View larger
1SDA067396R1 ABB XT1C 160 TMD 80-800 3p F F
1SDA067396R1
067396
ABB
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
XT1
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
1SDA067396R1 ABB XT1C 160 TMD 80-800 3p F F serves as a compact molded case circuit breaker designed to protect sub-distribution circuits from overloads and short circuits. Industrial machinery and control panels utilize units like this to ensure safe power disconnection during electrical faults. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- Circular Design Principles Recyclability Rate: Design for Closing Resource Loops - Standard EN45555 - 55.9 %
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- End of Life Instructions: 9AKK108468A2347
- Group Waste to Landfill Target: UL 2799 Zero Waste To Landfill Validation available
- Toxic Substances Control Act - TSCA: 9AKK108467A8326
- Environmental Product Declaration - EPD: 9AKK108468A1890
- Environmental Information: 9AKK108467A6707
- REACH Declaration: 9AKK108466A1425
- RoHS Information: 9AKK108466A1424
- RoHS Status: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- SCIP: 62bbce4d-080f-4d86-9d81-b900472c629b Italy (IT)
- Simplified SCIP: 479f51fc-294e-4dd6-895e-e829ac0b81e1 Poland (PL)
- Order Code US and Canada: XT1CE3080AFF000XXX
- E-Number (Finland): 3638627
- EAN: 8015644695200
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| Circular Value | |
| Circular Design Principles Recyclability Rate | Design for Closing Resource Loops - Standard EN45555 - 55.9 % |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| End of Life Instructions | 9AKK108468A2347 |
| Group Waste to Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| Eco Transparency | |
| Environmental Product Declaration - EPD | 9AKK108468A1890 |
| 9AKK108468A7793 | |
| Environmental | |
| Environmental Information | 9AKK108467A6707 |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Information | 9AKK108466A1424 |
| RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | 62bbce4d-080f-4d86-9d81-b900472c629b Italy (IT) |
| Simplified SCIP | 479f51fc-294e-4dd6-895e-e829ac0b81e1 Poland (PL) |
| 55b895cf-afa9-4baa-9ab8-1a4e51392550 France (FR) | |
| 2ff5a69b-4b7b-4aa0-aaca-580fc33c244a Sweden (SE) | |
| c6d4ab2c-2876-4862-a074-95b19ec7a5db Germany (DE) | |
| 0564b919-5fdc-4fac-83de-b868b1cf479a Hungary (HU) | |
| 30e03275-97e9-43fd-950a-c41477e4f724 Hungary (HU) | |
| 3f2635c8-8b68-4411-83d9-38c9ab429218 Germany (DE) | |
| b059d5cc-c10c-470b-b91a-8c5fba296910 Poland (PL) | |
| 352d50a8-6362-4006-aab7-149019f3a151 Netherlands (NL) | |
| ddd923fd-da41-4ae8-91dc-fc97e42eee32 Bulgaria (BG) | |
| 9afe4ace-6b6c-49ee-9880-5a365d758903 Belgium (BE) | |
| 752d4914-a434-422a-bf45-6467cc38fa93 Spain (ES) | |
| a1bdc34a-9ba6-4c5a-8124-e25737c8623e Sweden (SE) | |
| 59c45024-6b55-426e-939d-feef3baa0f33 Poland (PL) | |
| 76b7bfaf-8556-461f-9862-8cef9d327ecc Norway (NO) | |
| 99ecf823-5fdb-4e14-abf2-810261830484 Finland (FI) | |
| 7385ef91-2bd9-48a2-8c37-7dd4b14991c9 Belgium (BE) | |
| d34e8069-d92d-4d9f-bce5-dfbd55f31e6d Germany (DE) | |
| f93d3bb5-6874-4bfb-bc53-7426f177f77d Greece (GR) | |
| 264b5eaa-e9ff-4830-b97e-bc7991ec2f8c Portugal (PT) | |
| abf903d0-ee30-4afb-bf25-aff4181635e9 Germany (DE) | |
| 6ac49de9-8f8e-476d-816d-1483a6ffa760 Croatia (HR) | |
| 0acc9fa6-ca0e-4ffb-b2ca-63b2beae6d3f Czech Republic (CZ) | |
| 3e3ac273-7275-4ca1-b62e-88cce695e24b Germany (DE) | |
| 34880d7b-26c8-439a-b0c3-541a658baddc Estonia (EE) | |
| eb832ab9-ab8e-4a4f-8384-e601ee2473be Denmark (DK) | |
| Ordering | |
| Order Code US and Canada | XT1CE3080AFF000XXX |
| E-Number (Finland) | 3638627 |
| EAN | 8015644695200 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 76.2 mm |
| Product Net Height | 130 mm |
| Product Net Depth / Length | 70 mm |
| Product Net Weight | 1.1 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 128 mm |
| Package Level 1 Height | 135 mm |
| Package Level 1 Depth / Length | 143 mm |
| Package Level 1 Gross Weight | 1.133 kg |
| Package Level 1 EAN | 8015644695200 |
| Additional Information | |
| Circuit Breaker Type to be Associated | Power Distribution |
| Connecting Capacity Main Circuit | Busbar 45.5 ... 80 mm² |
| Current Type | AC/DC |
| Electrical Durability | 120 cycles per hour |
| 8000 cycle | |
| Mechanical Durability | 240 cycles per hour |
| 25000 cycle | |
| Number of Poles | 3 |
| Opening Time | CB with SOR 15 ms |
| CB with UVR 15 ms | |
| Order Multiple | 1 piece |
| Power Loss | at Rated Operating Conditions per Pole 4.8 W |
| Product Main Type | SACE Tmax XT |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Rated Current (In) | 80 A |
| Rated Frequency (f) | 50 / 60 Hz |
| Rated Voltage (Ur) | 690 V |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Instantaneous Short-Circuit Current Setting (Ii) | 800 A |
| Rated Insulation Voltage (Ui) | 800 V |
| Rated Operational Voltage | 690 V AC |
| 500 V DC | |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 40 kA |
| (230 V AC) 40 kA | |
| (240 V AC) 40 kA | |
| (380 V AC) 25 kA | |
| (415 V AC) 25 kA | |
| (440 V AC) 12.5 kA | |
| (500 V AC) 9 kA | |
| (525 V AC) 8 kA | |
| (690 V AC) 4 kA | |
| (250 V DC) 2 Poles in Series 25 kA | |
| (500 V DC) 3 Poles in Series 25 kA | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 40 kA |
| (230 V AC) 40 kA | |
| (240 V AC) 40 kA | |
| (380 V AC) 25 kA | |
| (415 V AC) 25 kA | |
| (440 V AC) 25 kA | |
| (500 V AC) 18 kA | |
| (525 V AC) 8 kA | |
| (690 V AC) 4 kA | |
| (250 V DC) 2 Poles in Series 25 kA | |
| (500 V DC) 3 Poles in Series 25 kA | |
| Rated Uninterrupted Current (Iu) | 160 A |
| Recommended Screw Driver | Main Circuit M6 |
| Release | TMD |
| Release Type | TM |
| RoHS Date | NA |
| Setting Range | 56...80 A |
| Short-Circuit Performance Level | C |
| Standards | IEC60947-2 |
| Sub-type | XT1 |
| Terminal Connection Type | Front |
| Terminal Type | Bolt |
| Tightening Torque | 6 N·m |
| Version | F |
| CAD Dimensional Drawing | 1SDH001295R0008 |
| Certificates and Declarations | |
| ATEX Certificate | No certification needed |
| Data Sheet, Technical Information | 1SDC210100D0206 |
| 1SDC210099D0206 | |
| Declaration of Conformity - CE | 9AKK106713A5532 |
| GL Certificate | 1SDL000163R0103 |
| LR Certificate | 1SDL000163R0100 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| Dimension Diagram | 1SDH000719R0100 |
| Mechanical Drawings | 1SDH000719R0100 |
| Wiring Diagram | 1SDM000068R0001 |
| Instructions and Manuals | 1SDH000719R0001 |
| Classifications | |
| ETIM 7 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 8 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| UNSPSC | 39120000 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |