ABB 1SAM340000R1007 1SAM340000R1007 ABB MS132-2.5T Circuit Breaker for Primary Transformer Protection View larger
Images are for illustrative purposes only. Please refer to data sheet for details

1SAM340000R1007 ABB MS132-2.5T Circuit Breaker for Primary Transformer Protection

1SAM340000R1007

340000

ABB

1 Pcs.

MS132-2.5T Circuit Breaker for Primary Transformer Protection MS132-2.5T GUARDAM. TRAP REG.1,6-2,5A MS132-2.5T Circuit Breaker for Primary Transformer Protection 1.6 ... 2.5 A

Automation > Power circuit-breaker for trafo/generator/installation protection
Mx116 and Mx132

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

An 1SAM340000R1007 ABB MS132-2.5T Circuit Breaker for Primary Transformer Protection is deployed in electrical panels to safeguard motors, transformers, and distribution circuits against overload and short-circuit conditions. These compact electromechanical devices automatically interrupt fault currents to prevent equipment damage and maintain system reliability. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Minimum Order Quantity: 1 piece
  • Customs Tariff Number: 85362010
  • Data Sheet, Technical Information: 2CDC131058D0201
  • Instructions and Manuals: 2CDC131057M6801
  • Instructions and Manuals (Part 2): 2CDC131060M0202
  • Time-Current Characteristic Curve: 1SAM300535F0007
  • I²t Characteristic: 1SAM300517F0001
  • Cut-off Current Characteristic: 1SAM300518F0001
  • CAD Dimensional Drawing: 2CDC001079B0201
  • Dimension Diagram: 1SAM300402F0001
  • Product Net Width: 45 mm
  • Product Net Height: 90 mm
  • Product Net Depth / Length: 86.75 mm
  • Product Net Weight: 0.265 kg
  • Rated Service Short-Circuit Breaking Capacity (I cs ): (230 V AC) 100 kA
  • Rated Ultimate Short-Circuit Breaking Capacity (I cu ): (400 V AC) 100 kA

More info

▲
Ordering
Minimum Order Quantity1 piece
Customs Tariff Number85362010
Popular Downloads
Data Sheet, Technical Information2CDC131058D0201
Instructions and Manuals2CDC131057M6801
Instructions and Manuals (Part 2)2CDC131060M0202
Time-Current Characteristic Curve1SAM300535F0007
I²t Characteristic1SAM300517F0001
Cut-off Current Characteristic1SAM300518F0001
CAD Dimensional Drawing2CDC001079B0201
Dimension Diagram1SAM300402F0001
Dimensions
Product Net Width45 mm
Product Net Height90 mm
Product Net Depth / Length86.75 mm
Product Net Weight0.265 kg
Technical
Rated Service Short-Circuit Breaking Capacity (Ics)(230 V AC) 100 kA
(400 V AC) 100 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(400 V AC) 100 kA
Rated Instantaneous Short-Circuit Current Setting (Ii)50 A
Setting Range1.6 ... 2.5 A
Rated Operational VoltageMain Circuit 690 V AC
Rated Operational Current (Ie)2.5 A
Rated Frequency (f)Main Circuit 50 Hz
Main Circuit 60 Hz
Operating Frequency (fsw)0 ... 400 Hz
Rated Impulse Withstand Voltage (Uimp)Main Circuit 6 kV
Rated Insulation Voltage (Ui)690 V
Power Lossat Rated Operating Conditions per Pole 0.6 ... 1.6 W
Number of Poles3P
Conventional Free-air Thermal Current (Ith)Main Circuit 2.5 A
Degree of ProtectionHousing IP20
Main Circuit Terminals IP10
Pollution Degree3
Electrical Durability50000 cycle
Mechanical DurabilityNr. Operations 100000 cycle
Terminal TypeScrew Terminals
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
Tightening TorqueMain Circuit 0.8 ... 1.2 N·m
Wire Stripping LengthMain Circuit 9 mm
Recommended Screw DriverM3.5
Pozidriv 2
Mounting Position1 ... 6
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting DistanceElectrical Conductive Board, Vertical 75 mm
Other Device Same Type, Horizontal 9 mm
Other Device Same Type, Vertical 150 mm
Actuator TypeRotary Handle
Contact Position IndicationON / OFF / TRIP
StandardsIEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
IEC 60335-2-40 A2L
Technical UL/CSA
Short-Circuit Current Rating (SCCR)Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (480Y / 277 V AC) 65 kA
Any UL Listed Fuses or Circuit-Breakers, Tap Conductor Protection in Group Installations (600Y / 347 V AC) 47 kA
Maximum Operating Voltage UL/CSAMain Circuit 600 V AC
Horsepower Rating UL/CSA(220 ... 240 V AC) Single Phase 0.17 Hp
Full Load Amps Motor Use(120 V AC) Single Phase 2.5 A
(220 ... 240 V AC) Single Phase 2.5 A
Locked Rotor Amps(120 V AC) Single Phase 15 A
(220 ... 240 V AC) Single Phase 15 A
Connecting Capacity Main Circuit UL/CSAFlexible 1/2x 16-12 AWG
Stranded 1/2x 16-12 AWG
Tightening Torque UL/CSAMain Circuit 10 ... 12 in·lb
Environmental
Ambient Air TemperatureAround the Enclosure 0 ... +40 °C
Operation -25 ... +70 °C
Operation Compensated -25 ... +60 °C
Storage -50 ... +80 °C
Ambient Air Temperature CompensationYes
Maximum Operating Altitude Permissible2000 m
Resistance to Shock acc. to IEC 60068-2-2711 ms Pulse 25g
Resistance to Vibrations5g 3 ... 150 Hz
Material Compliance
Conflict Minerals Reporting Template (CMRT)9AKK108467A5658
REACH Declaration1SAA963005-4502
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA2CMT2023-006539
WEEE B2C / B2BBusiness To Business
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
End Of Life Disassembling Instructions1SAC200332H0001
Environmental Product Declaration - EPD1SAC200360H0001
1SAC200385H0001
Certificates and Declarations
A2L Certificate – IEC1SAA963000-4601
CB Certificate1SAA963002-2002
1SAA963007-2002
CCC Certificate2024010307654702
2024010307658958
CQC CertificateCQC2010010307387700
CQC2019010307243864
Cut-off Current Characteristic1SAM300518F0001
Declaration of Conformity - CCC2020980307003526
2020980307003041
Declaration of Conformity - CE1SAD101100-3404
Declaration of Conformity - UKCA1SAD201100-3404
KC Certificate1SAA963002-1502
RMRS Certificate1SAA918000-0704
UL CertificateE137861-20090225
Container Information
Package Level 1 Unitsbox 1 piece
Package Level 1 Width92 mm
Package Level 1 Depth / Length95 mm
Package Level 1 Height50 mm
Package Level 1 Gross Weight0.28 kg
Package Level 1 EAN4013614484971
Package Level 2 Unitscarton 40 piece
Package Level 2 Width280 mm
Package Level 2 Depth / Length395 mm
Package Level 2 Height210 mm
Package Level 2 Gross Weight11.586 kg
Package Level 2 EAN4013614487170
External Classifications and Standards
Object Classification CodeF
ETIM 9EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 10EC000228 - Power circuit-breaker for trafo/generator/installation protection
eClassV11.0 : 27370409
UNSPSC39121601
IDEA Granular Category Code (IGCC)4864 >> Enclosed 3 Pole Circuit Breakers
E-Number (Finland)3707274
E-Number (Norway)4364106

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.