View larger
1SDA067871R1 ABB XT2H 160 Ekip LSI In 160A 3p F F
1SDA067871R1
067871
ABB
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
XT2
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An ABB XT2H 160 Ekip LSI In 160A 3p F F is a molded case circuit breaker designed to interrupt fault currents and protect electrical distribution branches in commercial and industrial environments. Featuring electronic trip units, these circuit breakers ensure reliable overload and short-circuit protection for equipment feeds. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- Circular Design Principles Recyclability Rate: Design for Closing Resource Loops - Standard EN45555 - 55.70 %
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- End of Life Instructions: 9AKK108468A2349
- Group Waste to Landfill Target: UL 2799 Zero Waste To Landfill Validation available
- Toxic Substances Control Act - TSCA: 9AKK108467A8326
- Environmental Product Declaration - EPD: 9AKK108469A1855
- Environmental Information: 9AKK108467A6707
- REACH Declaration: 9AKK108466A1425
- RoHS Information: 9AKK108466A1424
- RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- SCIP: 14b8d727-d8c0-470c-becc-309aaa5c2d28 Italy (IT)
- Simplified SCIP: c88b15e8-cda6-468b-8489-e726a0f69450 Germany (DE)
- Order Code US and Canada: XT2HE3160FFF000XXX
- EAN: 8015644017675
- Minimum Order Quantity: 1 piece
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate | Design for Closing Resource Loops - Standard EN45555 - 55.70 % |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| End of Life Instructions | 9AKK108468A2349 |
| Group Waste to Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| Eco Transparency | |
| Environmental Product Declaration - EPD | 9AKK108469A1855 |
| 9AKK108468A1897 | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Information | 9AKK108466A1424 |
| RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | 14b8d727-d8c0-470c-becc-309aaa5c2d28 Italy (IT) |
| Simplified SCIP | c88b15e8-cda6-468b-8489-e726a0f69450 Germany (DE) |
| 91b411a7-ffc9-43b3-97ea-3397465027bd Netherlands (NL) | |
| d12b3c0a-7436-427c-8190-c1c8f6a6cf04 Germany (DE) | |
| 533d9093-211d-4295-a720-75be5bd81a86 Germany (DE) | |
| ffe2644b-4dbc-439a-815a-bb44739bc072 France (FR) | |
| 6cacaa2b-fd04-4420-a30c-6b218727c31f Netherlands (NL) | |
| dbac8a60-6fcf-4be1-9f28-5b549e03a1cf Spain (ES) | |
| c8a5966d-d992-4480-99b4-ce5793ae60ca Netherlands (NL) | |
| 80cb4f8b-1d7f-4ca7-b891-f838decd8048 Bulgaria (BG) | |
| bad93a42-b8ef-4662-886d-f7a87ed44e21 Sweden (SE) | |
| 3f82cf82-e76f-488b-93ab-f90a5385f2d2 Poland (PL) | |
| 54a2d84c-fb1a-422b-90a7-2566e5dd2d08 France (FR) | |
| 6fcbfcb0-0d9b-4f80-8fa1-9fd40b05b360 Sweden (SE) | |
| 40d320ef-4340-424b-8634-f4c653faefec Poland (PL) | |
| cfae4b12-6790-4eb9-825c-ca4e1df3c354 Norway (NO) | |
| 2c0c0596-51bc-404a-a927-149e4743f086 Finland (FI) | |
| f6b14e7d-0a1a-49cc-8f22-f43d49c626eb Netherlands (NL) | |
| 89fb6454-2d1b-4c24-997d-66b7ccb96dae Germany (DE) | |
| 1f3ac166-4531-41a1-bb3f-c6bf1b74bb80 Denmark (DK) | |
| a2ff4099-52af-43bd-beae-be4aca6ecd2c Netherlands (NL) | |
| 0e1214a4-f81d-42da-83a4-9877d81bf827 Estonia (EE) | |
| ffe25668-ee29-4750-8819-96153c50f36c Greece (GR) | |
| 3f8adcfa-fa2a-4e4c-b625-0deeac834269 Portugal (PT) | |
| 61c1389f-5626-44e3-ae0b-dde296e59ca9 Germany (DE) | |
| 04521e5b-9d21-43dc-8aee-0fae6b09ade2 Croatia (HR) | |
| 1be294d0-cae3-4b46-97d0-b748e7fda98f Czech Republic (CZ) | |
| 5254db35-d08f-4bcf-9833-3dd5f61c47cc Poland (PL) | |
| Ordering | |
| Order Code US and Canada | XT2HE3160FFF000XXX |
| EAN | 8015644017675 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 90 mm |
| Product Net Height | 130 mm |
| Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 1.2 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 130 mm |
| Package Level 1 Height | 208 mm |
| Package Level 1 Depth / Length | 145 mm |
| Package Level 1 Gross Weight | 1.22 kg |
| Package Level 1 EAN | 8015644017675 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Power Distribution |
| Connecting Capacity Main Circuit | Busbar 32.5..100 mm² |
| Current Type | AC |
| Electrical Durability | 120 cycles per hour |
| 8000 cycle | |
| Mechanical Durability | 240 cycles per hour |
| 25000 cycle | |
| Number of Poles | 3 |
| Opening Time | CB with SOR 15 ms |
| CB with UVR 15 ms | |
| Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 10.80 W |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Rated Current (In) | 160 A |
| Rated Frequency (f) | 50/60 Hz |
| Rated Voltage (Ur) | 690 V AC |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V AC |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 100 kA |
| (230 V AC) 100 kA | |
| (240 V AC) 100 kA | |
| (380 V AC) 70 kA | |
| (415 V AC) 70 kA | |
| (440 V AC) 65 kA | |
| (500 V AC) 50 kA | |
| (525 V AC) 30 kA | |
| (690 V AC) 15 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 100 kA |
| (230 V AC) 100 kA | |
| (240 V AC) 100 kA | |
| (380 V AC) 70 kA | |
| (415 V AC) 70 kA | |
| (440 V AC) 65 kA | |
| (500 V AC) 50 kA | |
| (525 V AC) 30 kA | |
| (690 V AC) 15 kA | |
| Rated Uninterrupted Current (Iu) | 160 A |
| Recommended Screw Driver | Main Circuit M6 |
| Release | Ekip LSI |
| Release Type | EL |
| Short-Circuit Performance Level | H |
| Standards | IEC60947-2 |
| Sub-type | XT2 |
| Terminal Connection Type | Front |
| Terminal Type | Bolt |
| Tightening Torque | 6 N·m |
| Version | F |
| CAD Dimensional Drawing | 1SDH002230A1001 |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK106713A5901 |
| GL Certificate | 1SDL000163R0093 |
| LR Certificate | 1SDL000163R0100 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Dimension Diagram | 1SDH000721R0100 |
| Mechanical Drawings | 1SDH000721R0100 |
| Wiring Diagram | 1SDM000068R0001 |
| Instructions and Manuals | 1SDH000721R0001 |
| 1SDH000721R0506 | |
| Classifications | |
| ETIM 7 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| UNSPSC | 39120000 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |