View larger
DILM150-XHI11 277946 Y7-277946 EATON ELECTRIC Auxiliary contact module, 1N/O+1N/C
DILM150-XHI11
277946
Y7-277946
EATON - MOELLER
1 Pcs.
Automation > Auxiliary contact block
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for standard industrial applications, the Eaton Moeller DILM150-XHI11 auxiliary contact module (277946) attaches directly to power contactors to increase the available control pathways. Auxiliary contact modules are essential for managing interlocking sequences, indicator lights, and secondary automation signals.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product Name: Eaton Moeller® series DILM auxiliary contact module
- Catalog Number: 277946
- Model Code: DILM150-XHI11
- EAN: 4015082779467
- UPC: 782116354771
- Product Length/Depth: 39 mm
- Product Height: 46 mm
- Product Width: 24 mm
- Product Weight: 0.03 kg
- Functions: For standard applications
- Fitted with:: Interlocked opposing contacts
- Number of poles: Two-pole
- Electric connection type: Screw connection
- Connection: Screw terminals
More info
▲General specifications
| Product Name | Eaton Moeller® series DILM auxiliary contact module |
| Catalog Number | 277946 |
| Model Code | DILM150-XHI11 |
| EAN | 4015082779467 |
| UPC | 782116354771 |
| Product Length/Depth | 39 mm |
| Product Height | 46 mm |
| Product Width | 24 mm |
| Product Weight | 0.03 kg |
| Certifications | IEC/EN 60947-4-1 CE CSA UL Category Control No.: NKCR CSA-C22.2 No. 14-05 VDE 0660 UL CSA File No.: 012528 IEC/EN 60947 CSA Class No.: 3211-03 UL 508 UL File No.: E29184 |
Features & Functions
| Features | Interlocked opposing contacts within an auxiliary contact module (according to IEC 60947-5-1 Annex L) |
| Functions | For standard applications |
| Fitted with: | Interlocked opposing contacts |
| Number of poles | Two-pole |
| Number of poles | Two-pole |
| Number of poles | Two-pole |
| Electric connection type | Screw connection |
General information
| Connection | Screw terminals |
| Lifespan, electrical | 1,300,000 Operations (at 230 V, AC-15, 3 A) |
| Model | Top mounting |
| Mounting method | Front fastening |
| Overvoltage category | III |
| Pollution degree | 3 |
| Protection | Finger and back-of-hand proof, Protection against direct contact when actuated from front (EN 50274) |
| Rated impulse withstand voltage (Uimp) | 6000 V AC |
| Type | Front mounting auxiliary contact |
Ambient conditions, mechanical
| Shock resistance | 5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 7 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms |
Climatic environmental conditions
| Ambient operating temperature - min | -25 °C |
| Ambient operating temperature - max | 60 °C |
| Ambient operating temperature (enclosed) - min | -25 °C |
| Ambient operating temperature (enclosed) - max | 40 °C |
| Ambient storage temperature - min | -40 °C |
| Ambient storage temperature - max | 80 °C |
| Climatic proofing | Damp heat, cyclic, to IEC 60068-2-30 Damp heat, constant, to IEC 60068-2-78 |
Terminal capacities
| Terminal capacity (flexible with ferrule) | 1 x (0.75 - 2.5) mm² 2 x (0.75 - 2.5) mm² |
| Terminal capacity (solid) | 1 x (0.75 - 2.5) mm² 2 x (0.75 - 2.5) mm² |
| Terminal capacity (solid/stranded AWG) | 18 - 14 |
| Screwdriver size | 0.8 x 5.5/1 x 6 mm, Terminal screw, Standard screwdriver 2, Terminal screw, Pozidriv screwdriver |
| Tightening torque | 1.2 Nm, Screw terminals |
Electrical rating
| Rated operational current (Ie) at AC-15, 220 V, 230 V, 240 V | 6 A |
| Rated operational current (Ie) at AC-15, 380 V, 400 V, 415 V | 4 A |
| Rated operational current (Ie) at AC-15, 500 V | 1.5 A |
| Rated operational voltage (Ue) at AC - max | 500 V |
| Rated insulation voltage (Ui) | 690 V |
Short-circuit rating
| Short-circuit protection rating | Max. 16 A gG/gL, Fuse, Without welding, Auxiliary contacts |
| Short-circuit protection rating without welding | 16 A gG/gL, 500 V, Max. Fuse, Contacts |
Switching capacity
| Switching capacity (auxiliary contacts, general use) | 15 A, 600 V AC, (UL/CSA) 1 A, 250 V DC, (UL/CSA) |
| Switching capacity (auxiliary contacts, pilot duty) | P300, DC operated (UL/CSA) A600, AC operated (UL/CSA) |
Contacts
| Control circuit reliability | λ < 5 x 1/10⁷ (1 failure at 2,000,000 operations for Uₑ = 24 V DC, Umin = 17 V, Imin = 5.4 mA) |
| Number of contacts (change-over contacts) | 0 |
| Number of contacts (normally closed contacts) | 1 |
| Number of contacts (normally open contacts) | 1 |
Safety
| Safe isolation | 440 V AC, Between auxiliary contacts, According to EN 61140 440 V AC, Between coil and auxiliary contacts, According to EN 61140 |
Design verification
| Equipment heat dissipation, current-dependent Pvid | 0 W |
| Heat dissipation capacity Pdiss | 0 W |
| Heat dissipation per pole, current-dependent Pvid | 0.23 W |
| Rated operational current for specified heat dissipation (In) | 4 A |
| Static heat dissipation, non-current-dependent Pvs | 0 W |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |