View larger
1SAZ811201R1006
811201
ABB
1 Pcs.
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| Data Sheet, Technical Information | 2CDC106069D0201 |
| Instructions and Manuals | 2CDC106051M6803 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| Ex Operating Instructions | 2CDC106085M6801 |
| Time-Current Characteristic Curve | 1SAZ800502F0006 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimension Diagram | 1SAZ800401F0001 |
| Dimensions | |
| Product Net Width | 54.9 mm |
| Product Net Height | 101.4 mm |
| Product Net Depth / Length | 106.9 mm |
| Product Net Weight | 0.382 kg |
| Technical | |
| Setting Range | 50 ... 60 A |
| Rated Operational Voltage | Auxiliary Circuit 600 V AC/DC |
| Main Circuit 690 V AC | |
| Main Circuit 440 V DC | |
| Rated Operational Current (Ie) | 60 A |
| Rated Frequency (f) | Auxiliary Circuit 50 Hz |
| Auxiliary Circuit 60 Hz | |
| Auxiliary Circuit DC | |
| Main Circuit 50 Hz | |
| Main Circuit 60 Hz | |
| Rated Impulse Withstand Voltage (Uimp) | Auxiliary Circuit 6 kV |
| Main Circuit 8 kV | |
| Rated Insulation Voltage (Ui) | 690 V |
| Number of Poles | 3 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Protected Poles | 3 |
| Conventional Free-air Thermal Current (Ith) | Auxiliary Circuit NC 6 A |
| Auxiliary Circuit NO 4 A | |
| Rated Operational Current AC-15 (Ie) | (120 V) NC 3 A |
| (120 V) NO 0.5 A | |
| (240 V) NC 3 A | |
| (240 V) NO 0.5 A | |
| (400 V) NC 0.75 A | |
| (400 V) NO 0.5 A | |
| (500 V) NC 0.75 A | |
| (500 V) NO 0.5 A | |
| Rated Operational Current DC-13 (Ie) | (125 V) NC 0.55 A |
| (125 V) NO 0.55 A | |
| (24 V) NC 1.25 A | |
| (24 V) NO 1.25 A | |
| (250 V) NC 0.27 A | |
| (250 V) NO 0.27 A | |
| (500 V) NC 0.15 A | |
| (500 V) NO 0.15 A | |
| (60 V) NC 0.55 A | |
| (60 V) NO 0.55 A | |
| Degree of Protection | Housing IP20 |
| Main Circuit Terminals IP10 | |
| Pollution Degree | 3 |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | |
| Flexible 1/2x 0.75 ... 1 mm² | |
| Flexible 1/2x 1 ... 2.5 mm² | |
| Rigid 1/2x 0.75 ... 4 mm² | |
| Connecting Capacity Main Circuit | Flexible with Ferrule 1/2x 2.5 ... 10 mm² |
| Flexible with Ferrule 1x 2.5 ... 35 mm² | |
| Flexible with Insulated Ferrule 1x 2.5 ... 35 mm² | |
| Flexible with Insulated Ferrule 1/2x 2.5 ... 10 mm² | |
| Flexible 1/2x 2.5 ... 16 mm² | |
| Flexible 1x 2.5 ... 35 mm² | |
| Rigid 1/2x 2.5 ... 16 mm² | |
| Rigid 1x 2.5 ... 35 mm² | |
| Tightening Torque | Auxiliary Circuit 1 ... 1.2 N·m |
| Main Circuit 4.0 ... 4.5 N·m | |
| Wire Stripping Length | Auxiliary Circuit 9 mm |
| Main Circuit 17 mm | |
| Recommended Screw Driver | Auxiliary Circuit Pozidriv 2 |
| Main Circuit Pozidriv 2 | |
| Mounting Position | 1 ... 6 |
| Power Loss | at Rated Operating Conditions per Pole 2.3 ... 3.4 W |
| Suitable For | AF40 |
| AF52 | |
| AF65 | |
| Standards | IEC/EN 60947-1 |
| IEC/EN 60947-4-1 | |
| IEC/EN 60947-5-1 | |
| UL 60947-1 | |
| UL 60947-4-1 | |
| IEC 60335-2-40 A2L | |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | Main Circuit 600 V AC |
| Contact Rating UL/CSA | (NC:) B600 |
| (NC:) Q600 | |
| (NO:) Q600 | |
| (NO:) D300 | |
| Connecting Capacity Main Circuit UL/CSA | Flexible 1x 12-2 AWG |
| Flexible 2x 12-6 AWG | |
| Stranded 1x 12-2 AWG | |
| Stranded 2x 12-6 AWG | |
| Connecting Capacity Auxiliary Circuit UL/CSA | Flexible 1/2x 18-12 AWG |
| Stranded 1/2x 18-12 AWG | |
| Tightening Torque UL/CSA | Auxiliary Circuit 9 ... 11 in·lb |
| Main Circuit 35 ... 40 in·lb | |
| Environmental | |
| Ambient Air Temperature | Operation -40 ... +70 °C |
| Operation Compensated -40 ... +70 °C | |
| Storage -50 ... +80 °C | |
| Ambient Air Temperature Compensation | Yes |
| Maximum Operating Altitude Permissible | 2000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | 11 ms Pulse 25g |
| Resistance to Vibrations | 5g 3 ... 150 Hz |
| RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Information | 2CMT2021-006277 |
| RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Circular Value | |
| End of Life Instructions | 1SAC200334H0001 |
| Eco Transparency | |
| Environmental Product Declaration - EPD | 1SAC200249H0001 |
| Environmental Information | 1SAC200058H0009 |
| Certificates and Declarations | |
| A2L Certificate – IEC | 1SAA941000-4601 |
| ABS Certificate | 1SAA941003-0101 |
| ATEX Certificate | 1SAA941005-3901 |
| BV Certificate | 1SAA941001-0203 |
| CB Certificate | 1SAA941015-2001 |
| CQC Certificate | CQC2014010309689432 |
| Declaration of Conformity - CCC | 2020980309000291 |
| Declaration of Conformity - CE | 1SAD101100-3503 |
| Declaration of Conformity - UKCA | 1SAD201100-3503 |
| DNV GL Certificate | 1SAA941004-0301 |
| EAC Certificate | 1SAA941002-2701 |
| IECEx Certificate | 1SAA941001-4001 |
| LR Certificate | 1SAA941003-0501 |
| RINA Certificate | RINA_ELE098115XG |
| RMRS Certificate | 1SAA941002-0701 |
| UL Certificate | E48139-20130329 |
| Container Information | |
| Package Level 1 Units | 1 piece |
| Package Level 1 Width | 123 mm |
| Package Level 1 Height | 121 mm |
| Package Level 1 Depth / Length | 82 mm |
| Package Level 1 Gross Weight | 0.466 kg |
| Package Level 1 EAN | 4013614482960 |
| Package Level 2 Units | 12 piece |
| Package Level 2 Width | 280 mm |
| Package Level 2 Height | 210 mm |
| Package Level 2 Depth / Length | 395 mm |
| Package Level 2 Gross Weight | 5.978 kg |
| Package Level 2 EAN | 4013614485367 |
| Classifications | |
| Object Classification Code | F |
| ETIM 4 | EC000106 - Thermal overload relay |
| ETIM 5 | EC000106 - Thermal overload relay |
| ETIM 6 | EC000106 - Thermal overload relay |
| ETIM 7 | EC000106 - Thermal overload relay |
| ETIM 8 | EC000106 - Thermal overload relay |
| eClass | V11.0 : 27371501 |
| UNSPSC | 39122330 |
| IDEA Granular Category Code (IGCC) | 5366 >> Thermal overload relay |
| E-Number (Finland) | 3706588 |
| E-Number (Sweden) | 3210268 |
| Feature Name | Feature Value |
|---|---|
| Adjustable current range (EF008211) | 50 A |
| Max. rated operation voltage Ue (EF007357) | 690 V |
| Mounting method (EF000003) | Direct attachment |
| Type of electrical connection of main circuit (EF006819) | Screw connection |
| Number of auxiliary contacts as normally closed contact (EF001377) | 1 |
| Number of auxiliary contacts as normally open contact (EF001376) | 1 |
| Number of auxiliary contacts as change-over contact (EF003531) | 1 |
| Release class (EF006668) | CLASS 10 |
| Reset function input (EF011940) | No |
| Reset function automatic (EF011941) | Yes |
| Reset function push-button (EF011942) | Yes |