EATON - MOELLER NZM1-4-XKC NZM1-4-XKC 267075 Y7-267075 EATON ELECTRIC Box terminal, 4p, up to 160 A View larger
Images are for illustrative purposes only. Please refer to data sheet for details

NZM1-4-XKC 267075 Y7-267075 EATON ELECTRIC Box terminal, 4p, up to 160 A

NZM1-4-XKC

267075

Y7-267075

EATON - MOELLER

1 Pcs.

Box terminal, 4p, up to 160 A NZM1-4-XKC Eaton Moeller series NZM - Molded Case Circuit Breaker. Box terminal, 4p, up to 160 A, 1 Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: standard connection with all NZM1, PN1 and N(N/O)1 switches. Conversion kit for circuit-breaker with screw connection. Part no. contains parts for a 3 or 4 pole switch side. Fitted within the switch housing. Use ferrules with flexible and highly flexible conductors. Max. cross section shown can only be connected when flexible and without ferrules. Can be used for: NZM1(-4), PN1(-4), N(N/O)1(-4)

Automation > Wiring set for power circuit breaker
Circuit Breakers NZM

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton Moeller series NZM connection type
Catalog Number
267075
Model Code
NZM1-4-XKC
EAN
4015082670757
Product Length/Depth
13 mm
Product Height
24.5 mm
Product Width
16.6 mm
Product Weight
0.096 kg
Compliances
IEC
RoHS conform

Product specifications

Used with
NZM1(-4), PN1(-4), N(S)1(-4)
Type
Amperage Rating
≦ 160 A
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Frame
NZM1
Suitable for
Copper cable
Four-pole
Number of poles
Four-pole
Terminal capacity (copper strip)
2 segments of 9 mm x 0.8 mm - 9 segments of 9 mm x 0.8 mm
Model
Other
Terminal capacity (stranded cable)
10 mm² - 70 mm² (1x)
12 - 2/0 AWG/kcmil (1x)
6 mm² - 25 mm² (2x)

ETIM for 267075 Low-voltage industrial controls and switchgear (EC002050)
Feature Name Feature Value
Suitable for number of poles (EF001589) 4
Model (EF000010) Other

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.