View larger
Images are for illustrative purposes only. Please refer to data sheet for details
1SCA022763R6790 ABB Fuse switch OS400B03K
1SCA022763R6790
022763
ABB
1 Pcs.
Fuse switch OS400B03K
OS400B03K SWITCH FUSE
Connectors > Fuse switch disconnector
Manual Switches
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
ABB 1SCA022763R6790 fuse switch OS400B03K provides robust electrical isolation and short-circuit protection for heavy-duty industrial switchgear. These units protect downstream circuits from overloads while allowing safe manual disconnection.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- ABB Site Meeting Group Waste To Landfill Target: UL 2799 Zero Waste To Landfill Validation available
- End Of Life Disassembling Instructions: 1SCC311050M0201
- Environmental Product Declaration - EPD: 1SCC311198D0201
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- REACH Declaration: 1SCC011021D0201
- RoHS Declaration: 1SCC011020D0201
- RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- Toxic Substances Control Act - TSCA: 1SCC011025D0201
- Data Sheet, Technical Information: 1SCC311013C0201
- Instructions and Manuals: 1SCC311015M0215
- Mechanical Drawings: os315-400b03k.stp
- Environmental Product Declaration - EPD: 1SCC311198D0201
- Degree of Protection: acc. to IEC 60529 IP20
- Pollution Degree: 3
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85365080
More info
▲| ABB EcoSolutions | |
|---|---|
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| End Of Life Disassembling Instructions | 1SCC311050M0201 |
| Environmental Product Declaration - EPD | 1SCC311198D0201 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 1SCC011021D0201 |
| RoHS Declaration | 1SCC011020D0201 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 1SCC011025D0201 |
| Popular Downloads | |
| Data Sheet, Technical Information | 1SCC311013C0201 |
| Instructions and Manuals | 1SCC311015M0215 |
| Mechanical Drawings | os315-400b03k.stp |
| Environmental Product Declaration - EPD | 1SCC311198D0201 |
| Environmental | |
| Degree of Protection | acc. to IEC 60529 IP20 |
| Pollution Degree | 3 |
| Ordering | |
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85365080 |
| Country or Territory of Origin | Finland |
| Dimensions | |
| Product Net Width | 325 mm |
| Product Net Height | 230 mm |
| Product Net Depth / Length | 219 mm |
| Product Net Weight | 7 kg |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 365 mm |
| Package Level 1 Depth / Length | 360 mm |
| Package Level 1 Height | 280 mm |
| Package Level 1 Gross Weight | 7 kg |
| Package Level 1 EAN | 6417019249469 |
| Technical | |
| Conventional Free-air Thermal Current (Ith) | Θ = 40 °C 400 A |
| Conventional Thermal Current (Ithe) | Fully Enclosed 400 A |
| Degree of Protection | acc. to IEC 60529 IP20 |
| Fuse Size | B1-B4 |
| Fuse System | British Standard |
| Handle Type | Direct mounted handle |
| Mounting Type | Base mounting |
| Number of Poles | 3P |
| Operating Mode | Front |
| Pollution Degree | 3 |
| Position of Line Terminals | Top In - Bottom Out, Bottom In - Top Out |
| Power Loss | at Rated Current 36 W |
| Rated Conditional Short-Circuit Current (Inc) | (500 V) 100 kA |
| (690 V) 80 kA | |
| Rated Current (In) | Main Circuit 400 A |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Operational Current AC-21A (Ie) | (500 V) 400 A |
| (690 V) 400 A | |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 400 A |
| (500 V) 400 A | |
| (690 V) 400 A | |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 400 A |
| (500 V) 400 A | |
| (690 V) 400 A | |
| Rated Operational Power AC-23A (Pe) | (220 ... 240 V) 132 kW |
| (400 V) 220 kW | |
| (415 V) 230 kW | |
| (500 V) 280 kW | |
| (690 V) 400 kW | |
| Rated Operational Voltage | Main Circuit 690 V AC |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 14 kiloampere rms |
| Standards | IEC 60947-3 |
| Switches Operating Mechanism | 03 (Left Side) |
| Terminal Type | Lug terminals |
| Terminal Width | 25 mm |
| Tightening Torque | 30 ... 44 N·m |
| Technical UL/CSA | |
| Tightening Torque | 30 ... 44 N·m |
| Certificates and Declarations | |
| A2L Certificate – IEC | 1SCC311209D0201 |
| ATEX Certificate | No certification needed |
| CCC Certificate | CCC OS315-400 2016 |
| Declaration of Conformity - CE | 1SCC311099D2704 |
| DNV GL Certificate | 1SCC311131D0203 |
| UL Certificate | No certification needed |
| External Classifications and Standards | |
| Object Classification Code | Q |
| ETIM 9 | EC001040 - Fuse switch disconnector |
| ETIM 10 | EC001040 - Fuse switch disconnector |
| UNSPSC | 39122233 |
| IDEA Granular Category Code (IGCC) | 5291 >> Fuse switch disconnector |
| eClass | V11.1 : 27371401 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |