View larger
2CCS863001R0804 ABB S803S-C80 High Performance Circuit Breaker
2CCS863001R0804
863001
ABB
1 Pcs.
Automation > Miniature circuit breaker (MCB)
S800S
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for robust fault management, the Abb 2CCS863001R0804 high performance circuit breaker prevents damage by isolating overloaded or short-circuited commercial and industrial lines. Industrial circuit breakers are fundamental to maintaining overall system reliability and protecting personnel. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Ambient Air Temperature: Operation -25 ... +60 °C Storage -40 ... +70 °C
- Resistance to Vibrations acc. to IEC 60068-2-6: 2 - 13.2 Hz / 1mm 13.2 - 100Hz / 0.7g with load 100% x Ie
- RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
- Standards: IEC/EN 60947-2 IEC/EN 60898-1
- Number of Poles: 3
- Tripping Characteristic: C
- Rated Current (I n ): 80 A
- Rated Operational Voltage: 400/690 V AC 375 V DC
- Power Loss: at Rated Operating Conditions per Pole 6.4 W
- Rated Insulation Voltage (U i ): 690 V AC
- Operational Voltage: Maximum 230/400 V AC Minimum 12 V AC
- Rated Frequency (f): 50 / 60 Hz
- Rated Short-Circuit Capacity (I cn ): (230 / 400 V AC) 25 kA
- Rated Ultimate Short-Circuit Breaking Capacity (I cu ): (240 / 415 V AC) 50 kA (254 / 440 V AC) 30 kA (400 / 690 V AC) 6 kA (125 V DC) 30 kA
- Rated Service Short-Circuit Breaking Capacity (I cs ): (240 / 415 V AC) 40 kA (254 / 440 V AC) 22.5 kA (400 / 690 V AC) 4 kA (125 V DC) 30 kA
- Energy Limiting Class: 3
More info
▲The S803S-C80 is a 3-pole High Performance Circuit breaker with C-characteristic, with cage terminal and a rated current of 80 A. It is a current limiting device with a maximum breaking capacity of 50kA at 240/415V. It can be used for voltages up to 400/690V and in DC as well. It has two different tripping mechanisms, the thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. The S803S-C80 complies with IEC/EN 60947-2 and allows the use for industrial applications. It has numerous of approvals, therefore it can be used worldwide. The extensive range of accessory makes the use of S803S-C80 more comfortable. Due to the fast arc extinction of S803S-C80 your application will be secured.
Ordering
- EAN:
- 7612271200817
- Minimum Order Quantity:
- 1 piece
- Customs Tariff Number:
- 85362020
Dimensions
- Product Net Width:
- 81mm
- Product Net Depth:
- 82.5mm
- Product Net Height:
- 95mm
- Product Net Weight:
- 0.74kg
Container Information
- Package Level 1 Units:
- 1 piece
- Package Level 1 Width:
- 105 mm
- Package Level 1 Length:
- 86 mm
- Package Level 1 Height:
- 99 mm
- Package Level 1 Gross Weight:
- 0.77 kg
- Package Level 1 EAN:
- 7612271200817
- Package Level 2 Units:
- 1
Environmental
- Ambient Air Temperature:
- Operation -25 ... +60 °C
Storage -40 ... +70 °C
- Resistance to Vibrations acc. to IEC 60068-2-6:
- 2 - 13.2 Hz / 1mm
13.2 - 100Hz / 0.7g
with load 100% x Ie
- Environmental Conditions:
- Damp Heat Cyclic acc. to IEC 60068-2-30 12+12 cycle
Damp Heat Cyclic acc. to IEC 60068-2-30 55°C @ 90-96%
Damp Heat Cyclic acc. to IEC 60068-2-30 25°C @ 90-100%
Dry Heat Test B acc. to IEC 60068-2-2 16 hour @ 55 °C
Dry Heat Test B acc. to IEC 60068-2-2 2 hour @ 70 °C
- RoHS Status:
- Following EU Directive 2002/95/EC August 18, 2005 and amendment
Technical
- Standards:
- IEC/EN 60947-2 IEC/EN 60898-1
- Number of Poles:
- 3
- Tripping Characteristic:
- C
- Rated Current (In):
- 80 A
- Rated Operational Voltage:
- 400/690 V AC
375 V DC
- Power Loss:
- at Rated Operating Conditions per Pole 6.4 W
- Rated Insulation Voltage (Ui):
- 690 V AC
- Operational Voltage:
- Maximum 230/400 V AC
Minimum 12 V AC
- Rated Frequency (f):
- 50 / 60 Hz
- Rated Short-Circuit Capacity (Icn):
- (230 / 400 V AC) 25 kA
- Rated Ultimate Short-Circuit Breaking Capacity (Icu):
- (240 / 415 V AC) 50 kA
(254 / 440 V AC) 30 kA
(400 / 690 V AC) 6 kA
(125 V DC) 30 kA
- Rated Service Short-Circuit Breaking Capacity (Ics):
- (240 / 415 V AC) 40 kA
(254 / 440 V AC) 22.5 kA
(400 / 690 V AC) 4 kA
(125 V DC) 30 kA
- Energy Limiting Class:
- 3
- Overvoltage Category:
- IV
- Pollution Degree:
- 3
- Rated Impulse Withstand Voltage (Uimp):
- 8 kV
- Housing Material:
- Insulation group I, RAL 7035
- Contact Position Indication:
- ON / OFF / TRIP
- Degree of Protection:
- acc. to IEC 60529 IP20
- Remarks:
- Connection from top and bottom
Connecting with CU only
IP40 in enclosure with cover
Cage terminal with captive screw
- Electrical Endurance:
- 6000 cycle
- Mechanical Endurance:
- 4000 cycle
- Terminal Type:
- Screw Terminals
- Connecting Capacity:
- Stranded 1 ... 50 mm²
Flexible 1 …70 mm²
- Tightening Torque:
- 3.5 N·m
31 in·lb
- Recommended Screw Driver:
- Pozidriv 2
- Mounting on DIN Rail:
- TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
- Mounting Position:
- Any
Certificates and Declarations (Document Number)
- Declaration of Conformity - CE:
- 2CCC413016D060
- RoHS Information:
- 2CCC413008D0204
Classifications
- E-nummer:
- 2101569
- ETIM 4:
- EC000042 - Miniature circuit breaker (MCB)
- ETIM 5:
- EC000042 - Miniature circuit breaker (MCB)
- Object Classification Code:
- F