View larger
GJL1311901R0002 ABB VB7-40-00-02 Mini Reversing Contactor
GJL1311901R0002
1311901
ABB
1 Pcs.
Automation > Combination of contactors
Minicontactors B6-B7
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An ABB GJL1311901R0002 VB7-40-00-02 mini reversing contactor provides specialized switching functions for multi-pole electrical loads and reversing operations inside automated control systems. Its miniature profile optimizes rail space inside cramped enclosures.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85365080
- EPLAN Data: 9AAC205200_EPLAN
- Data Sheet, Technical Information: 1SBC100214C0202
- Instructions and Manuals: 2CDC102046M6801
- CAD Dimensional Drawing: 2CDC001079B0201
- Product Net Width: 96.2 mm
- Product Net Depth / Length: 46.7 mm
- Product Net Height: 57.5 mm
- Product Net Weight: 0.355 kg
- Dimension Diagram: GJL1200447F0001
- Number of Main Contacts NO: 4
- Number of Main Contacts NC: 0
- Number of Auxiliary Contacts NO: 0
- Number of Auxiliary Contacts NC: 0
- Number of Poles: 4P
More info
▲| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85365080 |
| Popular Downloads | |
| EPLAN Data | 9AAC205200_EPLAN |
| Data Sheet, Technical Information | 1SBC100214C0202 |
| Instructions and Manuals | 2CDC102046M6801 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 96.2 mm |
| Product Net Depth / Length | 46.7 mm |
| Product Net Height | 57.5 mm |
| Product Net Weight | 0.355 kg |
| Dimension Diagram | GJL1200447F0001 |
| Technical | |
| Number of Main Contacts NO | 4 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 0 |
| Number of Auxiliary Contacts NC | 0 |
| Number of Poles | 4P |
| Standards | IEC/EN 60947-1 |
| IEC/EN 60947-4-1 | |
| IEC/EN 60947-5-1 | |
| UL 60947-1 | |
| UL 60947-4-1 | |
| IEC 60335-2-40 A2L | |
| Rated Operational Voltage | Main Circuit 690 V AC |
| Main Circuit 220 V DC | |
| Rated Frequency (f) | Control Circuit 400 Hz |
| Control Circuit 50 Hz | |
| Control Circuit 60 Hz | |
| Main Circuit 60 Hz | |
| Main Circuit 50 Hz | |
| Main Circuit DC | |
| Rated Operational Current AC-1 (Ie) | (220 / 240 V) 40 °C 20 A |
| (220 / 240 V) 55 °C 16 A | |
| (380 / 440 V) 40 °C 20 A | |
| (380 / 440 V) 55 °C 16 A | |
| (690 V) 40 °C 6 A | |
| (690 V) 55 °C 6 A | |
| Rated Operational Current AC-3 (Ie) | (230 V) 55°C 12 A |
| (400 V) 55 °C 12 A | |
| (500 V) 55 °C 9 A | |
| (690 V) NO 55°C 3.5 A | |
| Rated Operational Power AC-3 (Pe) | (230 V) Three Phase 3 kW |
| (400 V) Three Phase 5.5 kW | |
| (500 V) Three Phase 5.5 kW | |
| (690 V) Three Phase, NO 3 kW | |
| Rated Breaking Capacity AC-3 | 8 x Ie / AC-3 |
| Rated Making Capacity AC-3 | 10 x Ie / AC-3 |
| Rated Short-time Withstand Current Low Voltage (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 96 A |
| Rated Insulation Voltage (Ui) | 690 V |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp) | Main Circuit 6 kV |
| Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour |
| (AC-3) 600 cycles per hour | |
| (DC-1) 600 cycles per hour | |
| (DC-3) 600 cycles per hour | |
| Mechanical Durability | Nr. Operations 10000000 cycle |
| Coil Operating Limits | (acc. to IEC 60947-4-1) for AC supply 0.85 ... 1.1 x Uc (at θ ≤ 55 °C) |
| Rated Control Circuit Voltage (Uc) | 42 V AC |
| Power Loss | at Rated Operating Conditions AC-1 per Pole 1.4 W |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 1 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1/2x 1 ... 2.5 mm² | |
| Flexible 1/2x 1 ... 2.5 mm² | |
| Rigid 1/2x 1 ... 4 mm² | |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 1 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1/2x 1 ... 2.5 mm² | |
| Flexible 1/2x 1 ... 2.5 mm² | |
| Rigid 1/2x 1 ... 4 mm² | |
| Wire Stripping Length | Control Circuit 9 mm |
| Main Circuit 9 mm | |
| Degree of Protection | Main Circuit Terminals IP20 |
| Recommended Screw Driver | M3 |
| Pozidriv 1 | |
| Tightening Torque | Control Circuit 0.8 ... 1.1 N·m |
| Main Circuit 0.8 ... 1.1 N·m | |
| Terminal Type | Screw Terminals |
| Product Name | Mini Reversing Contactor |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| General Use Rating UL/CSA | (600 V AC) 16 A |
| Horsepower Rating UL/CSA | (115 V AC) Single Phase 0.75 Hp |
| (200 V AC) Three Phase 2 Hp | |
| (220 ... 240 V AC) Three Phase 3 Hp | |
| (230 V AC) Single Phase 1.5 Hp | |
| (440 ... 480 V AC) Three Phase 5 Hp | |
| (550 ... 600 V AC) Three Phase 5 Hp | |
| Connecting Capacity Main Circuit UL/CSA | Stranded 1/2x 22-10 AWG |
| Tightening Torque UL/CSA | Control Circuit 7 in·lb |
| Main Circuit 7 in·lb | |
| Full Load Amps Motor Use | (115 V AC) Single Phase 13.8 A |
| (200 V AC) Three Phase 7.8 A | |
| (220 ... 240 V AC) Three Phase 9.6 A | |
| (230 V AC) Single Phase 10 A | |
| (440 ... 480 V AC) Three Phase 7.6 A | |
| (550 ... 600 V AC) Three Phase 6.1 A | |
| Environmental | |
| Ambient Air Temperature | Operation -25 ... +55 °C |
| Storage -40 ... +80 °C | |
| Maximum Operating Altitude Permissible | 2000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | 11 ms Pulse 15g |
| Resistance to Vibrations | 5g 5 ... 150 Hz |
| Pollution Degree | 3 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| End Of Life Disassembling Instructions | 1SBC100156C0269 |
| Environmental Product Declaration - EPD | 1SAC200410H0001 |
| Certificates and Declarations | |
| A2L Certificate – IEC | 1SAA938000-4601 |
| CB Certificate | 1SAA938000-2002 |
| CQC Certificate | CQC2003010304064033 |
| Declaration of Conformity - CCC | 2020980304001854 |
| Declaration of Conformity - CE | 1SAD101100-3101 |
| Declaration of Conformity - UKCA | 1SAD201100-3101 |
| DNV GL Certificate | 1SAA938000-0306 |
| EAC Certificate | 1SAA920000-2702 |
| KC Certificate | 1SAA938000-1501 |
| RMRS Certificate | 1SAA938000-0704 |
| UL Certificate | E191658-19881208 |
| Container Information | |
| Package Level 1 Units | carton 5 piece |
| Package Level 1 Width | 115 mm |
| Package Level 1 Depth / Length | 280 mm |
| Package Level 1 Height | 54 mm |
| Package Level 1 Gross Weight | 1.845 kg |
| Package Level 1 EAN | 4013614417320 |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 7 | EC000010 - Combination of contactors |
| ETIM 8 | EC000010 - Combination of contactors |
| ETIM 9 | EC000010 - Combination of contactors |
| eClass | V11.0 : 27371009 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4761 >> Magnet contactor, AC-switching |