MSC-DE-1,2-M17-SP(110V50HZ,120V60HZ) DOL starter, Ir= 0.3 - 1.2 A, 110 V 50 Hz, 120 V 60 Hz, AC voltage DOL starter, Basic device: MSC, Setting range of overload releases: Ir= 0.3 - 1.2 A, Actuating voltage: 110 V 50 Hz, 120 V 60 Hz, AC voltage, Standards: IEC/EN 60947-4-1, VDE 0660, UL, CSA

Automation > Motor starter/Motor starter combination
Electronic Circuit Breakers

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

DOL starter, Ir= 0.3 - 1.2 A, 110 V 50 Hz, 120 V 60 Hz, AC voltage
DOL starter, Basic device: MSC, Setting range of overload releases: Ir= 0.3 - 1.2 A, Actuating voltage: 110 V 50 Hz, 120 V 60 Hz, AC voltage, Standards: IEC/EN 60947-4-1, VDE 0660, UL, CSA

General specifications
Product name
Eaton Moeller® series MSC-DE Starter with electronic trip unit
Part no.
MSC-DE-1,2-M17-SP(110V50HZ,120V60HZ)
EAN
4015081643790
Product Length/Depth
145 millimetre
Product height
272 millimetre
Product width
45 millimetre
Product weight
1.174 kilogram
Certifications
VDE 0660
CSA File No.: 012528
UL Category Control No.: NKJH
CSA
UL
CSA-C22.2 No. 14-10
UL File No.: E123500
CE
UL60947-4-1A
CSA Class No.: 3211-08
IEC/EN 60947-4-1
Product Tradename
MSC-DE
Product Type
Starter with electronic trip unit
Product Sub Type
None
Features & Functions
Fitted with:
Short-circuit release
Functions
Temperature compensated overload protection
General information
Class
Adjustable
Connection
Screw terminals
Connection to SmartWire-DT
No
Current flow times - min
500 (Class 5) AC-4 cycle operation, Main conducting paths
900 (Class 15) AC-4 cycle operation, Main conducting paths
700 (Class 10) AC-4 cycle operation, Main conducting paths
1000 (Class 20) AC-4 cycle operation, Main conducting paths
Note: Going below the minimum current flow time can cause overheating of the load (motor).
For all combinations with an SWD activation, you need not adhere to the minimum current flow times and minimum cut-out periods.
Cut-out periods - min
≤ 500 ms, main conducting paths, AC-4 cycle operation
Degree of protection
IP20
NEMA Other
Model
Direct starter
Mounting method
Rail mounting possible
Number of auxiliary contacts (normally closed contacts)
0
Number of auxiliary contacts (normally open contacts)
1
Overload release current setting - min
0.3 A
Overload release current setting - max
1.2 A
Overvoltage category
III
Pollution degree
3
Rated impulse withstand voltage (Uimp)
6000 V AC
Type
Type E DOL starter (complete device)
Voltage type
AC
Climatic environmental conditions
Altitude
Max. 2000 m
Ambient operating temperature - min
-25 °C
Ambient operating temperature - max
55 °C
Electrical rating
Rated operational current (Ie)
16.7 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V
1.2 A
Rated operational power at AC-3, 220/230 V, 50 Hz
0.18 kW
Rated operational power at AC-3, 380/400 V, 50 Hz
7.5 kW
Rated operational voltage
208 - 480 V AC
Switching capacity (auxiliary contacts, general use)
1 A, 250 V DC, (UL/CSA)
15 A, 600 V AC, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)
A600, AC operated (UL/CSA)
P300, DC operated (UL/CSA)
Short-circuit rating
Rated conditional short-circuit current (Iq), type 2, 380 V, 400 V, 415 V
0 A
Short-circuit current rating (high fault at 600 V)
100 kA, Fuse, SCCR (UL/CSA)
1 A, Class J/CC, max. Fuse, SCCR (UL/CSA)
Short-circuit current rating (type E)
14 kA, 240 V, SCCR (UL/CSA)
14 kA, 480 Y/277 V, SCCR (UL/CSA)
Short-circuit release (Irm) - max
186 A
Magnet system
Power consumption, sealing, 50 Hz
2.1 W, Dual-frequency coil in a cold state and 1.0 x Us, at 50 Hz
Rated control supply voltage (Us) at AC, 50 Hz - min
110 V
Rated control supply voltage (Us) at AC, 50 Hz - max
110 V
Rated control supply voltage (Us) at AC, 60 Hz - min
120 V
Rated control supply voltage (Us) at AC, 60 Hz - max
120 V
Rated control supply voltage (Us) at DC - min
0 V
Rated control supply voltage (Us) at DC - max
0 V
Motor rating
Assigned motor power at 460/480 V, 60 Hz, 3-phase
0.5 HP
Design verification
Equipment heat dissipation, current-dependent Pvid
1.2 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0.4 W
Rated operational current for specified heat dissipation (In)
1.2 A
Static heat dissipation, non-current-dependent Pvs
2.1 W
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 8.0

Low-voltage industrial components (EG000017) / Motor starter/Motor starter combination (EC001037)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Load breakout, motor breakout / Motor starter combination ([email protected] [AJZ718013])
Type of motor starter
Direct online starter (DOL)
With short-circuit release
Yes
Rated control supply voltage Us at AC 50HZ
110 - 110 V
Rated control supply voltage Us at AC 60HZ
120 - 120 V
Rated control supply voltage Us at DC
0 - 0 V
Voltage type for actuating
AC
Rated operation power at AC-3, 230 V, 3-phase
0.18 kW
Rated operation power at AC-3, 400 V
7.5 kW
Rated power, 460 V, 60 Hz, 3-phase
0.37 kW
Rated power, 575 V, 60 Hz, 3-phase
0.37 kW
Rated operation current Ie
16.7 A
Rated operation current at AC-3, 400 V
1.2 A
Overload release current setting
0.3 - 1.2 A
Rated conditional short-circuit current, type 1, 480 Y/277 V
0 A
Rated conditional short-circuit current, type 1, 600 Y/347 V
0 A
Rated conditional short-circuit current, type 2, 230 V
0 A
Rated conditional short-circuit current, type 2, 400 V
0 A
Number of auxiliary contacts as normally open contact
1
Number of auxiliary contacts as normally closed contact
0
Ambient temperature, upper operating limit
55 °C
Temperature compensated overload protection
Yes
Release class
Adjustable
Type of electrical connection of main circuit
Screw connection
Type of electrical connection for auxiliary- and control current circuit
Screw connection
Rail mounting possible
Yes
With transformer
No
Number of command positions
0
Suitable for emergency stop
No
Coordination class according to IEC 60947-4-3
Class 2
Number of indicator lights
0
External reset possible
No
With fuse
No
Degree of protection (IP)
IP20
Degree of protection (NEMA)
Other
Supporting protocol for TCP/IP
No
Supporting protocol for PROFIBUS
No
Supporting protocol for CAN
No
Supporting protocol for INTERBUS
No
Supporting protocol for ASI
No
Supporting protocol for Modbus
No
Supporting protocol for Data-Highway
No
Supporting protocol for DeviceNet
No
Supporting protocol for SUCONET
No
Supporting protocol for LON
No
Supporting protocol for PROFINET IO
No
Supporting protocol for PROFINET CBA
No
Supporting protocol for SERCOS
No
Supporting protocol for Foundation Fieldbus
No
Supporting protocol for EtherNet/IP
No
Supporting protocol for AS-Interface Safety at Work
No
Supporting protocol for DeviceNet Safety
No
Supporting protocol for INTERBUS-Safety
No
Supporting protocol for PROFIsafe
No
Supporting protocol for SafetyBUS p
No
Supporting protocol for other bus systems
No
Width
45 mm
Height
272 mm
Depth
145 mm

ETIM for 167802 Low-voltage industrial controls and switchgear (EC001037)
Feature Name Feature Value
Type of motor starter (EF009598) Direct starter
With short-circuit release (EF006691) Yes
Rated control supply voltage AC 50 Hz (EF003978) 110 V
Rated control supply voltage AC 60 Hz (EF003979) 120 V
Rated control supply voltage DC (EF003980) 0 V
Voltage type for actuating (EF008242) AC
Rated operation power at AC-3, 230 V, 3-phase (EF009599) 0.18 kW
Rated operation power at AC-3, 400 V (EF001364) 7.5 kW
Rated power, 460 V, 60 Hz, 3-phase (EF009600) 0.37 kW
Rated power, 575 V, 60 Hz, 3-phase (EF009601) 0.37 kW
Rated operation current Ie (EF001443) 16.7 A
Rated operation current at AC-3, 400 V (EF009602) 1.2 A
Overload release current setting (EF002336) 0.3 A
Rated conditional short-circuit current, type 1, 480 Y/277 V (EF009607) 0 A
Rated conditional short-circuit current, type 1, 600 Y/347 V (EF009608) 0 A
Rated conditional short-circuit current, type 2, 230 V (EF009606) 0 A
Rated conditional short-circuit current, type 2, 400 V (EF009605) 0 A
Number of auxiliary contacts as normally open contact (EF001376) 1
Number of auxiliary contacts as normally closed contact (EF001377) 0
Ambient temperature, upper operating limit (EF009603) 55 °C
Temperature compensated overload protection (EF009604) Yes
Release class (EF006668) Adjustable
Type of electrical connection of main circuit (EF006819) Screw connection
Type of electrical connection for auxiliary- and control current circuit (EF006979) Screw connection
Suitable for rail mounting (EF003972) No
With transformer (EF000278) No
Number of command positions (EF001372) 0
Suitable for emergency stop (EF001433) No
Coordination class according to IEC 60947-4-3 (EF012390) Class 2
Number of indicator lights (EF001965) 0
External reset possible (EF003426) No
With fuse (EF006693) No
Degree of protection (IP) (EF005474) IP20
Degree of protection (NEMA) (EF011959) Other
Supporting protocol for TCP/IP (EF003050) No
Supporting protocol for PROFIBUS (EF003052) No
Supporting protocol for CAN (EF003053) No
Supporting protocol for INTERBUS (EF003054) No
Supporting protocol for ASI (EF003051) No
Supporting protocol for Modbus (EF003057) No
Supporting protocol for Data-Highway (EF003058) No
Supporting protocol for DeviceNet (EF003059) No
Supporting protocol for SUCONET (EF003060) No
Supporting protocol for LON (EF003017) No
Supporting protocol for PROFINET IO (EF007525) No
Supporting protocol for PROFINET CBA (EF007524) No
Supporting protocol for SERCOS (EF006657) No
Supporting protocol for Foundation Fieldbus (EF007522) No
Supporting protocol for EtherNet/IP (EF007521) No
Supporting protocol for AS-Interface Safety at Work (EF007519) No
Supporting protocol for DeviceNet Safety (EF007520) No
Supporting protocol for INTERBUS-Safety (EF006662) No
Supporting protocol for PROFIsafe (EF007526) No
Supporting protocol for SafetyBUS p (EF007527) No
Supporting protocol for other bus systems (EF003062) No
Width (EF000008) 45 mm
Height (EF000040) 272 mm
Depth (EF000049) 145 mm

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.