EATON - MOELLER CGVision Pro Package I CGVision Pro Package I 40071361021 EATON ELECTRIC Distribution board BI-7647 Package without metering applic.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

CGVision Pro Package I 40071361021 EATON ELECTRIC Distribution board BI-7647 Package without metering applic..

CGVision Pro Package I

40071361021

40071361021

EATON - MOELLER

1 Pcs.

Distribution board BI-7647 Package without metering application CGVision Pro Package I Eaton CGL+ CGVision, CGVision Pro Package I

Automation > Visualization software
Central Battery System

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

CGVision Pro Package I 40071361021 EATON ELECTRIC Distribution board BI-7647 Package without metering applic.. provides a structured component bundle intended for electrical distribution infrastructure and control panel installations. Distribution board packages of this type help organize protective devices, terminal blocks, and switching equipment safely within industrial switchgear assemblies. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.

  • Min. required main memory for runtime system (EF003176): None MB
  • Min. required processor speed for runtime system (EF003175): None GHz

More info

▲
Distribution board BI-7647 Package without metering application
EL-Nummer (Norway)
1728160
[

Design verification as per IEC/EN 61439

Technical data for design verification
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top of the enclosure, calculated as per IEC 60890Individual enclosure for wall mounting [PV]
61 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top of the enclosure, calculated as per IEC 60890Starting enclosure for wall mounting [PV]
59 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top of the enclosure, calculated as per IEC 60890Middle enclosure for wall mounting [PV]
56 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top of the enclosure, calculated as per IEC 60890Individual enclosure for wall mounting [PV]
123 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top of the enclosure, calculated as per IEC 60890Starting enclosure for wall mounting [PV]
118 W
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top of the enclosure, calculated as per IEC 60890Middle enclosure for wall mounting [PV]
113 W
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Not relevant to indoor installations.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply to enclosures without lifting aids.
10.2 Strength of materials and parts10.2.6 Mechanical impact
IK08
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
IP30
10.4 Clearances and creepage distances
Is the panel builder's responsibility.
10.5 Protection against electric shock
< 0.1 Ω; meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Ui= 1890 V AC
10.9 Insulation properties10.9.3 Impulse withstand voltage
2.5 kV
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Does not apply to metal enclosures.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
Meets the product standard's requirements.
,

Technical data ETIM 7.0

Distribution boards (EG000023) / Small distribution board (EC000214)
Electric engineering, automation, process control engineering / Electrical installation, device / Electrical distribution system (incl. small distribution board) / Small distribution board ([email protected] [ACN387011])
Mounting method
Surface mounted (plaster)
Number of rows
5
Width in number of modular spacings
20
Type of cover
Door
Cover model
Closed
Transparent cover/door
No
Material housing
Steel
Height
765 mm
Width
475 mm
Depth
220 mm
Built-in depth
212 mm
Internal depth
210 mm
DIN-rail
Yes
With mounting plate
No
Extension possible
No
EMC-version
Yes
Colour
White
RAL-number
9016
Degree of protection (IP)
IP30
With lock
No
Type of closure
Other
]

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.