View larger
199300 EATON ELECTRIC DILMP32-11(110V50HZ,120V60HZ)-PI
199300
199300
Y7-199300
EATON - MOELLER
1 Pcs.
Automation > Power contactor, AC switching
Contactors up to 170A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Equipped with spring clamp connections for efficient wiring, the 199300 EATON ELECTRIC DILMP32-11(110V50HZ,120V60HZ)-PI contactor delivers reliable multi-pole switching for industrial control panels. Contactors of this type are widely implemented to automate the operation of motors, heating elements, and lighting grids.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated control supply voltage AC 50 Hz (EF003978): 110 V
- Rated control supply voltage AC 60 Hz (EF003979): 120 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Number of normally open contacts as main contact (EF001374): 4
- Type of electrical connection of main circuit (EF006819): Spring clamp connection
- Operating voltage AC 50 Hz (EF008206): 24 V
- Operating voltage AC 60 Hz (EF008207): 24 V
- Rated operation current Ie at AC-1, 400 V (EF001393): 32 A
- Rated operation current Ie at AC-3, 400 V (EF001392): 18 A
- Rated operation power at AC-3, 400 V (EF001364): 7.5 kW
- Rated operation current Ie at AC-4, 400 V (EF008495): 15 A
- Rated operation power at AC-4, 400 V (EF008496): 7 kW
- Rated operation power NEMA (EF011960): 0 kW
- Modular version (EF001126): No
- Width (EF000008): 61 mm
More info
▲General specifications
IEC/EN 60947
Features & Functions
General
AC-3: Normal AC induction motors: starting, switch off during running
Ambient conditions, mechanical
10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
5 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Climatic environmental conditions
Damp heat, cyclic, to IEC 60068-2-30
Electro Magnetic Compatibility
Terminal capacities
2 x (1 - 4) mm², Main cables
2 x (0.5 - 1.5) mm², Control circuit cables
1 x (0.5 - 2.5) mm², Control circuit cables
2 x (1 - 6) mm², Main cables
1 x (0.5 - 2.5) mm², Control circuit cables
2 x (0.5 - 2.5) mm², Control circuit cables
1 x (1 - 6) mm², Main cables
2 x (1 - 6) mm², Main cables
1 x (0.5 - 2.5) mm², Control circuit cables
20 - 14, Control circuit cables
Electrical Rating
Short-circuit rating
125 A, max. Fuse, SCCR (UL/CSA)
5 kA, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
32 A, max. CB, SCCR (UL/CSA)
70 A, Class J, max. Fuse, SCCR (UL/CSA)
100 A, Class J, max. Fuse, SCCR (UL/CSA)
Conventional thermal current
Switching capacity
10 A, 600 V AC, (UL/CSA)
Switching time
Magnet system
0.8 - 1.1 V AC x Uc
40 W, Dual-frequency coil in a cold state and 1.0 x Us, at 60 Hz
2.1 W, Dual-frequency coil in a cold state and 1.0 x Us
Motor Rating
Communication
Contacts
Safety
400 V AC, Between coil and contacts, According to EN 61140