View larger
NZMH4-AEF1200-NA 271119 Y7-271119 EATON ELECTRIC Circuit-breaker, 3p, 1200A
NZMH4-AEF1200-NA
271119
Y7-271119
EATON - MOELLER
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller molded case circuit-breaker is engineered to protect electrical circuits from damage caused by excess current from an overload or short circuit. These robust devices are widely applied in commercial and industrial electrical architecture for safe power switching and fault isolation. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 1200 A
- Rated voltage (EF003977): 690 V
- Overload release current setting (EF002336): 1200 A
- Adjustment range undelayed short-circuit release (EF007131): 2400 A
- Device construction (EF008240): Built-in device fixed built-in technique
- Integrated earth fault protection (EF007296): No
- Type of electrical connection of main circuit (EF006819): Screw connection
- Suitable for DIN rail (top hat rail) mounting (EF007250): No
- DIN rail (top hat rail) mounting optional (EF008904): Yes
- With switched-off indicator (EF007006): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Position of connection for main current circuit (EF006671): Front
- Type of control element (EF006976): Rocker lever
- Complete device with protection unit (EF008906): Yes
- Motor drive integrated (EF006697): No
More info
▲General specifications
UL (File No. E31593)
Specially designed for North America
CSA certified
IEC 60947-2
UL 489
CE marking
UL listed
CSA-C22.2 No. 5-09
IEC/EN 60947
UL/CSA
IEC
CSA (Class No. 1432-01)
UL (Category Control Number DIVQ)
Product specifications
- Branch circuits, feeder circuits
- Use in unearthed supply systems at 690 V
Motor drive optional
Fixed
DIN rail (top hat rail) mounting optional
Damp heat, cyclic, to IEC 60068-2-30
500 V AC (between auxiliary contacts and main contacts)
IP20
1600 A (415 V AC-1, making and breaking capacity)
1200 A (690 V AC -1, making and breaking capacity)
1200 A (660-690 V AC-3, making and breaking capacity)
IP66 (with door coupling rotary handle)
IP00 (terminations, phase isolator and strip terminal)
Max. 10 segments of 32 mm x 1 mm (2x) at flat conductor terminal
10 segments of 50 mm x 1 mm (2x) at 1-hole module plate
Min. 10 segments of 50 mm x 1 mm (2x) at rear-side connection (punched)
Max. 10 segments of 50 mm x 1 mm (2x) at rear-side connection (punched)
10 segments of 80 mm x 1 mm (2x) at rear-side width extension
NA: same as for IEC
2000 operations at 400 V AC-3
2000 operations at 415 V AC-3
3000 operations at 400 V AC-1
2000 operations at 690 V AC-1
16 mm² - 18 mm² (2x)
Min. 25 mm x 5 mm direct at switch rear-side connection
Max. 50 mm x 10 mm (2x) direct at switch rear-side connection
Min. 25 mm x 5 mm at rear-side 1-hole module plate
Max. 50 mm x 10 mm (2x) at rear-side 1-hole module plate
50 mm x 10 mm (2x) at rear-side 2-hole module plate
Min. 60 mm x 10 mm at rear-side width extension
Max. 80 mm x 10 mm (2x) at rear-side width extension
NA: same as for IEC
120 mm² - 185 mm² (1x) direct at switch rear-side connection
50 mm² - 185 mm² (4x) direct at switch rear-side connection
Min. 120 mm² - 300 mm² (1x) at rear-side 1-hole module plate
Max. 95 mm² - 300 mm² (2x) at rear-side 1-hole module plate
Min. 95 mm² - 185 mm² (2x) at rear-side 2-hole module plate
Max. 35 mm² - 185 mm² (4x) at rear-side 2-hole module plate
300 mm² (4x) at rear-side width extension
95 mm² - 240 mm² (6x) at rear-side width extension
NA: AWG 0- kcmil 500 (4x) at 4-hole tunnel terminal
NA: kcmil 250 - kcmil 350 (1x) direct at switch rear-side connection
NA: AWG 0 - kcmil 350 (4x) direct at switch rear-side connection
NA: min. kcmil 250 - kcmil 600 (1x) at rear-side 1-hole module plate
NA: max. AWG 3/0 - kcmil 600 (2x) at rear-side 1-hole module plate
NA: min. AWG 3/0 - kcmil 350 (2x) at rear-side 2-hole module plate
NA: max. AWG 2 - kcmil 350 (4x) at rear-side 2-hole module plate
NA: kcmil 600 (4x) at rear-side width extension
NA: AWG 3/0 - kcmil 500 (6x) at rear-side width extension
Max. 70 mm² - 185 mm² (2x) at rear-side 1-hole module plate
50 mm² (4x) at rear-side 2-hole module plate
240 mm² (2x) at rear-side width extension
70 mm² - 240 mm² (6x) at rear-side width extension
NA: aluminum conductor not applicable