View larger
1SBL281022R5510 ABB UA30-30-10 500V 50Hz / 600V 60Hz Contactor
1SBL281022R5510
281022
ABB
1 Pcs.
Automation > Capacitor contactor
"A" FRCTLP
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Acting as an essential circuit control device, this ABB 1SBL281022R5510 contactor is utilized in electrical switchgear to regulate power distribution to heavy industrial loads. It provides reliable switching performance for automated manufacturing systems and electrical motor circuits. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85364900
- Data Sheet, Technical Information: 1SBC101140C0203
- Instructions and Manuals: FPTC407722P0001
- CAD Dimensional Drawing: 2CDC001079B0201
- Product Net Width: 54 mm
- Product Net Depth / Length: 108.3 mm
- Product Net Height: 90 mm
- Product Net Weight: 0.71 kg
- Number of Main Contacts NO: 3
- Number of Main Contacts NC: 0
- Number of Auxiliary Contacts NO: 1
- Number of Auxiliary Contacts NC: 0
- Standards: IEC/EN 60947-1, IEC/EN 60947-4-1
- Rated Operational Voltage: Auxiliary Circuit 690 V
- Rated Frequency (f): Auxiliary Circuit 50 / 60 Hz
More info
▲| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| Data Sheet, Technical Information | 1SBC101140C0203 |
| Instructions and Manuals | FPTC407722P0001 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 54 mm |
| Product Net Depth / Length | 108.3 mm |
| Product Net Height | 90 mm |
| Product Net Weight | 0.71 kg |
| Technical | |
| Number of Main Contacts NO | 3 |
| Number of Main Contacts NC | 0 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 0 |
| Standards | IEC/EN 60947-1, IEC/EN 60947-4-1 |
| Rated Operational Voltage | Auxiliary Circuit 690 V |
| Main Circuit 690 V | |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| Control Circuit 50 / 60 Hz | |
| Main Circuit 50 / 60 Hz | |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-5-1, Θ = 40 °C 16 A |
| Rated Operational Power AC-6b (Pe) | (230 / 240 V) 40 °C, 50 / 60 Hz 16 kvar |
| (230 / 240 V) 55 °C, 50 / 60 Hz 16 kvar | |
| (230 / 240 V) 70 °C, 50 / 60 Hz 11 kvar | |
| (400 / 415 V) 40 °C, 50 / 60 Hz 27.5 kvar | |
| (400 / 415 V) 70 °C, 50 / 60 Hz 19 kvar | |
| (400 / 415 V) 55 °C, 50 / 60 Hz 27.5 kvar | |
| (440 V) 40 °C, 50 / 60 Hz 30 kvar | |
| (440 V) 55 °C, 50 / 60 Hz 30 kvar | |
| (440 V) 70 °C, 50 / 60 Hz 20 kvar | |
| (500 / 550 V), 40 °C, 50 / 60 Hz 34 kvar | |
| (500 / 550 V) 55 °C, 50 / 60 Hz 34 kvar | |
| (500 / 550 V) 70 °C, 50 / 60 Hz 23.5 kvar | |
| (690 V) 40 °C, 50 / 60 Hz 45 kvar | |
| (690 V) 55 °C, 50 / 60 Hz 45 kvar | |
| (690 V) 70 °C, 50 / 60 Hz 32 kvar | |
| Rated Operational Current AC-15 (Ie) | (500 V) 2 A |
| (690 V) 2 A | |
| (24 / 127 V) 6 A | |
| (220 / 240 V) 4 A | |
| (380 / 400 V) 3 A | |
| Short-Circuit Protective Devices | Auxiliary Circuit - gG Type Fuses 10 A |
| gG Type Fuses 1.5 ... 1.8 A | |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 0.1 s 140 A |
| for 1 s 100 A | |
| Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 820 A |
| cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 340 A | |
| Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W |
| (48 V) 2.8 A / 134 W | |
| (72 V) 2 / 144 W | |
| (110 V) 1.1 A / 121 W | |
| (125 V) 1.1 / 138 W | |
| (220 V) 0.55 A / 121 W | |
| (250 V) 0.55 / 138 W | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 1000 V |
| acc. to IEC 60947-5-1 690 V | |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Mechanical Durability | 10 million |
| Maximum Mechanical Switching Frequency | 3600 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 500 V |
| 60 Hz 600 V | |
| Coil Consumption | Average Holding Value 50 Hz 12 V·A |
| Average Holding Value 60 Hz 12 V·A | |
| Average Pull-in Value 50 Hz 120 V·A | |
| Average Pull-in Value 60 Hz 140 V·A | |
| Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·A | |
| Holding at Max. Rated Control Circuit Voltage 50 Hz 3 W | |
| Holding at Max. Rated Control Circuit Voltage 60 Hz 12 V·A | |
| Holding at Max. Rated Control Circuit Voltage 60 Hz 3 W | |
| Pull-in at Max. Rated Control Circuit Voltage 50 Hz 120 V·A | |
| Pull-in at Max. Rated Control Circuit Voltage 60 Hz 140 V·A | |
| Operate Time | Between Coil De-energization and NO Contact Opening 4 ... 11 ms |
| Between Coil Energization and NO Contact Closing 8 ... 21 ms | |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting by Screws (not supplied) | 2 x M4 screws placed diagonally |
| Connecting Capacity Main Circuit | Flexible with Cable End 2.5 ... 10 mm² |
| Rigid Cable 2.5 ... 16 mm² | |
| Connecting Capacity Auxiliary Circuit | Flexible with Cable End 0.75 ... 2.5 mm² |
| Rigid Cable 1 ... 4 mm² | |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 | |
| Connecting Terminals (delivered in open position) Main Poles | M 5 (+,-) pozidriv 2 screw with 2x (5.6x6.5 mm) connector |
| Terminal Type | Screw Terminals |
| Environmental | |
| Ambient Air Temperature | Close to Contactor for Storage -60 ... +80 °C |
| Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +55 °C | |
| Near Contactor for Operation in Free Air (Uc) -40 ... 70 °C | |
| Climatic Withstand | acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Information | 2CMT2021-006277 |
| RoHS Status | Following EU Directive 2011/65/EU |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Certificates and Declarations | |
| CB Certificate | CB_CN64164-A1_1 |
| CQC Certificate | CQC2003010304060095 |
| CQC2007010309256050 | |
| Declaration of Conformity - CCC | 2020980304001610 |
| 2020980304001216 | |
| Declaration of Conformity - CE | 1SBD250805U1000 |
| Declaration of Conformity - UKCA | 1SBD250822U1000 |
| GOST Certificate | GOST_POCCFRME77B07175 |
| UL Certificate | UL-US-L312527-4104-71017991-2 |
| UL-CA-L312527-4104-71017991-2 | |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 101 mm |
| Package Level 1 Depth / Length | 115 mm |
| Package Level 1 Height | 61 mm |
| Package Level 1 Gross Weight | 0.71 kg |
| Package Level 1 EAN | 3471522074553 |
| Package Level 2 Units | box 24 piece |
| Package Level 2 Width | 300 mm |
| Package Level 2 Depth / Length | 245 mm |
| Package Level 2 Height | 308 mm |
| Package Level 2 Gross Weight | 17.04 kg |
| Package Level 3 Units | 576 piece |
| Classifications | |
| Object Classification Code | Q |
| ETIM 4 | EC001079 - Capacitor magnet contactor |
| ETIM 5 | EC001079 - Capacitor magnet contactor |
| ETIM 6 | EC001079 - Capacitor contactor |
| ETIM 7 | EC001079 - Capacitor contactor |
| ETIM 8 | EC001079 - Capacitor contactor |
| eClass | V11.0 : 27371006 |
| UNSPSC | 39121529 |