EATON - MOELLER NZM2-4-XAD250 NZM2-4-XAD250 138388 Y7-138388 EATON ELECTRIC Busbar adapter, 4p, for NZM2, 250A, UL508 View larger
Images are for illustrative purposes only. Please refer to data sheet for details

NZM2-4-XAD250 138388 Y7-138388 EATON ELECTRIC Busbar adapter, 4p, for NZM2, 250A, UL508

NZM2-4-XAD250

138388

Y7-138388

EATON - MOELLER

1 Pcs.

Busbar adapter, 4p, for NZM2, 250A, UL508 NZM2-4-XAD250 Eaton xEffect SASY 60i Enclosures Switch- & Controlgear Enclosure. Busbar adapter, 4p, for NZM2, 250A, UL508 Type-checked busbar adapter for NZM circuit-breaker and N switch-disconnector, for surface mounting on Cu-busbars 12-30x5-10, double t and triple t profile, rated operational current Ie=250A, can be used for NZM2, PN2, N(S)2, NZM2(-4), PN2(-4), N(N/O)2(-4), adapter width=140mm, rated operating voltage Ue=690VAC, screw connection on the busbar 5mm or 10mm thickness, cable connection at bottom, temperature resistant to 120 °C, self-extinguishing to UL 94, track resistance CTI 200, number of poles=4 pole, between busbar centers=60mm, can be used in conjunction with busbar system SASY 60i

Automation > Busbar adapter
Circuit Breakers NZM

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton xEffect SASY 60i MCCB adapter
Catalog Number
138388
Model Code
NZM2-4-XAD250
EAN
4015081351688
Product Length/Depth
35 mm
Product Height
270 mm
Product Width
140 mm
Product Weight
1.8 kg
Compliances
RoHS conform

Delivery program

Type
Nominal current
250 A
Number of poles
Four-pole

Technical data - electrical

Voltage rating at AC
690 V AC
Rated operation current (Ie)
250 A
Electric connection type
Other
Creepage resistance
CTI 200

Technical data - mechanical

Mounting rail armament
None
Rail width
30 mm
Busbar distance
60 mm
Busbar thickness - min
5 mm
Busbar thickness - max
10 mm
Busbar adapter width
140 mm
Adapter width
140 mm

Design verification as per IEC/EN 61439 - technical data

Equipment heat dissipation, current-dependent Pvid
8.1 W
Temperature resistance
Up to 120 °C

Additional information

Features
Self-extinguishing acc. UL 94
Functions
Busbar adapters for NZM
Component adapter for circuit breakers and switch-disconnector
Suitable for
Surface mounting on flat copper busbars 12 – 30 x 5 – 10, double T and triple T profile
Used with
NZM2(-4), PN2(-4), N2(-4)

ETIM for 138388 Low-voltage industrial controls and switchgear (EC001531)
Feature Name Feature Value
Mounting rail armament (EF003700) None
Type of electric connection (EF003961) Other
Rated current In (EF008250) 250 A
Min. busbar thickness (EF006536) 5 mm
Max. busbar thickness (EF003702) 10 mm
Width of the adapter (EF003703) 140 mm
Rail width (EF003704) 30 mm
Busbar distance (EF002638) 60 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.