View larger
1SCA022718R9830 ABB Switch disconnector OT600U03P
1SCA022718R9830
022718
ABB
1 Pcs.
Connectors > Switch disconnector
Manual Switches
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A switch disconnector OT600U03P manufactured by ABB acts as a manual safety breaker to interrupt electrical current in high-power setups. Units of this type are routinely integrated into electrical enclosures to ensure secure power isolation before servicing downstream equipment. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- End Of Life Disassembling Instructions: 1SCC301119M0201
- Environmental Information: 1SCC301232D0201
- Environmental Product Declaration - EPD: 1SCC301284D0201
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- REACH Declaration: 1SCC011021D0201
- RoHS Declaration: 1SCC011020D0201
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Toxic Substances Control Act - TSCA: 1SCC011025D0201
- Data Sheet, Technical Information: 1SCC301020C0201
- Instructions and Manuals: 1SCC301042M0211
- Mechanical Drawings: 1SCC301310F0001
- Degree of Protection: Front IP00
- Pollution Degree: 3
- Minimum Order Quantity: 1 piece
More info
▲| ABB EcoSolutions | |
|---|---|
| End Of Life Disassembling Instructions | 1SCC301119M0201 |
| Environmental Information | 1SCC301232D0201 |
| Environmental Product Declaration - EPD | 1SCC301284D0201 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 1SCC011021D0201 |
| RoHS Declaration | 1SCC011020D0201 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 1SCC011025D0201 |
| Popular Downloads | |
| Data Sheet, Technical Information | 1SCC301020C0201 |
| Instructions and Manuals | 1SCC301042M0211 |
| Mechanical Drawings | 1SCC301310F0001 |
| 1SCC301309F0001 | |
| OT600_800E03.igs | |
| Environmental Product Declaration - EPD | 1SCC301284D0201 |
| Environmental | |
| Degree of Protection | Front IP00 |
| Environmental Information | 1SCC301232D0201 |
| Pollution Degree | 3 |
| Ordering | |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85365080 |
| Country or Territory of Origin | Finland |
| Dimensions | |
| Product Net Width | 266 mm |
| Product Net Height | 250 mm |
| Product Net Depth / Length | 140 mm |
| Product Net Weight | 5.6 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 260 mm |
| Package Level 1 Depth / Length | 335 mm |
| Package Level 1 Height | 152 mm |
| Package Level 1 Gross Weight | 6.6 kg |
| Package Level 1 EAN | 6417019230757 |
| Technical | |
| Conventional Free-air Thermal Current (Ith) | Θ = 40 °C 600 A |
| Conventional Thermal Current (Ithe) | Fully Enclosed 600 A |
| Degree of Protection | Front IP00 |
| Distance Between Phases | Standard |
| Handle Color | Black |
| Handle Type | Handle and shaft included |
| Mechanical Durability | 10000 |
| Mounting Type | Base mounting |
| Number of Poles | 3P |
| Operating Mode | Front |
| Pollution Degree | 3 |
| Position of Line Terminals | Top In - Bottom Out |
| Bottom In - Top Out | |
| Power Loss | at Rated Operating Conditions per Pole 40 W |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V |
| Rated Operational Current AC-21A (Ie) | (500 V) 800 A |
| (690 V) 800 A | |
| (380 ... 415 V) 800 A | |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 800 A |
| (500 V) 800 A | |
| (690 V) 800 A | |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 800 A |
| (500 V) 800 A | |
| (690 V) 800 A | |
| Rated Operational Power AC-23A (Pe) | (380 ... 415 V) 450 kW |
| (500 V) 560 kW | |
| (690 V) 800 kW | |
| Rated Operational Voltage | Main Circuit 1000 V |
| Rated Short-Circuit Making Capacity (Icm) | (690 V) 80 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 20 kA |
| Special Functions | No |
| Standards | IEC 60947-3 / UL 98 / CSA C22.2 NO.4 |
| Switches Operating Mechanism | Mechanism at the End of the Switch |
| 03 (Left Side) | |
| Terminal Type | Lug terminals |
| Terminal Width | 39 mm |
| Tightening Torque | acc. IEC 60947-1 56.5 N·m |
| Technical UL/CSA | |
| Maximum Operating Voltage UL/CSA | 600 V |
| Ampere Rating | 600 A |
| Horsepower Rating UL/CSA | (acc. to UL 200 V) 150 Hp |
| (acc. to UL 208 V) 150 Hp | |
| (acc. to UL 240 V) 200 Hp | |
| (acc. to UL 480 V) 450 Hp | |
| (acc. to UL 600 V) 500 Hp | |
| Tightening Torque | acc. IEC 60947-1 56.5 N·m |
| Certificates and Declarations | |
| BV Certificate | 1SCC301103D0201 |
| Declaration of Conformity - CE | 1SCC301140D2704 |
| UL Certificate | cULus certificate OT600 |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 9 | EC000216 - Switch disconnector (low voltage) |
| ETIM 10 | EC000216 - Switch disconnector (AC) |
| UNSPSC | 39122233 |
| IDEA Granular Category Code (IGCC) | 5290 >> Disconnect switch |
| eClass | V11.1 : 27371403 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| E-Number (Finland) | 3660858 |
| E-Number (Norway) | 4372198 |