View larger
1SBH136001R2222 ABB NFZ22E-22 48-130V50/60HZ-DC Contactor Relay
1SBH136001R2222
136001
ABB
1 Pcs.
Automation > Contactor relay
AF contactors to 38 A
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
ABB NFZ22E-22 48-130V50/60HZ-DC Contactor Relay is utilized in electrical engineering applications to switch control signals and coordinate auxiliary circuit interactions. These industrial relays integrate smoothly into control panels to support sequential automation tasks and safety interlocking. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Minimum Order Quantity: 1 piece
- Customs Tariff Number: 85364900
- EPLAN Data: 9AAC159655_EPLAN
- Data Sheet, Technical Information: 1SBC100214C0202
- Instructions and Manuals: 1SBC101027M6801
- Instructions and Manuals (Part 2): 1SAC200017M0002
- CAD Dimensional Drawing: 2CDC001079B0201
- Product Net Width: 45 mm
- Product Net Depth / Length: 77 mm
- Product Net Height: 86 mm
- Product Net Weight: 0.31 kg
- Number of Auxiliary Contacts NO: 2
- Number of Auxiliary Contacts NC: 2
- Number of Poles: 4P
- Rated Operational Voltage: Auxiliary Circuit 690 V
- Rated Frequency (f): Auxiliary Circuit 50 / 60 Hz
More info
▲| Ordering | |
|---|---|
| Minimum Order Quantity | 1 piece |
| Customs Tariff Number | 85364900 |
| Popular Downloads | |
| EPLAN Data | 9AAC159655_EPLAN |
| Data Sheet, Technical Information | 1SBC100214C0202 |
| Instructions and Manuals | 1SBC101027M6801 |
| Instructions and Manuals (Part 2) | 1SAC200017M0002 |
| CAD Dimensional Drawing | 2CDC001079B0201 |
| Dimensions | |
| Product Net Width | 45 mm |
| Product Net Depth / Length | 77 mm |
| Product Net Height | 86 mm |
| Product Net Weight | 0.31 kg |
| Technical | |
| Number of Auxiliary Contacts NO | 2 |
| Number of Auxiliary Contacts NC | 2 |
| Number of Poles | 4P |
| Standards | IEC/EN 60947-1, IEC/EN 60947-5-1, UL 60335-2-40 LZGH2 A2L, UL 508, CSA C22.2 No. 60335-2-40 LZGH2 A2L, CSA C22.2 No. 14-13 |
| Rated Operational Voltage | Auxiliary Circuit 690 V |
| Rated Frequency (f) | Auxiliary Circuit 50 / 60 Hz |
| Control Circuit 50 / 60 Hz | |
| Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-5-1, Θ = 40 °C 16 A |
| Rated Operational Current AC-15 (Ie) | (500 V) 2 A |
| (690 V) 2 A | |
| (24 / 127 V) 6 A | |
| (220 / 240 V) 4 A | |
| (400 / 440 V) 3 A | |
| Rated Operational Current DC-13 (Ie) | (24 V) 6 A / 144 W |
| (48 V) 2.8 A / 134 W | |
| (72 V) 1 A / 72 W | |
| (110 V) 0.55 A / 60 W | |
| (125 V) 0.55 A / 69 W | |
| (220 V) 0.27 A / 60 W | |
| (250 V) 0.27 A / 68 W | |
| (400 V) 0.15 A / 60 W | |
| (500 V) 0.13 A / 65 W | |
| (600 V) 0.1 A / 60 W | |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 0.1 s 140 A |
| for 1 s 100 A | |
| Rated Insulation Voltage (Ui) | acc. to IEC 60947-5-1 690 V |
| acc. to UL/CSA 600 V | |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Maximum Electrical Switching Frequency | (AC-15) 1200 cycles per hour |
| (DC-13) 900 cycles per hour | |
| Maximum Mechanical Switching Frequency | 6000 cycles per hour |
| Rated Control Circuit Voltage (Uc) | 50 Hz 48 ... 130 V |
| 60 Hz 48 ... 130 V | |
| DC Operation 48 ... 130 V | |
| Power Loss | at 6 A per Pole 0.1 W |
| Operate Time | Between Coil De-energization and NC Contact Closing 13 ... 98 ms |
| Between Coil De-energization and NO Contact Opening 11 ... 95 ms | |
| Between Coil Energization and NC Contact Opening 38 ... 90 ms | |
| Between Coil Energization and NO Contact Closing 40 ... 95 ms | |
| Mounting on DIN Rail | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 | |
| Mounting by Screws (not supplied) | 2 x M4 Screws Placed Diagonally |
| Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | |
| Rigid Solid 1/2x 1 ... 2.5 mm² | |
| Rigid Stranded 1/2x 1 ... 2.5 mm² | |
| Connecting Capacity Control Circuit | Flexible with Ferrule 1/2x 0.75 ... 2.5 mm² |
| Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm² | |
| Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm² | |
| Rigid Solid 1/2x 1 ... 2.5 mm² | |
| Rigid Stranded 1/2x 1 ... 2.5 mm² | |
| Wire Stripping Length | Auxiliary Circuit 10 mm |
| Control Circuit 10 mm | |
| Degree of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 |
| acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 | |
| Tightening Torque | Auxiliary Circuit 1.2 N·m |
| Control Circuit 1.2 N·m | |
| Terminal Type | Screw Terminals |
| Product Name | Block Contactor Relay |
| Technical UL/CSA | |
| Connecting Capacity Auxiliary Circuit UL/CSA | Rigid Solid 1/2x 18-14 AWG |
| Rigid Stranded 1/2x 18-14 AWG | |
| Tightening Torque UL/CSA | Auxiliary Circuit 11 in·lb |
| Control Circuit 11 in·lb | |
| Environmental | |
| Ambient Air Temperature | Close to Contactor for Storage -60 ... +80 °C |
| Near Contactor for Operation in Free Air -40 ... 70 °C | |
| Climatic Withstand | Category B according to IEC 60947-1 Annex Q |
| Maximum Operating Altitude Permissible | Without Derating 3000 m |
| Resistance to Shock acc. to IEC 60068-2-27 | Closed, Shock Direction: B1 25 g |
| Open, Shock Direction: B1 5 g | |
| Shock Direction: A 30 g | |
| Shock Direction: B2 15 g | |
| Shock Direction: C1 25 g | |
| Shock Direction: C2 25 g | |
| Resistance to Vibrations | 4g Closed Position & 2g Open position 5 ... 300 Hz |
| Pollution Degree | 3 |
| Material Compliance | |
| Conflict Minerals Reporting Template (CMRT) | 9AKK108467A5658 |
| REACH Declaration | 2CMT2021-006202 |
| RoHS Declaration | 2CMT2021-006277 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| SCIP | 59ab69dc-3498-481d-aceb-c7edd2f791b8 China |
| Simplified SCIP | b631cc2e-6d47-4370-b0a1-4df3823236ee Spain |
| e6adca4b-3913-4642-810c-0f44c00bed77 Belgium | |
| e0ba0051-b9ae-45c9-b202-efbeba4198bf Hungary | |
| fcdcbfa6-f831-4728-be6c-26b00986b742 Sweden | |
| acddf924-7a1d-4ac9-a1b4-928ed37dc2b3 Germany | |
| 15555213-a2a6-4783-820f-76c5ff6a82a3 France | |
| 47597018-57c6-4756-afce-0d49561f87af France | |
| 6235eea7-a773-423d-ac9d-6f257598a2fb Germany | |
| aaeedf60-4a48-4dc3-bab0-7dfb3771cb75 Poland | |
| 79eee541-4812-4edc-b1ed-2f6f06926c04 Sweden | |
| 2c57f196-7281-4445-ae66-ae0d5203e8c4 Greece | |
| 17a36cae-a01e-4000-9ec5-a3f06cbc0eae Portugal | |
| 5d05b732-0ec8-46b2-a042-37fa4396671f Bulgaria | |
| b23a0d04-1394-40d0-992d-364c117380bf Poland | |
| bef7c8f4-ceef-43f4-a8a8-c39177547996 Netherlands | |
| 67823ffe-a187-4a48-8efe-df4ef88c2c37 Hungary | |
| 1d44f9a9-1053-460e-8b37-9cd21aeeb3fa Estonia | |
| 1b679ea7-66d4-434c-9e44-bb06f65ecfdb Croatia | |
| 48d8c1e6-46bc-48e3-8854-fcf2a4a95e09 Denmark | |
| e04c94da-c6cb-48c7-a815-b4718560fafd Germany | |
| 72b5011b-c017-4b48-8ef3-8a54394b0141 Belgium | |
| 7d95cb4d-8619-43be-a61d-ec719afe24c2 Finland | |
| e39ff55a-3a47-435e-a0c3-83a3f072079a Germany | |
| f3c98834-5407-4a33-98b8-365747f5c826 Norway | |
| 94678207-d5c2-4b46-a46d-6904663234c3 Czech Republic | |
| aef9a98a-c44b-4248-b45c-c85108ec4f83 Poland | |
| 2410fe6e-f496-42a5-90aa-69aed9ee3375 Germany | |
| Toxic Substances Control Act - TSCA | 2CMT2023-006525 |
| WEEE B2C / B2B | Business To Business |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB EcoSolutions | |
| ABB EcoSolutions | Yes |
| ABB Site Meeting Group Waste To Landfill Target | No non-hazardous waste is sent to a landfill |
| End Of Life Disassembling Instructions | 1SBC101080M6801 |
| Environmental Product Declaration - EPD | 1SBD250584E3000 |
| Improved Energy Efficiency for Customers | Product Efficiency - Product considered more energy-efficient compared to similar product on market or older products from the same line |
| Recyclability Rate of the Product acc. to EN45555 | Design for Closing Resource Loops - Standard EN45555 - 92.7 % |
| Certificates and Declarations | |
| A2L Certificate – UL | 9AKK108469A4900 |
| 9AKK108469A4902 | |
| ABS Certificate | ABS_20-2060694-PDA |
| BV Certificate | BV_2634H24899C1 |
| CB Certificate | CB_SE-116792 |
| CCC Certificate | CCC_2024010303656666 |
| Declaration of Conformity - CCC | CQC2011010303465426 |
| Declaration of Conformity - CE | 1SBD250005U1000 |
| Declaration of Conformity - UKCA | 1SBD250036U1000 |
| DNV Certificate | DNV_TAE00001BV-5 |
| EAC Certificate | EAC_RU C-FR ME77 B03544 |
| GOST Certificate | GOST_POCCFR.ME77.B07174.pdf |
| KC Certificate | KC-HW02016-21031A |
| LR Certificate | LRS_LR2003684TA-02 |
| RINA Certificate | RINA_ELE142224XG |
| RMRS Certificate | RMRS_1802702280 |
| UL Certificate | UL_20180227_E252354_2_1 |
| UL Listing Card | UL_E252354 |
| Container Information | |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 87 mm |
| Package Level 1 Depth / Length | 79 mm |
| Package Level 1 Height | 47 mm |
| Package Level 1 Gross Weight | 0.31 kg |
| Package Level 1 EAN | 3471523101722 |
| Package Level 2 Units | box 27 piece |
| Package Level 2 Width | 250 mm |
| Package Level 2 Depth / Length | 300 mm |
| Package Level 2 Height | 315 mm |
| Package Level 2 Gross Weight | 16.74 kg |
| External Classifications and Standards | |
| Object Classification Code | K |
| ETIM 7 | EC000196 - Contactor relay |
| ETIM 8 | EC000196 - Contactor relay |
| ETIM 9 | EC000196 - Contactor relay |
| eClass | V11.0 : 27371001 |
| UNSPSC | 39121529 |
| IDEA Granular Category Code (IGCC) | 4763 >> Power contactor, DC switching |
| E-Number (Finland) | 3706405 |
| E-Number (Sweden) | 3211458 |