Eaton Moeller® series DILM auxiliary contact module
Catalog Number
278428
Model Code
DILM1000-XHIC11-SI
EAN
4015082784287
Product Length/Depth
77 mm
Product Height
77 mm
Product Width
15 mm
Product Weight
0.037 kg
Certifications
CSA VDE 0660 CSA-C22.2 No. 14-05 IEC/EN 60947-4-1 CE UL CSA Class No.: 3211-04 CSA File No.: 012528 UL 508 UL Category Control No.: NKCR UL File No.: E29184 IEC/EN 60947
Features & Functions
Features
Interlocked opposing contacts within an auxiliary contact module (according to IEC 60947-5-1 Annex L)
Functions
For standard applications
Fitted with:
Interlocked opposing contacts
Number of poles
Two-pole
Electric connection type
Spring clamp connection
General
Lifespan, electrical
1,300,000 Operations (at 230 V, AC-15, 3 A)
Model
Top mounting
Mounting method
Side mounting
Overvoltage category
III
Pollution degree
3
Protection
Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274)
Rated impulse withstand voltage (Uimp)
6000 V 6000 V AC
Type
Side-mounting auxiliary contacts
Climatic environmental conditions
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
60 °C
Ambient operating temperature (enclosed) - min
-25 °C
Ambient operating temperature (enclosed) - max
40 °C
Ambient storage temperature - min
-40 °C
Ambient storage temperature - max
80 °C
Climatic proofing
Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
Terminal capacity (flexible with ferrule)
1 x (1 - 2.5) mm² 2 x (1 - 2.5) mm²
Terminal capacity (solid)
2 x (1 - 2.5) mm² 1 x (1 - 2.5) mm²
Terminal capacity (solid/stranded AWG)
16 - 14
Screwdriver size
0.6 x 3.5 mm, Spring-loaded terminals
Electrical Rating
Rated operational current (Ie)
1 A at 220 V, DC L/R ≤ 15 ms (with 1 contact in series) 10 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series) 6 A at 60 V, DC L/R ≤ 15 ms (with 1 contact in series) 3 A at 110 V, DC L/R ≤ 15 ms (with 1 contact in series)
Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V
6 A
Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V
4 A
Rated operational current (Ie) at AC-15, 500 V
1.5 A
Rated operational current (Ie) at DC-13, 24 V
2 A
Rated operational current (Ie) at DC-13, 60 V
1.5 A
Rated operational current (Ie) at DC-13, 110 V
0.8 A
Rated operational current (Ie) at DC-13, 220 V, 230 V
0.3 A
Rated insulation voltage (Ui)
690 V
Rated operational voltage (Ue) at AC - max
500 V
Short-circuit rating
Rated conditional short-circuit current (Iq)
1 kA at 500 V
Short-circuit protection rating
Max. 16 A gG/gL, Fuse, Without welding, Auxiliary contacts
Short-circuit protection rating without welding
16 A gG/gL, 500 V, Max. Fuse, Contacts
Conventional thermal current
Conventional thermal current ith at 60°C (3-pole, open)
10 A
Switching capacity
Switching capacity (auxiliary contacts, general use)
1 A, 250 V DC, (UL/CSA) 15 A, 600 V AC, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)
A600, AC operated (UL/CSA) P300, DC operated (UL/CSA)
Communication
Connection
Spring-loaded terminals
Contacts
Control circuit reliability
λ < 5 x 1/10⁷ (1 failure at 2,000,000 operations for Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA)
Number of contacts (change-over contacts)
0
Number of contacts (normally closed contacts)
1
Number of contacts (normally open contacts)
1
Safety
Safe isolation
440 V AC, Between coil and auxiliary contacts, According to EN 61140 440 V AC, Between auxiliary contacts, According to EN 61140