EATON - MOELLER BBA0-25 BBA0-25 101451 Y7-101451 EATON ELECTRIC Busbar adapter, 45mm, 25A, 1TS View larger
Images are for illustrative purposes only. Please refer to data sheet for details

BBA0-25 101451 Y7-101451 EATON ELECTRIC Busbar adapter, 45mm, 25A, 1TS

BBA0-25

101451

Y7-101451

EATON - MOELLER

4 Pcs.

Busbar adapter, 45mm, 25A, 1TS BBA0-25 Eaton Moeller® series BBA Busbar adapter, 45 mm, 25 A, DIN rail: 1 BBA0-25 45mm busbar adapter for 60mm busbar system, one mounting rail, three prefabricated cables (AWG12/4 square millimeter) for connection of switching device, can be used for motor-protective circuit-breaker PKZM0, PKE and DOL starter/ MSC-D(E)(A) with contactor DILM7 to DILM15, rated operational current: 25A

Automation > Busbar adapter
Circuit Breakers PKZ

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton Moeller® series BBA Accessory Busbar adapter
Catalog Number
101451
Model Code
BBA0-25
EAN
4015081013715
Product Length/Depth
200 mm
Product Height
73 mm
Product Width
45 mm
Product Weight
0.27 kg
Certifications
CE
UL
Certified by UL for use in Canada
CSA-C22.2 No. 14
UL Category Control No.: NMTR; NMTR7
IEC60439-1
UL 508A
UL File No.: E300273

Delivery program

Type
Nominal current
25 A

Technical data - electrical

Voltage rating (UL CSA 13)
600 V AC, UL/CSA
Voltage rating at AC
690 V
Rated operation current (Ie)
25 A
Electric connection type
3 conductors AWG 12

Technical data - mechanical

Mounting rail armament
1 mounting rail
Rail width
35 mm
Number of DIN rails
1
Busbar distance
60 mm
Busbar thickness - min
5 mm
Busbar thickness - max
10 mm
Adapter width
45 mm

Design verification as per IEC/EN 61439 - technical data

Equipment heat dissipation, current-dependent Pvid
1.9 W
Static heat dissipation, non-current-dependent Pvs
0 W
Heat dissipation per pole, current-dependent Pvid
0 W
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C

Design verification as per IEC/EN 61439

10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Additional information

Special features
Terminal capacity: 4 mm² (AWG 12)

ETIM for 101451 Low-voltage industrial controls and switchgear (EC001531)
Feature Name Feature Value
Mounting rail armament (EF003700) 1 mounting rail
Type of electric connection (EF003961) 3 conductors AWG 12
Rated current In (EF008250) 25 A
Min. busbar thickness (EF006536) 5 mm
Max. busbar thickness (EF003702) 10 mm
Width of the adapter (EF003703) 45 mm
Rail width (EF003704) 35 mm
Busbar distance (EF002638) 60 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.