View larger
NZMN2-SE140-BT-CNA 107850 Y7-107850 EATON ELECTRIC Circuit-breaker, 3p, 140A, box terminals
NZMN2-SE140-BT-CNA
107850
Y7-107850
EATON - MOELLER
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller circuit breaker, cataloged as NZMN2-SE140-BT-CNA 107850 Y7-107850 EATON ELECTRIC Circuit-breaker, 3p, 140A, box terminals, provides reliable fault protection for industrial electrical circuits. It prevents system damage by automatically disconnecting the power supply when dangerous overcurrents occur.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 140 A
- Rated voltage (EF003977): 690 V
- Overload release current setting (EF002336): 0 A
- Adjustment range undelayed short-circuit release (EF007131): 280 A
- Device construction (EF008240): Built-in device fixed built-in technique
- Integrated earth fault protection (EF007296): No
- Type of electrical connection of main circuit (EF006819): Frame clamp
- Suitable for DIN rail (top hat rail) mounting (EF007250): No
- DIN rail (top hat rail) mounting optional (EF008904): Yes
- With switched-off indicator (EF007006): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Position of connection for main current circuit (EF006671): Front
- Type of control element (EF006976): Rocker lever
- Complete device with protection unit (EF008906): Yes
- Motor drive integrated (EF006697): No
More info
▲General specifications
UL/CSA
IEC
UL (File No. E31593)
Specially designed for North America
IEC 60947-2
CSA-C22.2 No. 5-09
IEC/EN 60947
CSA certified
UL (Category Control Number DKPU2)
CSA (File No. 22086)
CE marking
UL listed
CSA (Class No. 1432-01)
Product specifications
- Branch circuits, feeder circuits
- Use in unearthed supply systems at 690 V
Protection unit
DIN rail (top hat rail) mounting optional
Fixed
Damp heat, constant, to IEC 60068-2-78
300 V AC (between the auxiliary contacts)
IP20
140 A (660-690 V AC-3, making and breaking capacity)
140 A (690 V AC -1, making and breaking capacity)
300 A (380/400 V AC-1, making and breaking capacity)
IP66 (with door coupling rotary handle)
IP10 (tunnel terminal)
Min. 2 segments of 9 mm x 0.8 mm at box terminal
Max. 10 segments of 16 mm x 0.8 mm at box terminal
Max. 10 segments of 16 mm x 0.8 mm at rear-side connection (punched)
10000 operations at 400 V AC-1
5000 operations at 690 V AC-3
6500 operations at 415 V AC-3
6500 operations at 400 V AC-3
14 mm² - 18 mm² (1x)
Min. 16 mm x 5 mm direct at switch rear-side connection
Max. 20 mm x 5 mm direct at switch rear-side connection
6 mm² - 11 mm² (1x) direct at switch rear-side connection
16 mm² (1x) at tunnel terminal
4 mm² - 350 mm² (1x) at box terminal