View larger
167804 Y7-167804 EATON ELECTRIC DOL starter, 3-12A, protection electronic, standard
167804
167804
Y7-167804
EATON - MOELLER
1 Pcs.
Automation > Motor starter/Motor starter combination
Electronic Circuit Breakers
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Direct starter model 167804 from Eaton Moeller serves as a dependable controller for starting and stopping industrial electric motors. DOL starters connect motors directly to the power supply while providing essential thermal and electronic overload protection to prevent equipment damage. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of motor starter (EF009598): Direct starter
- With short-circuit release (EF006691): Yes
- Rated control supply voltage AC 50 Hz (EF003978): 110 V
- Rated control supply voltage AC 60 Hz (EF003979): 120 V
- Rated control supply voltage DC (EF003980): 0 V
- Voltage type for actuating (EF008242): AC
- Rated operation power at AC-3, 230 V, 3-phase (EF009599): 3 kW
- Rated operation power at AC-3, 400 V (EF001364): 7.5 kW
- Rated power, 460 V, 60 Hz, 3-phase (EF009600): 5.52 kW
- Rated power, 575 V, 60 Hz, 3-phase (EF009601): 0 kW
- Rated operation current Ie (EF001443): 16.7 A
- Rated operation current at AC-3, 400 V (EF009602): 12 A
- Overload release current setting (EF002336): 3 A
- Ambient temperature, upper operating limit (EF009603): 55 °C
- Temperature compensated overload protection (EF009604): Yes
- Release class (EF006668): Adjustable
More info
▲General specifications
UL
CE
CSA File No.: 012528
UL Category Control No.: NKJH
VDE 0660
CSA
CSA-C22.2 No. 14-10
UL File No.: E123500
UL60947-4-1A
IEC/EN 60947-4-1
Features & Functions
General
1000 (Class 20) AC-4 cycle operation, Main conducting paths
700 (Class 10) AC-4 cycle operation, Main conducting paths
Note: Going below the minimum current flow time can cause overheating of the load (motor).
500 (Class 5) AC-4 cycle operation, Main conducting paths
For all combinations with an SWD activation, you need not adhere to the minimum current flow times and minimum cut-out periods.
NEMA Other
Climatic environmental conditions
Electrical rating
1 A, 250 V DC, (UL/CSA)
P300, DC operated (UL/CSA)
Short-circuit rating
5 kA, SCCR (UL/CSA)
40 A, max. Fuse, SCCR (UL/CSA)
15 A, max. CB, SCCR (UL/CSA)
100 kA, Fuse, SCCR (UL/CSA)
65 kA, CB, SCCR (UL/CSA)
100 kA, Fuse, SCCR (UL/CSA)
18 kA, 480 Y/277 V, SCCR (UL/CSA)