View larger
1SDA060216R1 ABB T6S 800 TMA 800-8000 3p F F
1SDA060216R1
060216
ABB
1 Pcs.
Automation > Power circuit-breaker for trafo/generator/installation protection
T6
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Abb part number 1SDA060216R1 is an ABB T6S 800 TMA 800-8000 3p F F designed to protect electrical circuits from damage caused by overload currents and short circuits. Molded case circuit breakers of this caliber are standard in commercial and industrial panel boards for dependable fault isolation. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- REACH Declaration: 9AKK108466A1425
- RoHS Declaration: 9AKK108466A1424
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- Toxic Substances Control Act - TSCA: 9AKK108467A8326
- Environmental Information: 9AKK10103A1058
- EAN: 8015644626761
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85362090
- Product Net Width: 210 mm
- Product Net Height: 268 mm
- Product Net Depth / Length: 103.5 mm
- Product Net Weight: 9.117 kg
- Package Level 1 Units: 1 piece
- Package Level 1 Width: 305 mm
- Package Level 1 Height: 285 mm
More info
▲| ABB EcoSolutions | |
|---|---|
| Material Compliance | |
| REACH Declaration | 9AKK108466A1425 |
| RoHS Declaration | 9AKK108466A1424 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| Toxic Substances Control Act - TSCA | 9AKK108467A8326 |
| Environmental | |
| Environmental Information | 9AKK10103A1058 |
| 9AKK108467A6707 | |
| Ordering | |
| EAN | 8015644626761 |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85362090 |
| Dimensions | |
| Product Net Width | 210 mm |
| Product Net Height | 268 mm |
| Product Net Depth / Length | 103.5 mm |
| Product Net Weight | 9.117 kg |
| Container Information | |
| Package Level 1 Units | 1 piece |
| Package Level 1 Width | 305 mm |
| Package Level 1 Height | 285 mm |
| Package Level 1 Depth / Length | 370 mm |
| Package Level 1 Gross Weight | 11 kg |
| Package Level 1 EAN | 8015644626761 |
| Additional Information | |
| Product Main Type | SACE Tmax T |
| Product Name | Moulded Case Circuit Breaker |
| Product Type | Automatic Circuit Breaker |
| Suitable For | T6 |
| Suitable for Product Class | Moulded Case Circuit Breakers |
| Version | F |
| Technical | |
| Electrical Durability | 5000 cycle |
| 60 cycles per hour | |
| Mechanical Durability | 20000 cycle |
| 120 cycles per hour | |
| Number of Poles | 3P |
| Power Loss | at Rated Operating Conditions per Pole 31 W |
| Rated Current (In) | 800 A |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Voltage | 690 V AC |
| 750 V DC | |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (380 V AC) 50 kA | |
| (400 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 45 kA | |
| (500 V AC) 35 kA | |
| (690 V AC) 16.5 kA | |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 10 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (220 V AC) 85 kA |
| (230 V AC) 85 kA | |
| (380 V AC) 50 kA | |
| (400 V AC) 50 kA | |
| (415 V AC) 50 kA | |
| (440 V AC) 45 kA | |
| (500 V AC) 35 kA | |
| (690 V AC) 22 kA | |
| (250 V DC) 2 Poles in Series 50 kA | |
| (500 V DC) 2 Poles in Series 35 kA | |
| (750 V DC) 3 Poles in Series 20 kA | |
| Rated Uninterrupted Current (Iu) | 800 A |
| Release | TMA |
| Release Type | TM |
| Short-Circuit Performance Level | S |
| Standards | IEC |
| Sub-type | T6 |
| Terminal Connection Type | Fixed Circuit-Breakers |
| Front | |
| Test Voltage Max (Utest) | 3500 V |
| Certificates and Declarations | |
| Data Sheet, Technical Information | 1SDC210015D0201 |
| Declaration of Conformity - CE | 9AKK106713A5538 |
| Instructions and Manuals | 1SDH000511R0001 |
| External Classifications and Standards | |
| ETIM 9 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| ETIM 10 | EC000228 - Power circuit-breaker for trafo/generator/installation protection |
| Object Classification Code | Q |
| UNSPSC | 39121100 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| eClass | V11.1 : 27370409 |