View larger
DILM150-XHI40 277948 Y7-277948 EATON ELECTRIC Auxiliary contact module, 4N/O
DILM150-XHI40
277948
Y7-277948
EATON - MOELLER
1 Pcs.
Automation > Auxiliary contact block
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller auxiliary contact module DILM150-XHI40 (277948) attaches to high-capacity contactors to furnish extra normally open switching pathways for control logic. These front-mounting blocks help system builders expand control capability without increasing panel footprint.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of contacts as change-over contact: 0
- Number of contacts as normally open contact: 4
- Number of contacts as normally closed contact: 0
- Number of fault-signal switches: 0
- Rated operation current Ie at AC-15, 230 V: 6 A
- Type of electric connection: Screw connection
- Model: Clip-on
- Mounting method: Front fastening
More info
▲General specifications
CE
IEC/EN 60947
UL
IEC/EN 60947-4-1
UL 508
UL File No.: E29184
CSA-C22.2 No. 14-05
CSA
CSA File No.: 012528
UL Category Control No.: NKCR
CSA Class No.: 3211-03
Features & Functions
General
Ambient conditions, mechanical
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
1 x (0.75 - 2.5) mm²
2 x (0.75 - 2.5) mm²
0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver
Electrical Rating
6 A at 60 V, DC L/R ≤ 15 ms (with 1 contact in series)
3 A at 110 V, DC L/R ≤ 15 ms (with 1 contact in series)
1 A at 220 V, DC L/R ≤ 15 ms (with 1 contact in series)
Short-circuit rating
Conventional thermal current
Switching capacity
15 A, 600 V AC, (UL/CSA)
P300, DC operated (UL/CSA)
Communication
Contacts
λ < 5 x 1/10⁷ (1 failure at 2,000,000 operations for Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA)
Safety
440 V AC, Between coil and auxiliary contacts, According to EN 61140