View larger
BP-U-800/10 100987 EATON ELECTRIC 2-step flush-mounting door frame with sheet steel door and rotary door han..
BP-U-800/10
100987
EATON - MOELLER
1 Pcs.
Automation > Small distribution board
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Eaton Moeller BP-U-800/10 100987 provides a robust architectural framework for flush-mounted electrical distribution systems. Door frames and enclosures of this type house modular electrical devices while offering clean panel integration.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Individual enclosure, flush mounting: P V
- Individual enclosure, flush mounting: P V
- Mounting method (EF000003): Flush mounted
- Number of rows (EF000266): 7
- Width in number of modular spacings (EF002950): 35
- Transparent cover/door (EF006244): No
- Signal passing door (EF015941): No
- With lock (EF006306): No
- Housing material (EF001596): Steel
- Built-in depth (EF000218): 93 mm
- Earthing terminal block (EF015776): No
- Neutral terminal block (EF015777): No
- DIN-rail (EF001134): Yes
- With mounting plate (EF000118): No
- Extension possible (EF001088): No
- EMC-version (EF001062): No
More info
▲Technical data for design verification | |||
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees, calculated as per IEC 60890 | |||
Individual enclosure, flush mounting | PV | CO | 72 |
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees, calculated as per IEC 60890 | |||
Individual enclosure, flush mounting | PV | CO | 144 |
IEC/EN 61439 design verification | |||
10.2 Strength of materials and parts | |||
10.2.2 Corrosion resistance | Meets the product standard's requirements. | ||
10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. | ||
10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. | ||
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects | Meets the product standard's requirements. | ||
10.2.4 Resistance to ultra-violet (UV) radiation | Not relevant to indoor installations. | ||
10.2.5 Lifting | Does not apply to enclosures without lifting aids. | ||
10.2.6 Mechanical impact | IK07 | ||
10.2.7 Inscriptions | Meets the product standard's requirements. | ||
10.3 Degree of protection of ASSEMBLIES | IP30 | ||
10.4 Clearances and creepage distances | Is the panel builder's responsibility. | ||
10.5 Protection against electric shock | < 0.1 Ω; meets the product standard's requirements. | ||
10.6 Incorporation of switching devices and components | Is the panel builder's responsibility. | ||
10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. | ||
10.8 Connections for external conductors | Is the panel builder's responsibility. | ||
10.9 Insulation properties | |||
10.9.2 Power-frequency electric strength | Ui= 440 V AC | ||
10.9.3 Impulse withstand voltage | 4 kV | ||
10.9.4 Testing of enclosures made of insulating material | Does not apply to metal enclosures. | ||
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. | ||
10.11 Short-circuit rating | Is the panel builder's responsibility. | ||
10.12 Electromagnetic compatibility | Is the panel builder's responsibility. | ||
10.13 Mechanical function | Meets the product standard's requirements. |
| Distribution boards (EG000023) / Small distribution board (EC000214) | |||
| Electric engineering, automation, process control engineering / Electrical installation, device / Electrical distribution system (incl. small distribution board) / Small distribution board (ecl@ss8-27-14-24-09 [ACN387007]) | |||
Mounting method | Flush mounted (plaster) | ||
Number of rows | 7 | ||
Width in number of modular spacings | 35 | ||
Type of cover | Closed | ||
With transparent cover | No | ||
Material housing | Steel | ||
Height | mm | 1000 | |
Width | mm | 800 | |
Depth | mm | 247 | |
Built-in depth | mm | 93 | |
DIN-rail | Yes | ||
With mounting plate | No | ||
Extension possible | No | ||
EMC-version | No | ||
Colour | Grey | ||
RAL-number | 7035 | ||
Degree of protection (IP) | IP30 | ||