View larger
DILA-XHIR11 110140 Y7-110140 EATON ELECTRIC Auxiliary contact module, 1N/O+1N/C, electronic
DILA-XHIR11
110140
Y7-110140
EATON - MOELLER
5 Pcs.
Automation > Auxiliary contact block
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Eaton Moeller electronic auxiliary contact module is designed for low-energy switching applications, ensuring reliable signal transmission to solid-state inputs. These modules mount onto control relays to interface mechanical systems securely with electronic controllers.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of contacts as change-over contact (EF008257): 0
- Number of contacts as normally open contact (EF008256): 1
- Number of contacts as normally closed contact (EF008255): 1
- Number of fault-signal switches (EF007613): 0
- Rated operation current Ie at AC-15, 230 V (EF001385): 4 A
- Type of electric connection (EF003961): Screw connection
- Model (EF000010): Clip-on
- Mounting method (EF000003): Front fastening
More info
▲General specifications
UL File No.: E29184
IEC/EN 60947-4-1
CSA
CSA Class No.: 3211-03
IEC/EN 60947
CE
UL Category Control No.: NKCR
CSA-C22.2 No. 14-05
UL 508
UL
VDE 0660
Features & Functions
Switching elements according to EN 50005
General
5 g, N/C auxiliary contact, Basic unit with auxiliary contact module, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
10,000,000 Operations (DC operated)
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Terminal capacities
2 x (0.75 - 1.5) mm², Screw terminals
1 x (0.75 - 2.5) mm², Screw terminals
2, Terminal screw, Pozidriv screwdriver
Electrical rating
1 A at 220 V, DC L/R ≤ 15 ms (with 1 contact in series)
2.5 A at 24 V, DC L/R ≤ 50 ms (with 3 contacts in series)
1 A at 60 V, DC L/R ≤ 50 ms (with 3 contacts in series)
0.5 A at 110 V, DC L/R ≤ 50 ms (with 3 contacts in series)
10 A at 24 V, DC L/R ≤ 15 ms (with 1 contact in series)
5 A at 220 V, DC L/R ≤ 15 ms (with 3 contacts in series)
6 A at 60 V, DC L/R ≤ 15 ms (with 1 contact in series)
3 A at 110 V, DC L/R ≤ 15 ms (with 1 contact in series)
0.25 A at 220 V, DC L/R ≤ 50 ms (with 3 contacts in series)
10 A at 60 V, DC L/R ≤ 15 ms (with 2 contacts in series)
400 V AC, Between auxiliary contacts, According to EN 61140
1 A, 250 V DC, (UL/CSA)
A600, AC operated (UL/CSA)
Contacts
42 in combination with DILA(C)-31
51E in combination with DILA(C)-40
λ < 5.3 x 1/10⁸ (1 failure at 19,000,000 operations for Uₑ = 24 V DC, Umin = 17 V, Imin = 1 mA)