breaker used to control and protect medium-to-large electrical power distribution lines. Devices of this type provide precise electronic trip curves for safeguarding complex industrial power systems.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Overload release current setting (EF002336): 0 A
- Adjustment range undelayed short-circuit release (EF007131): 280 A
- With thermal overload protection (EF006233): No
- Phase failure sensitive (EF007400): No
- Switch off technique (EF007007): Electronic
- Rated operating voltage (EF001435): 690 V
- Rated permanent current Iu (EF001389): 140 A
- Rated operation power at AC-3, 230 V (EF007025): 45 kW
- Rated operation power at AC-3, 400 V (EF001364): 75 kW
- Type of electrical connection of main circuit (EF006819): Screw connection
- Type of control element (EF006976): Rocker lever
- Device construction (EF008240): Built-in device fixed built-in technique
- With integrated auxiliary switch (EF001387): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Degree of protection (IP) (EF005474): IP20
More info
▲General specifications
IEC
UL listed
CSA (Class No. 1432-01)
UL (File No. E31593)
Specially designed for North America
CE marking
CSA certified
CSA (File No. 22086)
UL/CSA
UL (Category Control Number DKPU2)
IEC 60947-2
IEC/EN 60947
CSA-C22.2 No. 5-09
Product specifications
- Branch circuits, feeder circuits
- Use in unearthed supply systems at 690 V
Fixed
Damp heat, constant, to IEC 60068-2-78
500 V AC (between auxiliary contacts and main contacts)
IP20
140 A (690 V AC-1, making and breaking capacity)
300 A (400 V AC-1, making and breaking capacity)
140 A (660-690 V AC-3, making and breaking capacity)
IP40 (with insulating surround)
IP10 (tunnel terminal)
Min. 2 segments of 9 mm x 0.8 mm at box terminal
Max. 10 segments of 16 mm x 0.8 mm at rear-side connection (punched)
Max. 10 segments of 16 mm x 0.8 mm at box terminal
6500 operations at 415 V AC-3
5000 operations at 690 V AC-3
10000 operations at 400 V AC-1
7500 operations at 690 V AC-1
14 mm² - 18 mm² (1x)
Min. 16 mm x 5 mm direct at switch rear-side connection
Max. 20 mm x 5 mm direct at switch rear-side connection
6 mm² - 11 mm² (1x) direct at switch rear-side connection
16 mm² (1x) at tunnel terminal
4 mm² - 3/0 mm² (1x) direct at switch rear-side connection
4 mm² - 350 mm² (1x) at tunnel terminal