View larger
2CSM142120R1201 ABB RD2 Residual Current Monitor
2CSM142120R1201
142120
ABB
1 Pcs.
Automation > Residual current monitoring relay
RD2 TRM
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A residual current monitor, specifically the ABB RD2 unit, continuously evaluates distribution networks to identify insulation breakdown and prevent unexpected electrical hazards. Industrial facilities integrate these monitors into control cabinets to track differential currents and maintain strict safety compliance. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of Residual Current: Type A
- Function: For AC-current system
- Current Rating: Response value amperage 1 2000 ... 2000 mA
- Number of Contacts: 1
- Delay Time ( τ ): Delay-On Energization, Maximum, Permitted 5 second [unit of time]
- Filter Option: no frequency filter
- Options Provided: Pre-alarm threshold: no
- Rated Voltage (U r ): 400...400 V
- Rated Operational Voltage: 230 ... 400 V AC
- Rated Control Supply Voltage (U s ): (50 Hz) 400...400 V
- Rated Frequency (f): 50 … 60 Hz
- Power Loss: 3.4 W
- Number of Contacts CO: 1
- Number of Contacts NC: 0
- Number of Contacts NO: 0
- RoHS Declaration: 9AKK106713A5627
More info
▲| Technical | |
|---|---|
| Type of Residual Current | Type A |
| Function | For AC-current system |
| Current Rating | Response value amperage 1 2000 ... 2000 mA |
| Number of Contacts | 1 |
| Delay Time (τ) | Delay-On Energization, Maximum, Permitted 5 second [unit of time] |
| Delay-On Energization, Minimum, Adjustable 0.3 second [unit of time] | |
| Filter Option | no frequency filter |
| Options Provided | Pre-alarm threshold: no |
| Electrical | |
| Rated Voltage (Ur) | 400...400 V |
| Rated Operational Voltage | 230 ... 400 V AC |
| Rated Control Supply Voltage (Us) | (50 Hz) 400...400 V |
| (60 Hz) 400...400 V | |
| Rated Frequency (f) | 50 … 60 Hz |
| Power Loss | 3.4 W |
| Number of Contacts CO | 1 |
| Number of Contacts NC | 0 |
| Number of Contacts NO | 0 |
| Material Compliance | |
| RoHS Declaration | 9AKK106713A5627 |
| RoHS Information | Following EU Directive 2011/65/EU |
| RoHS Date | 20190722 |
| REACH Declaration | 9AKK108467A9482 |
| REACH Information | False - does not contain substances > 0.1 mass percentage |
| REACH Date | 20240429 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108468A3363 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B | Business To Business |
| Dimensions | |
| Product Net Width | 35 mm |
| Product Net Height | 0.085 m |
| Product Net Depth / Length | 65 mm |
| Product Net Weight | 0.105 kg |
| Ordering | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Gross Weight | 0.15 kg |
| E-Number (Norway) | 1629760 |
| Certificates and Declarations | |
| Declaration of Conformity - CE | 9AKK106713A5627 |
| Installation | |
| Instructions and Manuals | 0400 - 9924 |
| Mounting Type | DIN-Rail |
| Popular Downloads | |
| Data Sheet, Technical Information | 9AKK107046A0424 |
| External Classifications and Standards | |
| ETIM 9 | EC001445 - Residual current monitoring relay |
| ETIM 10 | EC001445 - Residual current monitoring relay |
| eClass | V11.0 : 27371809 |
| Object Classification Code | F |
| Standards | IEC EN 62020 |