Lateral auxiliary contact modules like the Eaton DILM820-XHI11-SA mount onto heavy industrial contactors to increase the available contact count for auxiliary control logic. They facilitate interlocking, status indication, and feedback integration within motor starter panels. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of contacts as change-over contact (EF008257): 0
- Number of contacts as normally open contact (EF008256): 1
- Number of contacts as normally closed contact (EF008255): 1
- Number of fault-signal switches (EF007613): 0
- Rated operation current Ie at AC-15, 230 V (EF001385): 6 A
- Type of electric connection (EF003961): Screw connection
- Model (EF000010): Clip-on
- Mounting method (EF000003): Side mounting
More info
▲General specifications
UL 508
CSA Class No.: 3211-04
IEC/EN 60947
UL Category Control No.: NKCR
CSA File No.: 012528
UL File No.: E29184
CSA-C22.2 No. 14-05
CE
IEC/EN 60947-4-1
UL
VDE 0660
Features & Functions
General
6000 V
Climatic environmental conditions
Damp heat, constant, to IEC 60068-2-78
Terminal capacities
1 x (0.75 - 2.5) mm²
1 x (0.75 - 2.5) mm²
2, Terminal screw, Control circuit cables, Pozidriv screwdriver
Electrical Rating
1 A at 220 V, DC L/R ≤ 15 ms (with 1 contact in series)
6 A at 60 V, DC L/R ≤ 15 ms (with 1 contact in series)
10 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series)
Short-circuit rating
FAZ-C4/1, Maximum overcurrent protective device, Short-circuit rating without welding, Short-circuit protection only, Contacts
Conventional thermal current
Switching capacity
15 A, 600 V AC, (UL/CSA)
P300, DC operated (UL/CSA)
Communication
Contacts
Safety
440 V AC, Between auxiliary contacts and main contacts, According to EN 61140