View larger
1SDA062931R1 ABB T7L 1250 PR232/P LSI In 1250A 3p F F
1SDA062931R1
062931
ABB
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
T7
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An ABB T7L 1250 PR232/P LSI In 1250A 3p F F molded case circuit breaker serves as a protective switching device in commercial and industrial electrical distribution setups. Panel builders utilize such components to interrupt fault currents and protect downstream wiring from thermal overloads.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- REACH Declaration: 9AKK108466A1425
- RoHS Declaration: 9AKK108466A1424
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- Toxic Substances Control Act - TSCA: 9AKK108467A8326
- Environmental Information: 9AKK10103A1059
- EAN: 8015644654801
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85362090
- Product Net Width: 210 mm
- Product Net Height: 268 mm
- Product Net Depth / Length: 154 mm
- Product Net Weight: 9.7 kg
- Package Level 1 Units: 1 piece
- Package Level 1 Width: 280 mm
- Package Level 1 Height: 350 mm
More info
▲| ABB EcoSolutions | |
|---|---|
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| Environmental | |
| Environmental Information | 9AKK10103A1059 |
| 9AKK108467A6707 | |
| Ordering | |
| EAN | 8015644654801 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 210 mm |
| Product Net Height | 268 mm |
| Product Net Depth / Length | 154 mm |
| Product Net Weight | 9.7 kg |
| Container Information | |
| Package Level 1 Units | 1 piece |
| Package Level 1 Width | 280 mm |
| Package Level 1 Height | 350 mm |
| Package Level 1 Depth / Length | 360 mm |
| Package Level 1 Gross Weight | 11.2 kg |
| Package Level 1 EAN | 8015644654801 |
| Additional Information | |
| Product Main Type | SACE Tmax T |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Suitable For | T7 |
| Suitable for Product Class | Moulded Case Circuit Breakers |
| Version | F |
| Technical | |
| Electrical Durability | 2000 cycle |
| 60 cycles per hour | |
| Mechanical Durability | 10000 cycle |
| 60 cycles per hour | |
| Number of Poles | 3P |
| Power Loss | at Rated Operating Conditions per Pole 47 W |
| Rated Current (In) | 1250 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 200 kA |
| (230 V AC) 200 kA | |
| (380 V AC) 120 kA | |
| (400 V AC) 120 kA | |
| (415 V AC) 120 kA | |
| (440 V AC) 100 kA | |
| (500 V AC) 64 kA | |
| (690 V AC) 37.5 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 20 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 200 kA |
| (230 V AC) 200 kA | |
| (380 V AC) 120 kA | |
| (400 V AC) 120 kA | |
| (415 V AC) 120 kA | |
| (440 V AC) 100 kA | |
| (500 V AC) 85 kA | |
| (690 V AC) 50 kA | |
| Rated Uninterrupted Current (Iu) | 1250 A |
| Release | PR232/P-LSI |
| Release Type | EL |
| Short-Circuit Performance Level | L |
| Standards | IEC |
| Sub-type | T7 |
| Terminal Connection Type | Fixed Circuit-Breakers |
| Front | |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC210015D0201 |
| Declaration of Conformity - CE | 9AKK106713A5537 |
| EU Data Act Compliance Declaration | 1SDH002560A1001 |
| GL Certificate | 1SDL000163R0054 |
| Instructions and Manuals | 1SDC210015D0201 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| UNSPSC | 39121100 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |