EATON - MOELLER 157860 157860 P-SOL-XUVRD110V50H EATON ELECTRIC Undervoltage release, delayed, 110V50/60Hz, 120V50/60Hz View larger
Images are for illustrative purposes only. Please refer to data sheet for details

157860 P-SOL-XUVRD110V50H EATON ELECTRIC Undervoltage release, delayed, 110V50/60Hz, 120V50/60Hz

157860

157860

P-SOL-XUVRD110V50H

EATON - MOELLER

1 Pcs.

Undervoltage release, delayed, 110V50/60Hz, 120V50/60Hz Coil shooting; Minimum; Delayed; 110 V 50/60 Hz; 120 V 50/60 Hz The undervoltage release P-SOL-XUV responds with a delay of 600 ms.. This means that the device is systematically designed in such a way that over 93% of all brief power failures and voltage drops will not cause it to trip. This way, yield losses caused by, e.g., an unnoticed tripping of the fire alarm button will be avoided.

Automation > Under voltage coil
Solar Switches

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

Undervoltage release, delayed, 110V50/60Hz, 120V50/60Hz
The undervoltage release P-SOL-XUV responds with a delay of 600 ms.. This means that the device is systematically designed in such a way that over 93% of all brief power failures and voltage drops will not cause it to trip. This way, yield losses caused by, e.g., an unnoticed tripping of the fire alarm button will be avoided.

Delivery program

Product range
Accessories
Accessories
Shunt and undervoltage releases
Product range
Accessories
Application field
Utility buildings
Residential buildings
Description
With internal delay for bridging intermittent voltage dips and fluctuations
Contact sequence
121S018
Connection technique
Screw terminals
For use with
PKZM0
PKZM4
PKZM0-T
PKM0
PKZM01
PKE
P-SOL
PKZ-SOL
Notes

Can be fitted to left side of motor-protective circuit-breaker

Can not be combined with shunt release A-PKZ0

Technical data

General
Terminal capacitiesSolid or flexible conductor, with ferrule
1 x (0,75 - 2,5)
2 x (0,75 - 2,5) mm2
Terminal capacitiesSolid or stranded
1 x (18 - 14)
2 x (18 - 14) AWG
Main conducting paths
Rated operating voltage [Ue]
110 - 110 V AC
Pick-up-/drop-out voltage
Pick-up voltage [x Uc]
0.85 - 1.1
Power consumption
ACPull-in power [Pick-up]
3 VA
ACSealing power [Sealing]
3 VA

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation [In]
0 A
Heat dissipation per pole, current-dependent [Pvid]
0 W
Equipment heat dissipation, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
0.8 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+60 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2 Strength of materials and parts10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts10.2.7 Inscriptions
Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.8 Connections for external conductors
Is the panel builder's responsibility.
10.9 Insulation properties10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
10.9 Insulation properties10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
10.9 Insulation properties10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 6.0

Low-voltage industrial components (EG000017) / Under voltage coil (EC001022)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Undervoltage trip ([email protected] [AKF015010])
Rated control supply voltage Us at AC 50HZ
0 - 110 V
Rated control supply voltage Us at AC 60HZ
0 - 120 V
Rated control supply voltage Us at DC
0 - 0 V
Voltage type for actuating
AC
Type of electric connection
Screw connection
Number of contacts as normally open contact
0
Number of contacts as normally closed contact
0
Number of contacts as change-over contact
0
Delayed
Yes
Suitable for power circuit breaker
No
Suitable for off-load switch
Yes
Suitable for motor safety switch
No
Suitable for overload relay
No

Approvals

Specially designed for North America
No

Characteristics

Characteristic curve
1210DIA-54
Delay limit values for bridging voltage fluctuations.

Dimensions

121X008

ETIM for 157860 Low-voltage industrial controls and switchgear (EC001022)
Feature Name Feature Value
Rated control supply voltage AC 50 Hz (EF003978) 0 V
Rated control supply voltage AC 60 Hz (EF003979) 0 V
Rated control supply voltage DC (EF003980) 0 V
Voltage type for actuating (EF008242) AC
Type of electric connection (EF003961) Screw connection
Number of contacts as normally open contact (EF008256) 0
Number of contacts as normally closed contact (EF008255) 0
Number of contacts as change-over contact (EF008257) 0
Delayed (EF001541) Yes
Suitable for power circuit breaker (EF005863) No
Suitable for off-load switch (EF001543) Yes
Suitable for motor safety switch (EF005826) No
Suitable for overload relay (EF001545) No