View larger
1SCA022753R5250 ABB OT800E22P switch-disconnector
1SCA022753R5250
022753
ABB
1 Pcs.
Connectors > Switch disconnector
OT
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An Abb 1SCA022753R5250 OT800E22P switch-disconnector acts as a dependable circuit control element in electrical switchboards, designed to safely make and break load currents under standard operational conditions. This category of device is commonly integrated into industrial installations to provide secure isolation for downstream machinery during maintenance work.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- End Of Life Disassembling Instructions: 1SCC301119M0201
- Environmental Information: 1SCC301232D0201
- Environmental Product Declaration - EPD: 1SCC301284D0201
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- REACH Declaration: 1SCC011021D0201
- RoHS Declaration: 1SCC011020D0201
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Toxic Substances Control Act - TSCA: 1SCC011025D0201
- Data Sheet, Technical Information: 1SCC301020C0201
- Instructions and Manuals: 1SCC301042M0211
- Mechanical Drawings: 1SCC301344F0001
- Environmental Product Declaration - EPD: 1SCC301284D0201
- Degree of Protection: Front IP00
- Environmental Information: 1SCC301232D0201
- Pollution Degree: 3
- Minimum Order Quantity: 1 piece
More info
▲| ABB EcoSolutions | |
|---|---|
| End Of Life Disassembling Instructions | 1SCC301119M0201 |
| Environmental Information | 1SCC301232D0201 |
| Environmental Product Declaration - EPD | 1SCC301284D0201 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 1SCC011021D0201 |
| RoHS Declaration | 1SCC011020D0201 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 1SCC011025D0201 |
| Popular Downloads | |
| Data Sheet, Technical Information | 1SCC301020C0201 |
| Instructions and Manuals | 1SCC301042M0211 |
| Mechanical Drawings | 1SCC301344F0001 |
| 1SCC301343F0001 | |
| OT600_800E22.igs | |
| Environmental Product Declaration - EPD | 1SCC301284D0201 |
| Environmental | |
| Degree of Protection | Front IP00 |
| Environmental Information | 1SCC301232D0201 |
| Pollution Degree | 3 |
| Ordering | |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85365080 |
| Country or Territory of Origin | Finland |
| Dimensions | |
| Product Net Width | 331 mm |
| Product Net Height | 250 mm |
| Product Net Depth / Length | 140 mm |
| Product Net Weight | 8 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 260 mm |
| Package Level 1 Depth / Length | 335 mm |
| Package Level 1 Height | 152 mm |
| Package Level 1 Gross Weight | 8.4 kg |
| Package Level 1 EAN | 6417019245126 |
| Technical | |
| Conventional Free-air Thermal Current (Ith) | Θ = 40 °C 800 A |
| Conventional Thermal Current (Ithe) | Fully Enclosed 800 A |
| Degree of Protection | Front IP00 |
| Distance Between Phases | Standard |
| Fourth Pole Position | Right Side |
| Fourth Pole Type | Switched - Simultaneous Function |
| Handle Color | Black |
| Handle Type | Handle and shaft included |
| Mechanical Durability | 10000 |
| Mounting Type | Base mounting |
| Number of Poles | 4P |
| Operating Mode | Front |
| Pollution Degree | 3 |
| Position of Line Terminals | Top In - Bottom Out |
| Bottom In - Top Out | |
| Power Loss | at Rated Operating Conditions per Pole 40 W |
| Rated Conditional Short-Circuit Current (Inc) | (800 A fuse, 500 V) 100 kA |
| (800 A fuse, 690 V) 80 kA | |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V |
| Rated Operational Current AC-21A (Ie) | (380 ... 415 V) 800 A |
| (500 V) 800 A | |
| (690 V) 800 A | |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 800 A |
| (500 V) 800 A | |
| (690 V) 800 A | |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 800 A |
| (500 V) 800 A | |
| (690 V) 800 A | |
| Rated Operational Power AC-23A (Pe) | (220 ... 240 V) 250 kW |
| (400 ... 415 V) 450 kW | |
| (500 V) 560 kW | |
| (690 V) 800 kW | |
| Rated Operational Voltage | Main Circuit 1000 V |
| Rated Short-Circuit Making Capacity (Icm) | (690 V) 80 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 20 kA |
| Special Functions | No |
| Standards | IEC 60947-3 |
| Switches Operating Mechanism | Mechanism Between the Poles |
| 22 (Between the Poles) | |
| Terminal Type | Lug terminals |
| Terminal Width | 39 mm |
| Tightening Torque | acc. IEC 60947-1 50 … 75 N·m |
| Technical UL/CSA | |
| Tightening Torque | acc. IEC 60947-1 50 … 75 N·m |
| Certificates and Declarations | |
| A2L Certificate – IEC | 1SCC301337D0201 |
| ATEX Certificate | No certification needed |
| BV Certificate | 1SCC301103D0201 |
| Declaration of Conformity - CE | 1SCC301140D2704 |
| DNV GL Certificate | 1SCC301184D0203 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 9 | EC000216 - Switch disconnector (low voltage) |
| ETIM 10 | EC000216 - Switch disconnector (AC) |
| UNSPSC | 39122221 |
| eClass | V11.1 : 27371403 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| E-Number (Finland) | 3660789 |