Request QuoteProduct Overview
2CCS811001R0634 ABB S801B-C63 High Performance Circuit Breaker provides robust electrical protection by interrupting abnormal current flows and short circuits in heavy-duty distribution systems. High-performance circuit breakers of this category are typically integrated into industrial switchgear architectures to handle high fault levels and maintain operational safety. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- ABB EcoSolutions: Yes
- EcoSolutions Profile: 9AKK108471A1082
- Recyclability Rate of the Product acc. to EN45555: Design for Closing Resource Loops - Standard EN45555 - 86.29 %
- ABB Site Meeting Group Waste To Landfill Target: No non-hazardous waste is sent to a landfill
- End Of Life Disassembling Instructions: 9AKK108470A2575
- Environmental Product Declaration - EPD: 9AKK108470A1695
- Rated Ultimate Short-Circuit Breaking Capacity (I cu ): (230 V AC) 16 kA
- Rated Service Short-Circuit Breaking Capacity (I cs ): (230 V AC) 10 kA
- Contact Position Indication: ON / OFF / TRIP
- Energy Limiting Class: 3
- Number of Protected Poles: 1
- Number of Poles: 1P
- Tightening Torque: 3.5 N·m
- Release Type: C
- Actuator Marking: I / O
- Recommended Screw Driver: Pozidriv 2
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB EcoSolutions | Yes |
| EcoSolutions Profile | 9AKK108471A1082 |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 86.29 % |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| End Of Life Disassembling Instructions | 9AKK108470A2575 |
| Environmental Product Declaration - EPD | 9AKK108470A1695 |
| 9AKK108470A1696 | |
| Technical | |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | (230 V AC) 16 kA |
| (75 V DC) 10 kA | |
| Rated Service Short-Circuit Breaking Capacity (Ics) | (230 V AC) 10 kA |
| (75 V DC) 10 kA | |
| Contact Position Indication | ON / OFF / TRIP |
| Energy Limiting Class | 3 |
| Number of Protected Poles | 1 |
| Number of Poles | 1P |
| Tightening Torque | 3.5 N·m |
| Release Type | C |
| Actuator Marking | I / O |
| Recommended Screw Driver | Pozidriv 2 |
| Accessories Available | Yes |
| Remarks | Connection from top and bottom Connecting with CU only IP40 in enclosure with cover Cage terminal with captIIIe screw |
| Connecting Capacity | Flexible 0 … 50 mm² |
| Rigid 0 … 70 mm² | |
| Terminal Type | Screw Terminals |
| Electrical | |
| Tripping Characteristic | C |
| Rated Operational Voltage | acc. to IEC 60898-1 230 V AC |
| acc. to IEC 60947-2 230 V AC | |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 500 V |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Input Voltage Type | AC/DC |
| Rated Current (In) | 63 A |
| Rated Short-Circuit Capacity | (230 / 400 V AC) 10 kA |
| Frequency (f) | 50...60 Hz |
| Rated Frequency (f) | 50/60 Hz |
| Power Loss | 6.4 W |
| at Rated Operating Conditions per Pole 6.4 W | |
| Overvoltage Category | III |
| Design | |
| Housing Material | Insulation group I, RAL 7035 |
| Material Compliance | |
| RoHS Declaration | 2CCC005083D0202 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| RoHS Date | 20211214 |
| REACH Declaration | 9AKK108470A9089 |
| REACH Information | False - does not contain substances > 0.1 mass percentage |
| REACH Date | 20250313 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108468A3363 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B | Business To Business |
| Environmental | |
| Ambient Air Temperature | Operation -25 ... +60 °C |
| Storage -40 ... +70 °C | |
| Reference Ambient Air Temperature | acc. to IEC60947-2 30 °C |
| Degree of Protection | IP20 |
| Pollution Degree | 3 |
| Environmental Information | 2CCY413207D0203 |
| Dimensions | |
| Width in Number of Modular Spacings | 1.5 |
| Product Net Width | 27 mm |
| Product Net Height | 95 mm |
| Product Net Depth / Length | 82.5 mm |
| Product Net Weight | 240 g |
| Built-In Depth (t2) | 82.5 mm |
| Engineering | |
| EPLAN Data | 9AAC174355_EPLAN |
| Ordering | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Gross Weight | 260 g |
| Replacement Product ID (NEW) | 2CCS881001R0634 |
| Certificates and Declarations | |
| CB Certificate | 9AKK107680A0829 |
| 2CCC413030D0201 | |
| Declaration of Conformity - CE | 2CCC005083D0202 |
| ESTI Certificate | 2CCC413031D0101 |
| VDE Certificate | 9AKK107680A0832 |
| Installation | |
| Instructions and Manuals | 2CCC413016M0008 |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting Position | Any |
| Popular Downloads | |
| Data Sheet, Technical Information | 9AKK108468A9560 |
| 9AKK108468A9561 | |
| 9AKK108468A9562 | |
| External Classifications and Standards | |
| ETIM 9 | EC000042 - Miniature circuit breaker (MCB) |
| ETIM 10 | EC000042 - Miniature circuit breaker (MCB) |
| eClass | V11.0 : 27141901 |
| Object Classification Code | F |
| Standards | IEC/EN 60947-2 |
| IEC/EN 60898-1 | |