1SCA022785R8690 ABB OT630E12CP CHANGE-OVER SWITCH
1SCA022785R8690
022785
ABB
1 Pcs.
Connectors > Switch disconnector
OT_C
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
An 1SCA022785R8690 ABB OT630E12CP CHANGE-OVER SWITCH acts as a manual transfer switch designed to route electrical power between two alternative sources, such as a primary grid and a backup generator. These units are utilized in critical facilities and industrial plants to ensure seamless operational continuity during main power interruptions. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- End Of Life Disassembling Instructions: 1SCC303052M0201
- Environmental Information: 1SCC303050D0201
- Environmental Product Declaration - EPD: 1SCC303090D0201
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- REACH Declaration: 1SCC011021D0201
- RoHS Declaration: 1SCC011020D0201
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Data Sheet, Technical Information: 1SCC303003C0201
- Instructions and Manuals: 1SCC303008M0208
- Environmental Product Declaration - EPD: 1SCC303090D0201
- Degree of Protection: Front IP20
- Environmental Information: 1SCC303050D0201
- Pollution Degree: 3
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85365080
- Country or Territory of Origin: Finland
More info
▲| ABB EcoSolutions | |
|---|---|
| End Of Life Disassembling Instructions | 1SCC303052M0201 |
| Environmental Information | 1SCC303050D0201 |
| Environmental Product Declaration - EPD | 1SCC303090D0201 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 1SCC011021D0201 |
| RoHS Declaration | 1SCC011020D0201 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Popular Downloads | |
| Data Sheet, Technical Information | 1SCC303003C0201 |
| Instructions and Manuals | 1SCC303008M0208 |
| Environmental Product Declaration - EPD | 1SCC303090D0201 |
| Environmental | |
| Degree of Protection | Front IP20 |
| Environmental Information | 1SCC303050D0201 |
| Pollution Degree | 3 |
| Ordering | |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85365080 |
| Country or Territory of Origin | Finland |
| Dimensions | |
| Product Net Width | 311 mm |
| 12.24 in | |
| Product Net Height | 250 mm |
| 9.84 in | |
| Product Net Depth / Length | 280 mm |
| 11.02 in | |
| Product Net Weight | 15.37 kg |
| 33.89 lb | |
| Container Information | |
| Package Level 1 Units | box 1 box |
| Package Level 1 Width | 310 mm |
| 12.2 in | |
| Package Level 1 Depth / Length | 560 mm |
| 22.05 in | |
| Package Level 1 Height | 330 mm |
| 12.99 in | |
| Package Level 1 Gross Weight | 18.51 kg |
| 40.81 lb | |
| Package Level 1 EAN | 6417019256139 |
| Technical | |
| Conventional Free-air Thermal Current (Ith) | Θ = 40 °C 630 A |
| Conventional Thermal Current (Ithe) | Fully Enclosed 630 A |
| Degree of Protection | Front IP20 |
| Distance Between Phases | Standard |
| Handle Color | Black |
| Handle Type | Handle and shaft included |
| Mounting Type | Base mounting |
| Number of Poles | 3P |
| Operating Mode | Front |
| Pollution Degree | 3 |
| Position of Line Terminals | Top In - Bottom Out, Bottom In - Top Out |
| Power Loss | at Rated Operating Conditions per Pole 25 W |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Current AC-21A (Ie) | (380 ... 415 V) 630 A |
| (500 V) 630 A | |
| (690 V) 630 A | |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 630 A |
| (500 V) 630 A | |
| (690 V) 630 A | |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 630 A |
| (500 V) 630 A | |
| (690 V) 630 A | |
| Rated Operational Current AC-31B (Ie) | (380 ... 415 V) 630 A |
| Rated Operational Current AC-33B (Ie) | (380 ... 415 V) 630 A |
| Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 355 kW |
| (500 V) 400 kW | |
| (690 V) 630 kW | |
| Rated Operational Voltage | Main Circuit 1000 V |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 20 kiloampere rms |
| Switches Operating Mechanism | Mechanism Between the Poles |
| 12 (Between the Poles) | |
| Terminal Type | Screw Terminals |
| Terminal Width | 40 mm |
| Tightening Torque | acc. IEC 60947-1 50 ... 75 N·m |
| Transition Type | Open |
| Technical UL/CSA | |
| Tightening Torque | acc. IEC 60947-1 50 ... 75 N·m |
| Certificates and Declarations | |
| Declaration of Conformity - CE | 1SCC303008D2703 |
| DNV Certificate | 1SCC303138D0201 |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 9 | EC000216 - Switch disconnector (low voltage) |
| ETIM 10 | EC000216 - Switch disconnector (AC) |
| UNSPSC | 39122233 |
| eClass | V11.1 : 27371403 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| E-Number (Finland) | 3641515 |