A moulded case circuit breaker is an essential protective device designed to safeguard electrical circuits from overloads and short circuits in industrial power distribution systems. This Abb 1SDA068003R1 unit provides reliable switching and fault interruption for downstream equipment.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- ABB Site Meeting Group Waste To Landfill Target: UL 2799 Zero Waste To Landfill Validation available
- End Of Life Disassembling Instructions: 9AKK108468A2349
- Environmental Product Declaration - EPD: 9AKK108469A1855
- Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops - Standard EN45555 - 55.70 %
- REACH Declaration: 9AKK108466A1425
- RoHS Declaration: 9AKK108466A1424
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- Toxic Substances Control Act - TSCA: 9AKK108467A8326
- Environmental Information: 9AKK108467A6707
- Order Code US and Canada: XT2VE3100KFF000XXX
- E-Number (Norway): 4379484
- EAN: 8015644018993
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85362090
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 9AKK108468A2349 |
| Environmental Product Declaration - EPD | 9AKK108469A1855 |
| 9AKK108468A1897 | |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 55.70 % |
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| Ordering | |
| Order Code US and Canada | XT2VE3100KFF000XXX |
| E-Number (Norway) | 4379484 |
| EAN | 8015644018993 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 90 mm |
| Product Net Height | 130 mm |
| Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 1.12 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 131 mm |
| Package Level 1 Height | 212 mm |
| Package Level 1 Depth / Length | 147 mm |
| Package Level 1 Gross Weight | 1.22 kg |
| Package Level 1 EAN | 8015644018993 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Motor Protection |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Version | F |
| CAD Dimensional Drawing | 1SDH002230A1001 |
| Technical | |
| Connecting Capacity Main Circuit | Busbar 32.5..100 mm² |
| Current Type | AC |
| Electrical Durability | 120 cycles per hour |
| 8000 cycle | |
| Mechanical Durability | 240 cycles per hour |
| 25000 cycle | |
| Number of Poles | 3P |
| Opening Time | CB with SOR 30 ms |
| CB with UVR 30 ms | |
| Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 4.2 W |
| Rated Current (In) | 100 A |
| Rated Frequency (f) | 50 / 60 Hz |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 200 kA |
| (230 V AC) 200 kA | |
| (240 V AC) 200 kA | |
| (380 V AC) 150 kA | |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 70 kA | |
| (525 V AC) 50 kA | |
| (690 V AC) 15 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 200 kA |
| (230 V AC) 200 kA | |
| (240 V AC) 200 kA | |
| (380 V AC) 150 kA | |
| (415 V AC) 150 kA | |
| (440 V AC) 150 kA | |
| (500 V AC) 70 kA | |
| (525 V AC) 50 kA | |
| (690 V AC) 20 kA | |
| Rated Uninterrupted Current (Iu) | 160 A |
| Rated Voltage (Ur) | 690 V |
| Recommended Screw Driver | Main Circuit M6 |
| Release | Ekip M-I |
| Release Type | EL |
| Short-Circuit Performance Level | V |
| Standards | IEC60947-2 |
| Sub-type | XT2 |
| Terminal Connection Type | Front |
| Terminal Type | Bolt |
| Tightening Torque | 6 N·m |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK106713A5901 |
| GL Certificate | 1SDL000163R0093 |
| LR Certificate | 1SDL000163R0100 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Dimension Diagram | 1SDH000721R0100 |
| Mechanical Drawings | 1SDH000721R0100 |
| Wiring Diagram | 1SDM000068R0001 |
| Instructions and Manuals | 1SDH000721R0001 |
| 1SDH000721R0507 | |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| UNSPSC | 39120000 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |