Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
| Minimum Order Quantity: | 1 piece |
| Customs Tariff Number: | 85362020 |
| Data Sheet, Technical Information: | 2CCC413003C0208 |
| Instructions and Manuals: | 2CCC413016M0008 |
| Dimension Diagram: | 2CCC413003C0201 |
| Product Net Width: | 81 mm |
| Product Net Depth / Length: | 82.5 mm |
| Product Net Height: | 95 mm |
| Product Net Weight: | 735 g |
| Standards: | IEC/EN 60947-2 IEC/EN 60898-1 |
| Number of Poles: | 3 |
| Tripping Characteristic: | C |
| Rated Current (In): | 63 A |
| Rated Operational Voltage: | 400/690 V AC 375 V DC |
| Power Loss: | at Rated Operating Conditions per Pole 6.4 W |
| Rated Insulation Voltage (Ui): | 690 V AC |
| Operational Voltage: | Maximum 230/400 V AC Minimum 12 V AC |
| Rated Frequency (f): | 50 / 60 Hz |
| Rated Short-Circuit Capacity (Icn): | (230 / 400 V AC) 20 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu): | (240 / 415 V AC) 36 kA (254 / 440 V AC) 20 kA (400 / 690 V AC) 4.5 kA (375 V DC) 20 kA |
| Rated Service Short-Circuit Breaking Capacity (Ics): | (240 / 415 V AC) 30 kA (254 / 440 V AC) 15 kA (400 / 690 V AC) 3 kA (125 V DC) 20 kA |
| Energy Limiting Class: | 3 |
| Overvoltage Category: | IV |
| Pollution Degree: | 3 |
| Rated Impulse Withstand Voltage (Uimp): | 8 kV |
| Housing Material: | Insulation group I, RAL 7035 |
| Contact Position Indication: | ON / OFF / TRIP |
| Degree of Protection: | acc. to IEC 60529 IP20 |
| Remarks: | Connection from top and bottom Connecting with CU only IP40 in enclosure with cover Cage terminal with captive screw |
| Electrical Endurance: | 6000 cycle |
| Mechanical Endurance (Nendu): | 4000 cycle |
| Terminal Type: | Screw Terminals |
| Connecting Capacity: | Stranded 1 ... 50 mm² Flexible 1 ... 70 mm² |
| Tightening Torque: | 3.5 N·m 31 in·lb |
| Recommended Screw Driver: | Pozidriv 2 |
| Mounting on DIN Rail: | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 |
| Mounting Position: | Any |
| Ambient Air Temperature: | Operation -25 ... +60 °C Storage -40 ... +70 °C |
| Resistance to Shock acc. to IEC 60068-2-27: | 5 g 30 ms |
| Resistance to Vibrations acc. to IEC 60068-2-6: | 2 - 13.2 Hz / 1mm 13.2 - 100Hz / 0.7g with load 100% x Ie |
| Environmental Conditions: | Damp Heat Cyclic acc. to IEC 60068-2-30 12+12 cycle Damp Heat Cyclic acc. to IEC 60068-2-30 55°C @ 90-96% Damp Heat Cyclic acc. to IEC 60068-2-30 25°C @ 90-100% Dry Heat Test B acc. to IEC 60068-2-2 16 hour @ 55 °C Dry Heat Test B acc. to IEC 60068-2-2 2 hour @ 70 °C |
| RoHS Status: | Following EU Directive 2011/65/EU |
| Declaration of Conformity - CE: | 2CCC413016D0601 |
| Environmental Information: | 2CCY413207D0203 |
| Instructions and Manuals: | 2CCC413016M0008 |
| RoHS Information: | 2CCC413008D0206 |
| Package Level 1 Units: | 1 piece |
| Package Level 1 Width: | 105 mm |
| Package Level 1 Depth / Length: | 86 mm |
| Package Level 1 Height: | 99 mm |
| Package Level 1 Gross Weight: | 770 g |
| Package Level 1 EAN: | 7612271204600 |
| Package Level 2 Units: | 1 |
| Object Classification Code: | F |
| E-nummer: | 2101538 |
| ETIM 4: | EC000042 - Miniature circuit breaker (MCB) |
| ETIM 5: | EC000042 - Miniature circuit breaker (MCB) |
| ETIM 6: | EC000042 - Miniature circuit breaker (MCB) |
| ETIM 7: | EC000042 - Miniature circuit breaker (MCB) |
| Feature Name | Feature Value |
|---|---|
| Built-in depth (EF000218) | 82.5 mm |
| Release characteristic (EF000889) | C |
| Number of poles (total) (EF008618) | 3 |
| Number of protected poles (EF005548) | 3 |
| Rated current (EF000227) | 63 A |
| Rated voltage (EF000228) | 400 V |
| Rated insulation voltage Ui (EF001366) | 690 V |
| Rated impulse withstand voltage Uimp (EF011980) | 8 kV |
| Voltage type (EF000187) | AC/DC |
| Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V (EF009555) | 20 kA |
| Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V (EF009558) | 36 kA |
| Frequency (EF000416) | 50 Hz |
| Current limiting class (EF002568) | 3 |
| Flush-mounted installation (EF007517) | No |
| Concurrently switching neutral conductor (EF005997) | No |
| Over voltage category (EF002569) | 4 |
| Pollution degree (EF002570) | 3 |
| Additional equipment possible (EF008148) | Yes |
| Width in number of modular spacings (EF002950) | 4.5 |
| Degree of protection (IP) (EF005474) | IP20 |
| Ambient temperature during operating (EF007515) | -25 °C |
| Connectable conductor cross section multi-wired (EF007343) | 0 mm² |
| Connectable conductor cross section solid-core (EF007337) | 0 mm² |
| Explosion-proof (EF004663) | No |