View larger
2CTB815704R1100 ABB OVR T2 4L 40-275s P TS QS
2CTB815704R1100
815704
ABB
1 Pcs.
Automation > Surge protection device for power supply systems
OVR surge protection
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Abb 2CTB815704R1100 ovr t2 4l 40-275s p ts qs is a four-pole surge protective device utilized in industrial power distribution frameworks to absorb high-energy electrical transients. It is typically installed at the main incoming supply panel to shield complex electrical assets from atmospheric disturbances.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Environmental Product Declaration - EPD: 9AKK108468A7418
- Type of Low Voltage Distribution System: TN-S
- Suitable For: To protect the systems against the transient overvoltage (lightning)
- Nominal AC Voltage of the System (U o ): 230 / 400 V
- Maximum Continuous Operating Voltage (U c ): (L-PE) 275 V
- Temporary Overvoltage Test Value (U T ): 337 V
- Rated Service Short-Circuit Breaking Capacity (I cs ): 100 kA
- Discharge Current: Nominal (8 / 20 µs) 20 kA
- Impulse Current: I (imp, 10 / 350 µs) 2 kA
- Short Circuit Withstand Icc: 100 kA
- Arrester Class: II
- Number of Protected Poles: 4
- Number of Auxiliary Contacts NC: 1
- Number of Auxiliary Contacts NO: 1
- Number of Poles: 4P
- Number of Conductors: 4
More info
▲| ABB EcoSolutions | |
|---|---|
| Environmental Product Declaration - EPD | 9AKK108468A7418 |
| Technical | |
| Type of Low Voltage Distribution System | TN-S |
| Suitable For | To protect the systems against the transient overvoltage (lightning) |
| Nominal AC Voltage of the System (Uo) | 230 / 400 V |
| Maximum Continuous Operating Voltage (Uc) | (L-PE) 275 V |
| Temporary Overvoltage Test Value (UT) | 337 V |
| Rated Service Short-Circuit Breaking Capacity (Ics) | 100 kA |
| Discharge Current | Nominal (8 / 20 µs) 20 kA |
| I (max, 8 / 20 µs) 40 kA | |
| Impulse Current | I (imp, 10 / 350 µs) 2 kA |
| Short Circuit Withstand Icc | 100 kA |
| Arrester Class | II |
| Number of Protected Poles | 4 |
| Number of Auxiliary Contacts NC | 1 |
| Number of Auxiliary Contacts NO | 1 |
| Number of Poles | 4P |
| Number of Conductors | 4 |
| Position of Neutral Terminals | Right |
| Transmission Standard | Optic |
| Version | Plug-in |
| Product Type | QS |
| Options Provided | Residential, commercial building. |
| Auxiliary Circuit Load | Minimum 12Vdc - 10mA |
| Maximum 250Vac - 1A | |
| Preventive Maintenance Feature | Yes |
| Status Indicator | Yes |
| Fuse Size | 4 modular spacing |
| Cross-Section (Across) | Maximum Conductor Solid-Stranded 35 mm² |
| Maximum Conductor Flexible 25 mm² | |
| Electrical | |
| Rated Voltage (Ur) | 230 V AC |
| Voltage Protection Level ( Up) | 1.4 kV |
| (L-N) 2.8 kV | |
| (N-PE) 1.4 kV | |
| Power Loss | Total 49 mW |
| Material Compliance | |
| RoHS Declaration | 9AKK108466A4617 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| RoHS Date | 20230707 |
| REACH Declaration | 9AKK107492A1906 |
| REACH Information | False - does not contain substances > 0.1 mass percentage |
| REACH Date | 20231212 |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108468A3363 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| WEEE B2C / B2B | Business To Consumer |
| Environmental | |
| Degree of Protection | IP20 |
| Maximum Operating Altitude Permissible | Without Derating 5000 |
| Dimensions | |
| Width in Number of Modular Spacings | 4 |
| Product Net Width | 71.2 mm |
| Product Net Height | 95.8 mm |
| Product Net Depth / Length | 76.7 mm |
| Product Net Weight | 0.6 kg |
| Ordering | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Gross Weight | 630 g |
| Certificates and Declarations | |
| CQC Certificate | 9AKK107680A1974 |
| Declaration | 2CTC432056G1701 |
| Declaration of Conformity - CE | 9AKK108466A4617 |
| Installation | |
| Instructions and Manuals | 2CTC432106M1701 |
| Mounting Type | DIN-Rail |
| Popular Downloads | |
| Data Sheet, Technical Information | 2CTC432309D0201 |
| Mechanical Drawings | 2CTC800015F1400.pdf |
| 2CTC800015F1401.dxf | |
| 2CTC800015F1402.stp | |
| 2CTC800015F1403.igs | |
| External Classifications and Standards | |
| ETIM 9 | EC000941 - Surge protection device for power supply systems |
| ETIM 10 | EC000941 - Surge protection device for power supply systems |
| UNSPSC | 39121610 |
| eClass | V11.0 : 27130805 |
| Object Classification Code | 141DCC |
| Standards | IEC 61643-11 / EN 61643-11 |