View larger
1SCA022860R1940 ABB Int. Section. control side OT400ES04
1SCA022860R1940
022860
ABB
1 Pcs.
Connectors > Switch disconnector
Manual Switches
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
This ABB 1SCA022860R1940 int. section. control side OT400ES04 functions as an essential component within high-capacity industrial switchgear configurations. Section control and switch accessories facilitate mechanical linkage and operational adjustments in modular disconnect systems across manufacturing facilities. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- End Of Life Disassembling Instructions: 1SCC301118M0201
- Environmental Information: 1SCC301266D0201
- Environmental Product Declaration - EPD: 1SCC301283D0201
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- REACH Declaration: 1SCC011021D0201
- RoHS Declaration: 1SCC011020D0201
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Toxic Substances Control Act - TSCA: 1SCC011025D0201
- Data Sheet, Technical Information: 1SCC301020C0201
- Instructions and Manuals: 1SCC301070M0207
- Mechanical Drawings: 1SCC301662F0001
- Environmental Product Declaration - EPD: 1SCC301283D0201
- Degree of Protection: Front IP00: Front IP00
- Environmental Information: 1SCC301266D0201
- Pollution Degree: 3
- Minimum Order Quantity: 1 piece
More info
▲| ABB EcoSolutions | |
|---|---|
| End Of Life Disassembling Instructions | 1SCC301118M0201 |
| Environmental Information | 1SCC301266D0201 |
| Environmental Product Declaration - EPD | 1SCC301283D0201 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 1SCC011021D0201 |
| RoHS Declaration | 1SCC011020D0201 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 1SCC011025D0201 |
| Popular Downloads | |
| Data Sheet, Technical Information | 1SCC301020C0201 |
| Instructions and Manuals | 1SCC301070M0207 |
| Mechanical Drawings | 1SCC301662F0001 |
| 1SCC301661F0001 | |
| Environmental Product Declaration - EPD | 1SCC301283D0201 |
| Environmental | |
| Degree of Protection | Front IP00 |
| Environmental Information | 1SCC301266D0201 |
| Pollution Degree | 3 |
| Ordering | |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85365080 |
| Country or Territory of Origin | Finland |
| Dimensions | |
| Product Net Width | 270 mm |
| Product Net Height | 185 mm |
| Product Net Depth / Length | 107 mm |
| Product Net Weight | 3.9 kg |
| 8.7 lb | |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 250 mm |
| 9.8 in | |
| Package Level 1 Depth / Length | 290 mm |
| 11.4 in | |
| Package Level 1 Height | 170 mm |
| 6.7 in | |
| Package Level 1 Gross Weight | 4.2 kg |
| 9.3 lb | |
| Package Level 1 EAN | 6417019308906 |
| Technical | |
| Conventional Free-air Thermal Current (Ith) | Θ = 40 °C 400 A |
| Conventional Thermal Current (Ithe) | Fully Enclosed 400 A |
| Degree of Protection | Front IP00 |
| Distance Between Phases | Standard |
| Fourth Pole Position | Right Side |
| Fourth Pole Type | Switched - Simultaneous Function |
| Handle Type | Handle and shaft not included |
| Mechanical Durability | 16000 |
| Mounting Type | Base mounting |
| Number of Poles | 4P |
| Operating Mode | Side |
| Pollution Degree | 3 |
| Position of Line Terminals | Top In - Bottom Out |
| Bottom In - Top Out | |
| Power Loss | at Rated Operating Conditions per Pole 10 W |
| Rated Conditional Short-Circuit Current (Inc) | (500 A fuse, 500 V) 100 kA |
| (500 A fuse, 690 V) 80 kA | |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Insulation Voltage (Ui) | acc. to IEC/EN 60664-1 1000 V |
| Rated Operational Current AC-21A (Ie) | (380 ... 415 V) 400 A |
| (500 V) 400 A | |
| (690 V) 400 A | |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 400 A |
| (500 V) 400 A | |
| (690 V) 400 A | |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 400 A |
| (500 V) 400 A | |
| (690 V) 400 A | |
| Rated Operational Power AC-23A (Pe) | (220 ... 240 V) 132 kW |
| (400 ... 415 V) 230 kW | |
| (500 V) 280 kW | |
| (690 V) 400 kW | |
| Rated Operational Voltage | Main Circuit 1000 V |
| Rated Short-Circuit Making Capacity (Icm) | (690 V) 65 kA |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 15 kA |
| Special Functions | No |
| Standards | IEC 60947-3 |
| Switches Operating Mechanism | Mechanism at the End of the Switch |
| 04 (Left Side) | |
| Terminal Type | Lug terminals |
| Tightening Torque | acc. IEC 60947-1 30 … 44 N·m |
| Technical UL/CSA | |
| Tightening Torque | acc. IEC 60947-1 30 … 44 N·m |
| Certificates and Declarations | |
| A2L Certificate – IEC | 1SCC301337D0201 |
| ATEX Certificate | No certification needed |
| Declaration of Conformity - CE | 1SCC301135D2704 |
| DNV GL Certificate | 1SCC301174D0204 |
| UL Certificate | No certification needed |
| VDE Certificate | No certification needed |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 9 | EC000216 - Switch disconnector (low voltage) |
| ETIM 10 | EC000216 - Switch disconnector (AC) |
| UNSPSC | 39122233 |
| IDEA Granular Category Code (IGCC) | 5290 >> Disconnect switch |
| eClass | V11.1 : 27371403 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| E-Number (Finland) | 3661715 |