EATON - MOELLER 12KV 20AMP 2.5" HG OIL FUSE 12KV 20AMP 2.5" HG OIL FUSE 12OHGMA20 EATON ELECTRIC Oil fuse-link, medium voltage, 20 A, AC 12 kV, BS2692 F.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

12KV 20AMP 2.5" HG OIL FUSE 12OHGMA20 EATON ELECTRIC Oil fuse-link, medium voltage, 20 A, AC 12 kV, BS2692 F..

12KV 20AMP 2.5" HG OIL FUSE

12OHGMA20

12OHGMA20

EATON - MOELLER

3 Pcs.

Oil fuse-link, medium voltage, 20 A, AC 12 kV, BS2692 F02, 254 x 63.5 mm, back-up, BS, IEC, ESI, with striker 12KV 20AMP 2.5" HG OIL FUSE Fuse, Oil fuse-link, medium voltage, 20 A, AC 12 kV, BS2692 F02, 359 x 63.5 mm, back-up, BS, IEC, ESI, with striker, cylindrical, oil-tight, protection of primary side transformer, and oil-filled fuse switch combination unit, BS2692-1, IEC 60282-1, ESI 12-8, Breaking Capacity 40 kA

Automation > Medium-/high voltage fuse
Bussmann Series Medium Voltage fuses and accessories

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Add your required quantity to begin.

No account, online checkout or payment is required.

More info

General specifications

Product Name
Eaton Bussmann series medium voltage oil fuse
Catalog Number
12OHGMA20
EAN
5027590432757
UPC
051712585811
Product Length/Depth
359 mm
Product Height
63.5 mm
Product Width
63.5 mm
Product Weight
2600 g
Compliances
BS 2692-1
ESI 12-8
Certifications
IEC Rated
IEC60282-1
KEMA

Product specifications

Type
fuse
Application
protection of primary side transformer, and oil-filled fuse switch combination unit
Amperage Rating
20 A
Fuse indicator
with striker
Fuse size
63.5 x 359 mm
Breaking capacity
40 kA
Installation technique
Oil
Performance Cat According To IEC 60282-1
Back-up
Product application
Primary side transformer protection
Rated frequency - max
60 Hz
Rated frequency - min
50 Hz
Release characteristic
Other
Standard
British Standard
Utilization category
Other
Voltage type
AC
With striker
Yes
Fuse diameter
63.5 mm
Joule integral (I2T) - max operating
5 x 103
Joule integral (I2T) - min pre-arcing
3.4 x 102
Resistance
77
Class
Class back-up
Barrels
1
Construction type
F02/BS 2692
Fuse shape
Cylindrical
Interrupt rating
40 kAIC
Construction size
63.5 x 359 mm
Voltage rating
12 kV
Fuse type
OHGM

ETIM for 12OHGMA20 Circuit breakers and fuses (EC003507)
Feature Name Feature Value
Rated current (EF000227) 20 A
Rated voltage (EF000228) 12 kV
Voltage type (EF000187) AC
Rated frequency (EF001663) 50 Hz
Breaking capacity (EF005617) 40 kA
Utilization category according to IEC 60269 (EF002572) Other
Application (EF000041) Primary side transformer protection
Length (EF001438) 359 mm
Diameter (EF000551) 63.5 mm
Performance category according to IEC 60282-1 (EF012539) Back-up
With striker (EF008175) Yes
Standard (EF009322) British Standard
Release characteristic (EF000889) Other
Installation technique (EF001474) Oil

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.