View larger
NZMB2-AF100-NA 269164 Y7-269164 EATON ELECTRIC Circuit-breaker, 3p, 100A
NZMB2-AF100-NA
269164
Y7-269164
EATON - MOELLER
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
Circuit Breakers NZM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The NZMB2-AF100-NA 269164 Y7-269164 EATON ELECTRIC Circuit-breaker, 3p, 100A is a thermal-magnetic circuit breaker applied in commercial and industrial electrical distribution setups for branch circuit protection. It reliably interrupts excessive currents caused by overloads or short circuits to maintain operational safety. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated permanent current Iu (EF001389): 100 A
- Rated voltage (EF003977): 440 V
- Overload release current setting (EF002336): 100 A
- Adjustment range undelayed short-circuit release (EF007131): 600 A
- Device construction (EF008240): Built-in device fixed built-in technique
- Integrated earth fault protection (EF007296): No
- Type of electrical connection of main circuit (EF006819): Screw connection
- Suitable for DIN rail (top hat rail) mounting (EF007250): No
- DIN rail (top hat rail) mounting optional (EF008904): Yes
- With switched-off indicator (EF007006): No
- With integrated under voltage release (EF001390): No
- Number of poles (EF001391): 3
- Position of connection for main current circuit (EF006671): Front
- Type of control element (EF006976): Rocker lever
- Complete device with protection unit (EF008906): Yes
- Motor drive integrated (EF006697): No
More info
▲General specifications
UL/CSA
CSA certified
Specially designed for North America
CSA-C22.2 No. 5-09
IEC
CSA (Class No. 1432-01)
CE marking
UL (Category Control Number DIVQ)
UL 489
CSA (File No. 22086)
UL listed
IEC/EN 60947
UL (File No. E31593)
Product specifications
- Branch circuits, feeder circuits
- Use in unearthed supply systems at 440 V
Motor drive optional
Built-in device fixed built-in technique
Fixed
Damp heat, constant, to IEC 60068-2-78
500 V AC (between auxiliary contacts and main contacts)
IP20
300 A (415 V AC-1, making and breaking capacity)
IP66 (with door coupling rotary handle)
IP10 (tunnel terminal)
Max. 10 segments of 16 mm x 0.8 mm at box terminal
Max. 10 segments of 16 mm x 0.8 mm at rear-side connection (punched)
Min. 2 segments of 9 mm x 0.8 mm at box terminal
7500 operations at 400 V AC-1
Current limiting circuit breaker
14 mm² - 18 mm² (1x)
Min. 16 mm x 5 mm direct at switch rear-side connection
M8 at rear-side screw connection
6 mm² - 12 mm² (1x) at box terminal
16 mm² (1x) at tunnel terminal
4 mm² - 350 mm² (1x) at tunnel terminal
4 mm² - 350 mm² (1x) at box terminal