View larger
2CCS862001R0065 ABB S802S-B6 High Performance Circuit Breaker
2CCS862001R0065
862001
ABB
1 Pcs.
Automation > Miniature circuit breaker (MCB)
S800S
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Abb S802S-B6 high performance circuit breaker serves as a reliable protective mechanism designed to interrupt abnormal electrical currents within industrial control systems. These specialized components safeguard wiring infrastructure and connected automation hardware against thermal overloads and short circuits.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Ambient Air Temperature: Operation -25 ... +60 °C Storage -40 ... +70 °C
- Resistance to Vibrations acc. to IEC 60068-2-6: 2 - 13.2 Hz / 1mm 13.2 - 100Hz / 0.7g with load 100% x Ie
- RoHS Status: Following EU Directive 2002/95/EC August 18, 2005 and amendment
- Standards: IEC/EN 60947-2 IEC/EN 60898-1
- Number of Poles: 2
- Tripping Characteristic: B
- Rated Current (I n ): 6 A
- Rated Operational Voltage: 400/690 V AC 250 V DC
- Power Loss: at Rated Operating Conditions per Pole 1.8 W
- Rated Insulation Voltage (U i ): 690 V AC
- Rated Frequency (f): 50 / 60 Hz
- Rated Ultimate Short-Circuit Breaking Capacity (I cu ): (240 / 415 V AC) 50 kA (254 / 440 V AC) 30 kA (400 / 690 V AC) 6 kA (125 V DC) 30 kA
- Rated Service Short-Circuit Breaking Capacity (I cs ): (240 / 415 V AC) 40 kA (254 / 440 V AC) 22.5 kA (400 / 690 V AC) 4 kA (125 V DC) 30 kA
- Overvoltage Category: IV
- Pollution Degree: 3
- Rated Impulse Withstand Voltage (U imp ): 8 kV
More info
▲The S802S-B6 is a 2-pole High Performance Circuit breaker with B-characteristic, with cage terminal and a rated current of 6 A. It is a current limiting device with a maximum breaking capacity of 50kA at 240/415V. It can be used for voltages up to 400/690V and in DC as well. It has two different tripping mechanisms, the thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. The S802S-B6 complies with IEC/EN 60947-2 and allows the use for industrial applications. It has numerous of approvals, therefore it can be used worldwide. The extensive range of accessory makes the use of S802S-B6 more comfortable. Due to the fast arc extinction of S802S-B6 your application will be secured.
Ordering
- EAN:
- 7612271408114
- Minimum Order Quantity:
- 1 piece
- Customs Tariff Number:
- 85362020
Dimensions
- Product Net Width:
- 54mm
- Product Net Depth:
- 82.5mm
- Product Net Height:
- 95mm
- Product Net Weight:
- 0.49kg
Container Information
- Package Level 1 Units:
- 1 piece
- Package Level 1 Width:
- 105 mm
- Package Level 1 Length:
- 60 mm
- Package Level 1 Height:
- 99 mm
- Package Level 1 Gross Weight:
- 0.51 kg
- Package Level 1 EAN:
- 7612271408114
Environmental
- Ambient Air Temperature:
- Operation -25 ... +60 °C
Storage -40 ... +70 °C
- Resistance to Vibrations acc. to IEC 60068-2-6:
- 2 - 13.2 Hz / 1mm
13.2 - 100Hz / 0.7g
with load 100% x Ie
- Environmental Conditions:
- Damp Heat Cyclic acc. to IEC 60068-2-30 12+12 cycle
Damp Heat Cyclic acc. to IEC 60068-2-30 55°C @ 90-96%
Damp Heat Cyclic acc. to IEC 60068-2-30 25°C @ 90-100%
Dry Heat Test B acc. to IEC 60068-2-2 16 hour @ 55 °C
Dry Heat Test B acc. to IEC 60068-2-2 2 hour @ 70 °C
- RoHS Status:
- Following EU Directive 2002/95/EC August 18, 2005 and amendment
Technical
- Standards:
- IEC/EN 60947-2 IEC/EN 60898-1
- Number of Poles:
- 2
- Tripping Characteristic:
- B
- Rated Current (In):
- 6 A
- Rated Operational Voltage:
- 400/690 V AC
250 V DC
- Power Loss:
- at Rated Operating Conditions per Pole 1.8 W
- Rated Insulation Voltage (Ui):
- 690 V AC
- Rated Frequency (f):
- 50 / 60 Hz
- Rated Ultimate Short-Circuit Breaking Capacity (Icu):
- (240 / 415 V AC) 50 kA
(254 / 440 V AC) 30 kA
(400 / 690 V AC) 6 kA
(125 V DC) 30 kA
- Rated Service Short-Circuit Breaking Capacity (Ics):
- (240 / 415 V AC) 40 kA
(254 / 440 V AC) 22.5 kA
(400 / 690 V AC) 4 kA
(125 V DC) 30 kA
- Overvoltage Category:
- IV
- Pollution Degree:
- 3
- Rated Impulse Withstand Voltage (Uimp):
- 8 kV
- Housing Material:
- Insulation group I, RAL 7035
- Contact Position Indication:
- ON / OFF / TRIP
- Degree of Protection:
- acc. to IEC 60529 IP20
- Remarks:
- Connection from top and bottom
Connecting with CU only
IP40 in enclosure with cover
Cage terminal with captive screw
- Electrical Endurance:
- 10000 cycle
- Mechanical Endurance:
- 10000 cycle
- Terminal Type:
- Screw Terminals
- Connecting Capacity:
- Stranded 1 ... 50 mm²
Flexible 1 …70 mm²
- Tightening Torque:
- 3.5 N·m
31 in·lb
- Recommended Screw Driver:
- Pozidriv 2
- Mounting on DIN Rail:
- TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
- Mounting Position:
- Any
Certificates and Declarations (Document Number)
- Declaration of Conformity - CE:
- 2CCC413016D060
- RoHS Information:
- 2CCC413008D0204
Classifications
- ETIM 4:
- EC000042 - Miniature circuit breaker (MCB)
- ETIM 5:
- EC000042 - Miniature circuit breaker (MCB)
- Object Classification Code:
- F